5 - 16
MELSEC-Q
5 UTILITY PACKAGE (SW0D5C-QADU-E)
[Explanation of items]
(1) Contents of screen display
Setting item
: The I/O signal or buffer memory names are displayed.
Current value
: The I/O signal status or current value of buffer memory are
monitored.
Setting value
: Select or enter the data to be written during test operation.
(2) Explanation of the command buttons
Current value display
The current value of the selected item is displayed.
(This is used to check text that cannot be displayed in
the current value field. However, in this utility package,
all items can be displayed in the display fields).
Make text file
Creates a file consisting of the screen contents in text file
format.
Start monitor /
Stop monitor
Selects whether or not the current value fields are
monitored.
Select test
Performs a test of the selected item. To select more
than one item, select multiple items while holding down
the Ctrl key.
Close
Closes the screen currently displayed and returns to
the previously displayed screen.
POINT
If the selection test operation is performed while deleting the setting value using the
Delete key (the setting value field is blank), the message "Completed" will be
displayed but write operation will not be performed.
REMARK
The following describes an example where sampling process for the selection test
operation is changed to a 10-time averaging process setting.
(1) Set averaging process in the setting value field for CH Sampling
process/Averaging process setting.
(2) Set number of times in the setting value field for CH Time/number of times
specifying.
(3) Click the setting value field for CH Average time/average number of times
setting to select.
(4) After entering the average number of times, press the Enter key.
At this point, nothing has been written to the A/D conversion module.
(5) Select the setting value fields that were specified in steps 1 to 4 while holding
down the Ctrl key.
(6) Click Select test to execute write operation.
Once writing has been completed, the value that was written will be displayed in
the present value field.
Содержание Q64AD
Страница 11: ...1 2 MELSEC Q 1 OVERVIEW MEMO...
Страница 13: ...2 2 MELSEC Q 2 SYSTEM CONFIGURATION MEMO...
Страница 31: ...3 18 MELSEC Q 3 SPECIFICATIONS MEMO...
Страница 43: ...4 12 MELSEC Q 4 SETUP AND PROCEDURES BEFORE OPERATION MEMO...
Страница 58: ...5 15 MELSEC Q 5 UTILITY PACKAGE SW0D5C QADU E Operating condition setting Offset gain setting 1...
Страница 61: ...5 18 MELSEC Q 5 UTILITY PACKAGE SW0D5C QADU E MEMO...
Страница 67: ...6 6 MELSEC Q 6 PROGRAMMING MEMO...
Страница 76: ...Index 3 MEMO...