background image

8

4.  Installing the refrigerant piping

4.3.  Refrigerant piping (Fig. 4-4)

Remove the service panel 

D

 (three screws) and the front piping cover 

A

 (two screws) 

and rear piping cover 

B

 (two screws).

1

  Perform refrigerant piping connections for the indoor/outdoor unit when the outdoor 

unit’s stop valve is completely closed.

2

  Vacuum-purge air from the indoor unit and the connection piping.

3

  After connecting the refrigerant pipes, check the connected pipes and the indoor 

unit for gas leaks. (Refer to 4.4 Refrigerant pipe airtight testing method)

4

  Vacuumize the refrigerant lines through the service port of the liquid and gas stop 

valves. And then open the stop valves completely (for both the liquid and gas stop 
valves). This will completely connect the refrigerant lines of the indoor and outdoor 
units.

•  If the stop valves are left closed and the unit is operated, the compressor and 

control valves will be damaged.

•  Use a leak detector or soapy water to check for gas leaks at the pipe connec-

tion sections of the outdoor unit.

•  Do not use the refrigerant from the unit to purge air from the refrigerant 

lines.

•  After the valve work is completed, tighten the valve caps to the correct torque: 

20 to 25 N·m (200 to 250 kgf·cm).

  Failure to replace and tighten the caps may result in refrigerant leakage. In 

addition, do not damage the insides of the valve caps as they act as a seal to 
prevent refrigerant leakage.

5

 Use sealant to seal the ends of the thermal insulation around the pipe connection 

sections to prevent water from entering the thermal insulation.

4.4.  Refrigerant pipe airtight testing method

(1) Connect the testing tools.

•  Make sure the stop valves 

A

 

B

 are closed and do not open them.

•  Add pressure to the refrigerant lines through the service port 

C

 of the liquid 

stop valve 

and the gas stop valve 

B

.

(2) Do not add pressure to the speci

fi

 ed pressure all at once; add pressure little by lit-

tle.

1

 Pressurize to 0.5 MPa (5 kgf/cm

2

G), wait 

fi

 ve minutes, and make sure the  

pressure does not decrease.

2

 Pressurize to 1.5 MPa (15 kgf/cm

2

G), wait 

fi

 ve minutes, and make sure the 

pressure does not decrease.

3

 Pressurize to 4.15 MPa (41.5 kgf/cm

2

G) and measure the surrounding tem-

perature and refrigerant pressure.

(3) If the speci

fi

 ed pressure holds for about one day and does not decrease, the pipes 

have passed the test and there are no leaks.

•  If the surrounding temperature changes by 1°C, the pressure will change by 

about 0.01 MPa (0.1 kgf/cm

2

G). Make the necessary corrections.

(4) If the pressure decreases in steps (2) or (3), there is a gas leak. Look for the source 

of the gas leak.

4.5.  Stop valve opening method

(1) Gas side (Fig. 4-6)

1

  Remove the cap, pull the handle toward you and rotate 1/4 turn in a counterclock-

wise direction to open.

2

  Make sure that the stop valve is open completely, push in the handle and rotate 

the cap back to its original position.

(2) Liquid side (Fig. 4-7)

1

  Remove the cap and turn the valve rod counterclockwise as far as it will go with 

the use of a 4 mm hexagonal wrench. Stop turning when it hits the stopper.

 

(ø6.35: Approximately 4.5 revolutions) (ø9.52: Approximately 10 revolutions)

2

  Make sure that the stop valve is open completely, push in the handle and rotate 

the cap back to its original position.

A

 Valve

B

 Unit side

C

 Handle

D

 Cap

E

  Local pipe side

A

  Stop valve <Liquid side>

B

  Stop valve <Gas side>

C

 Service port

D

 Open/Close section

E

 Local pipe

F

  Open position side

G

 Service port

H

 Wrench hole

I

 Refrigerant 

fl

 ow direction

Refrigerant pipes are protectively wrapped
•  The pipes can be protectively wrapped up to a diameter of ø90 before or after con-

necting the pipes. Cut out the knockout in the pipe cover following the groove and 
wrap the pipes.

Pipe inlet gap
•  Use putty or sealant to seal the pipe inlet around the pipes so that no gaps re-

main.

  (If the gaps are not closed, noise may be emitted or water and dust will enter the 

unit and breakdown may result.)

Fig. 4-5

Fig. 4-4

A

  Front piping cover

B

 Piping cover

C

 Stop valve

Service panel

E

  Bend radius : 100 mm - 150 mm

(1) 

1

2

Fig. 4-7

Fig. 4-6

(2) 

1

2

F

  Sealed, same way for gas side

G

 Pipe cover

H

  Do not use a wrench here.

  Refrigerant leakage may result.

I

  Use two wrenches here.

Содержание PUMY-P125

Страница 1: ...ir Conditioners PUMY P125 140VHMS PUMY P125 140YHMS INSTALLATION MANUAL For safe and correct use read this manual and the indoor unit installation manual thoroughly before installing the air condition...

Страница 2: ...ent to securing product safety Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly installed water leakag...

Страница 3: ...refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tool...

Страница 4: ...portation handles of the outdoor unit to transport the unit If the unit is carried from the bottom hands or fingers may be pinched 2 3 Outline dimensions Outdoor unit Fig 2 1 Constraints on indoor uni...

Страница 5: ...ir outlet guides for upward airflow 2 4 2 When installing multiple outdoor units Leave 10 mm space or more between the units 1 Obstacles at rear only Fig 2 8 2 Obstacles at rear and above only Fig 2 9...

Страница 6: ...it may fall down and cause damage or injuries The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes typhoons or strong winds An incor rectly...

Страница 7: ...ak them Bend radius of 100 mm to 150 mm is sufficient Make sure the pipes do not contact the compressor Abnormal noise or vibration may result 1 Pipes must be connected starting from the indoor unit F...

Страница 8: ...re does not decrease 2 Pressurize to 1 5 MPa 15 kgf cm2 G wait five minutes and make sure the pressure does not decrease 3 Pressurize to 4 15 MPa 41 5 kgf cm2 G and measure the surrounding tem peratur...

Страница 9: ...electrical part box of indoor and outdoor units because the box is sometimes removed at the time of service work 5 Never connect the main power source to terminal block of transmission line If connect...

Страница 10: ...50 M NET R C Main 101 to 150 Set at an IC Main address within the same group plus 100 M NET R C Sub 151 to 200 Set at an IC Main address within the same group plus 150 MA R C Unnecessary address sett...

Страница 11: ...S TB3 M1M2 S M1M2 S A B M1M2 M1M2 S M1M2 S F A B C E D TB7 IC 51 TB15 TB15 TB15 MA 01 IC TB5 03 IC TB5 TB5 02 IC TB5 04 IC 05 IC 07 IC 06 L1 MA MA MA OC 53 OC 1 m4 3 Power Supply Unit L3 L 7 L4 m 3 1...

Страница 12: ...fuse with correct capacity Using fuse and wire or copper wire with too large capacity may cause a malfunction of unit or fire IMPORTANT Make sure that the current leakage breaker is one compatible wit...

Страница 13: ...or the compressor will start to warm up after power is supplied After supplying power for the times indicated below measure the insulation resistance again The insulation resistance drops due to accum...

Страница 14: ......

Страница 15: ......

Страница 16: ...BH79D109H05 Printed in Japan Please be sure to put the contact address telephone number on this manual before handing it to the customer...

Отзывы: