10

2

 

Wiring examples

•  Controller name, symbol and allowable number of controllers.

Name

Symbol

Allowable number of controllers

Outdoor unit controller

OC

Indoor unit controller

IC

1 to 8 controllers for 1 OC

Remote controller

RC

(M-NET)

Maximum of 16 controllers 
for 1 OC

RC

MA

Maximum of 2 per group

6.3.  Wiring transmission cables

1

 

Types of control cables

1.  Wiring transmission cables
•  Types of transmission cables: Shielding wire CVVS, CPEVS or MVVS
•  Cable diameter: More than 1.25 mm

2

 

•  Maximum wiring length: Within 200 m

2.  M-NET Remote control cables

Kind of remote control cable

Shielding wire CVVS, CPEVS or MVVS

Cable diameter 

0.5 to 1.25 mm

Remarks 

When 10 m is exceeded, use cable with the same 
speci

fi

 cations as transmission line cables.

Example of a group operation system with multiple outdoor units (Shielding wires and address setting are nec-
essary.)

<Examples of Transmission Cable Wiring>

 

M-NET Remote Controller (Fig. 6-2)

 

MA Remote Controller (Fig. 6-3)

<Wiring Method and Address Settings>
a.  Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well for all OC-OC, and IC-IC wiring intervals.
b.  Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3) of each outdoor unit (OC) to terminals M1, M2 

and terminal S on the transmission cable block of the indoor unit (IC).

c.  Connect terminals 1 (M1) and 2 (M2) on the transmission cable terminal block of the indoor unit (IC) that has the most recent address within the same group to the terminal 

block on the remote controller (RC).

d.  Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit (OC).
e.  The jumper connector CN41 on the control panel does not change.
f.   Connect shield ground of the indoor units transmission line to the shield (S) terminal of (TB3) and also connect (S) terminal to screw 

C

 or 

D

 using attached lead wire. 

 

Connect shield ground of the line between outdoor units and the central control system transmission line to the shield (S) terminal of (TB7). 

g.  Set the address setting switch as follows.

Unit

Range

Setting Method

IC (Main)

01 to 50

Use the most recent address within the same group of  indoor units

IC (Sub) 

01 to 50

Use an address, other than that of the IC (Main) from among the units within the same group of indoor units. This must 
be in sequence with the IC (Main)

Outdoor Unit

51 to 100

Use the most recent address of all the indoor units plus 50
*  The address automatically becomes “100” if it is set as “01 - 50”.

M-NET R/C (Main)

101 to 150

Set at an IC (Main) address within the same group plus 100

M-NET R/C (Sub)

151 to 200

Set at an IC (Main) address within the same group plus 150

MA R/C

Unnecessary address setting (Necessary main/sub setting)

h.  The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical power has been turned on.

<Permissible Lengths>

1

 

M-NET Remote controller

•  Max length via outdoor units: 

L1+L2+L3+L4 and L1+L2+L3+L5 and L1+L2+L6+L7   500 m (1.25 mm2 or more)

•  Max transmission cable length:  L1 and L3+L4 and L3+L5 and L6 and L2+L6 and L7   200 m (1.25 mm2 or more)
•  Remote controller cable length: 

1, 

2, 

2+

3, 

4    10 m (0.5 to 1.25 mm2)

 

 If the length exceeds 10 m, use a 1.25 mm2 shielded wire.  The length of this section (L8) should be included in the calculation of the 
maximum length and overall length.

2

 

MA Remote controller

•  Max length via outdoor unit (M-NET cable): L1+L2+L3+L4 and L1+L2+L6+L7   500 m (1.25 mm2 or more)
•  Max transmission cable length (M-NET cable): L1 and L3+L4 and L6 and L2+L6 and L7   200 m (1.25 mm2 or more)
•  Remote controller cable length: m1 and m1+m2 +m3 and m1+m2+m3+m4    200 m (0.3 to 1.25 mm2)

6. Electrical work

M1

S

M2

B

A

C

M1

S

M2

L

N

TB3

TB1

TB7

D

3.  MA Remote control cables

Kind of remote control cable

2-core cable (unshielded) 

Cable diameter

0.3 to 1.25 mm

 *

* Connected with simple remote controller.

