106
OPERATING PROCEDURE
PHOTOS
12. Removing the compressor (MC)
(1) Remove the service panel. (See Figure 1)
(2) Remove the top panel. (See Figure 1)
(3) Remove the cover panel (front). (See Figure 2)
(4) Remove the cover panel (rear).(See Figure 2)
(5) Remove the electrical parts box. (Refer to procedure 3)
(6) Remove the valve bed. (Refer to procedure 8)
(7) Remove the side panel (R). (Refer to procedure 8)
(8) Remove front panel fixing screws (2 of 4 x 10, and 4 of 5 x
12) and remove the front panel. (See Photo 1)
(9) Remove 2 separator fixing screws (4 × 10) and remove
the separator.
(10) Remove the soundproof cover for compressor.
(11) Recover refrigerant.
(12) Remove the welded pipe of motor for compressor inlet
and outlet and then remove the compressor.
(13) Remove the 3 points of the motor for compressor fixing
nut using a spanner or a adjustable wrench.
Note: Recover refrigerant without spreading it in the air.
13. Removing the accumulator
(1) Remove the service panel. (See Figure 1)
(2) Remove the top panel. (See Figure 1)
(3) Remove the cover panel (front). (Refer to procedure 12)
(4) Remove the cover panel (rear). (Refer to procedure 12)
(5) Remove the electrical parts box. (Refer to procedure 3)
(6) Remove the valve bed. (Refer to procedure 8)
(7) Remove the side panel (R). (Refer to procedure 8)
(8) Recover refrigerant.
(9) Remove welded pipes of accumulator inlet and outlet.
(10) Remove 2 accumulator leg fixing screws (4 × 10).
Note: Recover refrigerant without spreading it in the air.
Photo 12
Accumulator leg
fixing screws
Accumulator
Inlet
Outlet
Separator
Separator fixing
screw
Soundproof
cover for
compressor
Terminal cover
Photo 11
Electrical parts box
Controller circuit
board
(C.B.)
Terminal cover
Cover panel
(Front)
Cover panel fixing screws
Compressor (MC)
Terminal block
(TB1)
Valve bed
OCH566A