3 - 4
MELSEC-Q
3 SPECIFICATIONS
(2) Current input characteristic
A current input characteristic graph is shown in Figure 3.2.
Di
gi
ta
l out
put
val
u
e
Analog input current (mA)
1)
2)
4095
4000
2000
0
–2000
–4000
–96
–4096
–30
–20
–10
0
10
20
30
Analog input practical range
4
Number
Analog input
range setting
Offset value
Gain value
Digital output value 2
Maximum
resolution
1)
4 to 20 mA
4 mA
20 mA
4
A
2)
0 to 20 mA
0 mA
20 mA
0 to 4000
5
A
—
User range setting
1
1
–4000 to 4000
—
Figure 3.2 Current input characteristic
POINT
(1) Do not input an analog input current of more than ± 30 mA. A breakdown may
result due to overheating.
(2) Set the offset/gain values for the user setting range 1 within a range in which
the following conditions are satisfied.
{ (Gain value) – (Offset value) } > 5.5 mA
(3) When an analog value that exceeds the range of the digital output value 2 is
entered, the digital output value will be fixed at the maximum or minimum
value.
• For 0 to 4000, the range for the digital output value is from –96 to 4095.
Содержание Q64AD
Страница 11: ...1 2 MELSEC Q 1 OVERVIEW MEMO...
Страница 13: ...2 2 MELSEC Q 2 SYSTEM CONFIGURATION MEMO...
Страница 31: ...3 18 MELSEC Q 3 SPECIFICATIONS MEMO...
Страница 43: ...4 12 MELSEC Q 4 SETUP AND PROCEDURES BEFORE OPERATION MEMO...
Страница 58: ...5 15 MELSEC Q 5 UTILITY PACKAGE SW0D5C QADU E Operating condition setting Offset gain setting 1...
Страница 61: ...5 18 MELSEC Q 5 UTILITY PACKAGE SW0D5C QADU E MEMO...
Страница 67: ...6 6 MELSEC Q 6 PROGRAMMING MEMO...
Страница 76: ...Index 3 MEMO...