A

 : Power source

B

 : Transmission line

C

 : Screw on the electrical component box

D

 : Screw on the electrical component box

6.2.  Control box and connecting position of wiring
  

(Fig. 6-1)

1.  Connect the indoor unit transmission line to transmission terminal block (TB3), or 

connect the wiring between outdoor units or the wiring with the centralized control 
system to the centralized control terminal block (TB7).

 

When using shielded wiring, connect shield ground of the indoor unit transmission 
line to the screw (

C

 or 

D

) and connect shield ground of the line between outdoor 

units and the central control system transmission line to the shield (S) terminal of 
the centralized control terminal block (TB7) shield (S) terminal. In addition, in the 
case of outdoor units whose power supply connector CN41 has been replaced 
by CN40, the shield terminal (S) of terminal block (TB7) of the centralized control 
system should also be connected to the screw 

C

 or 

using attached lead wire.

2.  Conduit mounting plates (ø27) are being provided. Pass the power supply and 

transmission wires through the appropriate knock-out holes, then remove the 
knock-out piece from the bottom of the terminal box and connect the wires.

3.  Fix power source wiring to terminal box by using buffer bushing for tensile force 

(PG connection or the like).

Fig. 6-1

M1

S

M2

B

A

C

M1

S

M2

L1 L2 L3 N

TB3

TB7

D

<PUMY-P·VHMS>

<PUMY-P·YHMS>

Содержание PUMY-P125

Страница 1: ...ir Conditioners PUMY P125 140VHMS PUMY P125 140YHMS INSTALLATION MANUAL For safe and correct use read this manual and the indoor unit installation manual thoroughly before installing the air condition...

Страница 2: ...ent to securing product safety Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly installed water leakag...

Страница 3: ...refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tool...

Страница 4: ...portation handles of the outdoor unit to transport the unit If the unit is carried from the bottom hands or fingers may be pinched 2 3 Outline dimensions Outdoor unit Fig 2 1 Constraints on indoor uni...

Страница 5: ...ir outlet guides for upward airflow 2 4 2 When installing multiple outdoor units Leave 10 mm space or more between the units 1 Obstacles at rear only Fig 2 8 2 Obstacles at rear and above only Fig 2 9...

Страница 6: ...it may fall down and cause damage or injuries The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes typhoons or strong winds An incor rectly...

Страница 7: ...ak them Bend radius of 100 mm to 150 mm is sufficient Make sure the pipes do not contact the compressor Abnormal noise or vibration may result 1 Pipes must be connected starting from the indoor unit F...

Страница 8: ...re does not decrease 2 Pressurize to 1 5 MPa 15 kgf cm2 G wait five minutes and make sure the pressure does not decrease 3 Pressurize to 4 15 MPa 41 5 kgf cm2 G and measure the surrounding tem peratur...

Страница 9: ...electrical part box of indoor and outdoor units because the box is sometimes removed at the time of service work 5 Never connect the main power source to terminal block of transmission line If connect...

Страница 10: ...50 M NET R C Main 101 to 150 Set at an IC Main address within the same group plus 100 M NET R C Sub 151 to 200 Set at an IC Main address within the same group plus 150 MA R C Unnecessary address sett...

Страница 11: ...S TB3 M1M2 S M1M2 S A B M1M2 M1M2 S M1M2 S F A B C E D TB7 IC 51 TB15 TB15 TB15 MA 01 IC TB5 03 IC TB5 TB5 02 IC TB5 04 IC 05 IC 07 IC 06 L1 MA MA MA OC 53 OC 1 m4 3 Power Supply Unit L3 L 7 L4 m 3 1...

Страница 12: ...fuse with correct capacity Using fuse and wire or copper wire with too large capacity may cause a malfunction of unit or fire IMPORTANT Make sure that the current leakage breaker is one compatible wit...

Страница 13: ...or the compressor will start to warm up after power is supplied After supplying power for the times indicated below measure the insulation resistance again The insulation resistance drops due to accum...

Страница 14: ......

Страница 15: ......

Страница 16: ...BH79D109H05 Printed in Japan Please be sure to put the contact address telephone number on this manual before handing it to the customer...

Отзывы: