85
11-1-2. Selecting functions using the wired remote controller <PAC-YT52CRA>
Make the following settings for Mr. SLIM if necessary.
Set the functions of each indoor unit from the remote controller, as required. The functions of each indoor unit can be
.
Set the functions by selecting the necessary items from “Table 1. Function selection”, “Table 3. Available functions and settings
for PLA-BA” or “Table 4. Available functions and settings for PEAD-SP•JA(L)” in the previous pages.
selected only from the remote controller.
<Function Selection>
<Function Selection Flow>
First grasp the function selection flow. The following describes setting of “Thermistor selection” of Table 1 as an example.
(For the actual setting procedure, see <Setting procedure>
1
to
.)
0
1
Check the function selection set contents.
2
Switch to the FUNCTION SELECTION mode*.
(Press and simultaneously in the remote
controller OFF state.)
3
Refrigerant address specification
→
00 (Outdoor unit specification)
(Unnecessary for single refrigerant system)
4
Unit address No. specification
(Buttons
and )
→
00 (Indoor unit specification)
5
Register (Press button .)
6
Mode No. Selection
→
02 (Thermistor selection)
7
Setting No. selection
→
3 (Built-in sensor on the remote controller)
8
Register (Press button .)
(Specified indoor unit
→
Fan operation)
End?
Ending function display*
(Press buttons and simultaneously.)
Change
refrigerant
address and unit
address No.?
Yes
No
Yes
No
A
B
9
0
C
D
D
C
D
C
B
,
C
D
A
(Buttons
and )
B
,
C
D
A
<Setting Procedure>
(Set only when change is necessary.)
Check the set contents of each mode. When the set contents of a mode were changed by function selection, the functions
Check the set contents as described in steps to and change the setting based on the entries in the Table 1 check field.
For the initial settings, refer to the indoor unit installation manual.
of that mode also change.
2
7
1
Set the remote controller to Off.
Press and hold down the
and the
buttons (for modes 15 to 28, add the
B
time for 2 seconds or longer.
“ (FUNCTION)” blinks for a while, then the remote controller display changes to the display shown below.
.
Refrigerant address
display
D
C
2
Set the outdoor unit refrigerant address No.
When the
B
and
C
buttons are pressed, the refrigerant address No. decreases and increases
Set it to the refrigerant address No. whose function you want to select.
(This step is unnecessary for single refrigerant system.)
.
.
3
between 00 and 15.
If the remote controller enters the OFF state after the “ (FUNCTION)” and room temperature displays “
” have
flashes for 2 seconds, communication is probably abnormal. Make sure there are no noise sources near the transmission line.
Note: If you make a mistake during operation, end function selection by step and repeat selection from step
0
2
.
Set the indoor unit address No.
Press the
button. The unit address No. display “– –” flashes.
When the
and
C
buttons are pressed, the unit address No. changes in the order of
00↔
01
↔
02
↔
03
↔
04
↔
AL. Set it to the unit address No. of the indoor unit for which functions you want to set.
.
.
Unit address No.
display
4
D
B
1. When setting mode 1 to 6 or 15 to 22, set the unit address No. to “00”.
2. When setting modes 7 to 14 or 23 to 28:
- When setting for each indoor unit, set the unit address No. to “01-04”.
- When batch setting for all indoor units, set the unit address No. to “AL”.
Notes:
*For modes 15 and higher,
press
B
,
C
and
D
simultaneously.
Modes 01 to 14 can be activated
by pressing buttons
C
and
D
simultaneously, and modes 15 to
28 by pressing buttons
B
,
C
and
D
simultaneously.
at the same
.
)
OCH566A