3 - 5
MELSEC-Q
3 SPECIFICATIONS
3.1.3 Accuracy
Accuracy is expressed as a full-scale value.
For example, the accuracy is ± 0.1% ( ± 4 for digital output value) when the module is
used in an ambient temperature of 25 ± 5 °C, and ± 0.3% (± 12 for digital output value)
in an ambient temperature of 0 to 55 °C with temperature drift compensation function.
4000
–4000
Di
g
it
a
l out
p
u
t
va
lu
e
–10 V
0 V
10 V
Analog input value
Range of fluctuation with
respect to the ambient
temperature
Figure 3.3 Accuracy
Содержание Q64AD
Страница 11: ...1 2 MELSEC Q 1 OVERVIEW MEMO...
Страница 13: ...2 2 MELSEC Q 2 SYSTEM CONFIGURATION MEMO...
Страница 31: ...3 18 MELSEC Q 3 SPECIFICATIONS MEMO...
Страница 43: ...4 12 MELSEC Q 4 SETUP AND PROCEDURES BEFORE OPERATION MEMO...
Страница 58: ...5 15 MELSEC Q 5 UTILITY PACKAGE SW0D5C QADU E Operating condition setting Offset gain setting 1...
Страница 61: ...5 18 MELSEC Q 5 UTILITY PACKAGE SW0D5C QADU E MEMO...
Страница 67: ...6 6 MELSEC Q 6 PROGRAMMING MEMO...
Страница 76: ...Index 3 MEMO...