SW2 setting
Display detail
Explanation for display
Unit
The black square (■) indicates a switch position.
75
1
ON
2 3 4 5 6
Liquid temperature (TH3) on error occur
-
ring
−40 to 90
−40 to 90
(When the coil thermistor detects 0
:
or below, “-”
and temperature are displayed by turns.)
(Example) When −15
:
;
0.5 s 0.5 s 2 s
:
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Compressor operating current on error
occurring
0 to 20
Error history (1) (latest)
Alternate display of abnormal unit
number and code
Error history (2)
Alternate display of error unit number
and code
3 to 217 <SP125/140>
−52 to 221 <SP100>
(When the temperature is 100
:
or more, the
hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 130
:
;
0.5 s 0.5 s 2 s
:
A
Code
display
Code
display
0 to 20
When no error history,
“ 0 ” and “– –” are displayed by turns.
When no error history,
“ 0 ” and “– –” are displayed by turns.
1
ON
2 3 4 5 6
Thermo ON time
0 to 999
Test run elapsed time
0 to 120
0 to 999
(When it is 100 minutes or more, the hundreds digit,
tens digit and ones digit are displayed by turns.)
(Example) When 245 minutes;
0.5 s 0.5 s 2 s
0 to 120
(When it is 100 minutes or more, the hundreds digit,
tens digit and ones digit are displayed by turns.)
(Example) When 105 minutes;
0.5 s 0.5 s 2 s
Minute
Minute
15
1
30
2
45
1
05
1
ON
2 3 4 5 6
Code
display
Operation mode on error occurring
Operation mode of when operation stops due to
error is displayed by setting SW2 like below.
1
ON
2 3 4 5 6
(SW2)
Comp. surface temperature (TH32)
3 to 217 <SP125/140>
−52 to 221 <SP100>
OCH566A