1.  Use a separate power supply for the outdoor unit and indoor unit.
2.  Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
3.  The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage drops.
 

Make sure the power-supply voltage does not drop more than 10%.

4. Speci

fi

 c wiring requirements should adhere to the wiring regulations of the region.

5.  Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed 

fl

 exible cord (design 60245 IEC57). For example, 

use wiring such as YZW.

6.  Install an earth longer than other cables.

 Warning:

•  Be sure to use speci

fi

 ed wires to connect so that no external force is imparted to terminal connections. If connections are not 

fi

 xed 

fi

 rmly, it may cause heat-

ing or 

fi

 re.

•  Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.

 Caution:

•  Some installation site may require attachment of an earth leakage breaker. If no earth leakage breaker is installed, it may cause an electric shock.
•  Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large capacity may cause a malfunction 

of unit or 

fi

 re.

IMPORTANT
Make sure that the current leakage breaker is one compatible with higher harmonics.
Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter.
The use of an inadequate breaker can cause the incorrect operation of inverter.

Never splice the power cable or the indoor-outdoor connection cable, otherwise it may result in a smoke, a 

fi

 re or communication failure.

Indoor unit

V1

V2

Type 1

PLFY-VBM, PMFY-VBM, PEFY-VMS,
PCFY-VKM, PKFY-VHM, PKFY-VKM

18.6

2.4

Type 2

PEFY-VMA

38

1.6

Type 3

PEFY-VMHS

13.8

4.8

Others

Other indoor unit

0

0

C : Multiple of tripping current at tripping time 0.01s
Please pick up "C" from the tripping characteristic of the breaker.

<Example of "F2" calculation> 
*Condition  PEFY-VMS × 4 + PEFY-VMA × 1, C = 8 (refer to right sample chart)

F2  = 18.6 × 4/8  +  38 × 1/8

=  14.05 

 16A breaker  (Tripping current = 8 × 16A at 0.01s)

*3 Current sensitivity is calculated using the following formula. 

G1 =  V2 × (Quantity of Type1) + V2 × (Quantity of Type2) + V2 × (Quantity of Type3) + V2 × (Quantity of Others)

+ V3 × (Wire length[km])

G1

Current sensitivity

30 or less

30 mA  0.1sec or less

100 or less

100 mA  0.1sec or less

Wire thickness

V3

1.5 mm²

48

2.5 mm²

56

4.0 mm²

66

6000

600

60

10

1

0.1

0.01

1

2

3

4

6 8

C

10

20

Sample chart

Rated Tripping current (x)

T

ripping T

ime 

[s]

SAMPLE

6. Electrical work

Содержание PUMY-P125

Страница 1: ...ir Conditioners PUMY P125 140VHMS PUMY P125 140YHMS INSTALLATION MANUAL For safe and correct use read this manual and the indoor unit installation manual thoroughly before installing the air condition...

Страница 2: ...ent to securing product safety Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly installed water leakag...

Страница 3: ...refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tool...

Страница 4: ...portation handles of the outdoor unit to transport the unit If the unit is carried from the bottom hands or fingers may be pinched 2 3 Outline dimensions Outdoor unit Fig 2 1 Constraints on indoor uni...

Страница 5: ...ir outlet guides for upward airflow 2 4 2 When installing multiple outdoor units Leave 10 mm space or more between the units 1 Obstacles at rear only Fig 2 8 2 Obstacles at rear and above only Fig 2 9...

Страница 6: ...it may fall down and cause damage or injuries The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes typhoons or strong winds An incor rectly...

Страница 7: ...ak them Bend radius of 100 mm to 150 mm is sufficient Make sure the pipes do not contact the compressor Abnormal noise or vibration may result 1 Pipes must be connected starting from the indoor unit F...

Страница 8: ...re does not decrease 2 Pressurize to 1 5 MPa 15 kgf cm2 G wait five minutes and make sure the pressure does not decrease 3 Pressurize to 4 15 MPa 41 5 kgf cm2 G and measure the surrounding tem peratur...

Страница 9: ...electrical part box of indoor and outdoor units because the box is sometimes removed at the time of service work 5 Never connect the main power source to terminal block of transmission line If connect...

Страница 10: ...50 M NET R C Main 101 to 150 Set at an IC Main address within the same group plus 100 M NET R C Sub 151 to 200 Set at an IC Main address within the same group plus 150 MA R C Unnecessary address sett...

Страница 11: ...S TB3 M1M2 S M1M2 S A B M1M2 M1M2 S M1M2 S F A B C E D TB7 IC 51 TB15 TB15 TB15 MA 01 IC TB5 03 IC TB5 TB5 02 IC TB5 04 IC 05 IC 07 IC 06 L1 MA MA MA OC 53 OC 1 m4 3 Power Supply Unit L3 L 7 L4 m 3 1...

Страница 12: ...fuse with correct capacity Using fuse and wire or copper wire with too large capacity may cause a malfunction of unit or fire IMPORTANT Make sure that the current leakage breaker is one compatible wit...

Страница 13: ...or the compressor will start to warm up after power is supplied After supplying power for the times indicated below measure the insulation resistance again The insulation resistance drops due to accum...

Страница 14: ......

Страница 15: ......

Страница 16: ...BH79D109H05 Printed in Japan Please be sure to put the contact address telephone number on this manual before handing it to the customer...

Отзывы: