4.6.  Additional refrigerant charge

Refrigerant of 3 kg equivalent to 50 m total extended piping length is already included 
when the outdoor unit is shipped. Thus, if the total extended piping length is 50 m or 
less, there is no need to charge with additional refrigerant.

Calculation of Additional Refrigerant Charge

•  If the total extended piping length exceeds 50 m, calculate the required additional 

refrigerant charge using the procedure shown below.

•  If the calculated additional refrigerant charge is a negative amount, do not charge 

with any refrigerant.

<Additional Charge>

Additional 
refrigerant charge

=

Liquid pipe size 
Total length of
ø9.52 

×

 0.06

+

Liquid pipe size 
Total length of 
ø6.35 

×

 0.024

Refrigerant 
amount for 
outdoor unit

(kg)

(m) 

×

 0.06 (kg/m)

(m) 

×

 0.024 (kg/m)

3.0 kg

<Example>
Outdoor model  :  125
Indoor 1 : 63  A : ø9.52  30 m 

a : ø9.52  15 m

 2 

40 

 

 

   

ø6.35 

10 

m

 3 

25 

 

 

   

ø6.35 

10 

m

 4 

20 

 

 

   

ø6.35 

20 

m

The total length of each liquid line is as follows
ø9.52 : A + a  = 30 + 15  = 45 m
ø6.35 : b + c + d = 10 + 10 + 20 = 40 m
Therefore,
<Calculation example>
Additional refrigerant charge 
= 45 

×

 0.06 + 40 

×

 0.024 – 3.0 = 0.7 kg (rounded up)

4.  Installing the refrigerant piping

5.  Drainage piping work

Outdoor unit drainage pipe connection

When drain piping is necessary, use the drain socket or the drain pan (option).

P125, P140

Drain socket

PAC-SG61DS-E

Drain pan

PAC-SG64DP-E

6.1. Caution

1

  Follow ordinance of your governmental organization for technical standard related 

to electrical equipment, wiring regulations and guidance of each electric power 
company.

2

  Wiring for control (hereinafter referred to as transmission line) shall be (5 cm or 

more) apart from power source wiring so that it is not in

fl

 uenced by electric noise 

from power source wiring. (Do not insert transmission line and power source wire 
in the same conduit.)

3

  Be sure to provide designated grounding work to outdoor unit.

4

  Give some allowance to wiring for electrical part box of indoor and outdoor units, 

because the box is sometimes removed at the time of service work.

5

  Never connect the main power source to terminal block of transmission line. If 

connected, electrical parts will be burnt out.

6

  Use 2-core shield cable for transmission line. If transmission lines of different 

systems are wired with the same multiplecore cable, the resultant poor transmit-
ting and receiving will cause erroneous operations.

6. Electrical work

7

  Only the transmission line speci

fi

 ed should be connected to the terminal block 

for outdoor unit transmission.

 

(Transmission line to be connected with indoor unit : Terminal block TB3 for 
transmission line, Other : Terminal block TB7 for centralized control)

 

Erroneous connection does not allow the system to operate.

8

  In case to connect with the upper class controller or to conduct group operation in 

different refrigerant systems, the control line for transmission is required between 
the outdoor units each other.

 

Connect this control line between the terminal blocks for centralized control. (2-
wire line with no polarity)

 

When conducting group operation in different refrigerant systems without connect-
ing to the upper class controller, replace the insertion of the short circuit connector 
from CN41 of one outdoor unit to CN40.

9

  Group is set by operating the remote controller.

At the conditions 
below:

*   The 

fi

 gure to the left is an example 

only. The stop valve shape, service port 
position, etc., may vary according to the 
model.

* Turn 

section 

A

 only.

  (Do not further tighten sections 

A

 and 

B

 together. )

C

 Charge hose

D

  Service port

Precautions when using the charge valve (Fig.4-8)

Do not tighten the service port too much when installing it, otherwise, the valve core 
could be deformed and become loose, causing a gas leak.
After positioning section 

B

 in the desired direction, turn section 

A

 only and tighten 

it.
Do not further tighten sections 

A

 and 

B

 together after tightening section 

A

.

 Warning:

When installing the unit, securely connect the refrigerant pipes before starting 
the compressor.

Fig. 4-8

Содержание PUMY-P125

Страница 1: ...ir Conditioners PUMY P125 140VHMS PUMY P125 140YHMS INSTALLATION MANUAL For safe and correct use read this manual and the indoor unit installation manual thoroughly before installing the air condition...

Страница 2: ...ent to securing product safety Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly installed water leakag...

Страница 3: ...refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tool...

Страница 4: ...portation handles of the outdoor unit to transport the unit If the unit is carried from the bottom hands or fingers may be pinched 2 3 Outline dimensions Outdoor unit Fig 2 1 Constraints on indoor uni...

Страница 5: ...ir outlet guides for upward airflow 2 4 2 When installing multiple outdoor units Leave 10 mm space or more between the units 1 Obstacles at rear only Fig 2 8 2 Obstacles at rear and above only Fig 2 9...

Страница 6: ...it may fall down and cause damage or injuries The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes typhoons or strong winds An incor rectly...

Страница 7: ...ak them Bend radius of 100 mm to 150 mm is sufficient Make sure the pipes do not contact the compressor Abnormal noise or vibration may result 1 Pipes must be connected starting from the indoor unit F...

Страница 8: ...re does not decrease 2 Pressurize to 1 5 MPa 15 kgf cm2 G wait five minutes and make sure the pressure does not decrease 3 Pressurize to 4 15 MPa 41 5 kgf cm2 G and measure the surrounding tem peratur...

Страница 9: ...electrical part box of indoor and outdoor units because the box is sometimes removed at the time of service work 5 Never connect the main power source to terminal block of transmission line If connect...

Страница 10: ...50 M NET R C Main 101 to 150 Set at an IC Main address within the same group plus 100 M NET R C Sub 151 to 200 Set at an IC Main address within the same group plus 150 MA R C Unnecessary address sett...

Страница 11: ...S TB3 M1M2 S M1M2 S A B M1M2 M1M2 S M1M2 S F A B C E D TB7 IC 51 TB15 TB15 TB15 MA 01 IC TB5 03 IC TB5 TB5 02 IC TB5 04 IC 05 IC 07 IC 06 L1 MA MA MA OC 53 OC 1 m4 3 Power Supply Unit L3 L 7 L4 m 3 1...

Страница 12: ...fuse with correct capacity Using fuse and wire or copper wire with too large capacity may cause a malfunction of unit or fire IMPORTANT Make sure that the current leakage breaker is one compatible wit...

Страница 13: ...or the compressor will start to warm up after power is supplied After supplying power for the times indicated below measure the insulation resistance again The insulation resistance drops due to accum...

Страница 14: ......

Страница 15: ......

Страница 16: ...BH79D109H05 Printed in Japan Please be sure to put the contact address telephone number on this manual before handing it to the customer...

Отзывы: