Installation instructions

3. Installation of outdoor unit

Connection between indoor and outdoor unit

Don’t  make  wrong  connection. The  air  conditioner  can’t  operate 

normally in case of wrong connection.

Tighten the screws to avoid looseness.

Pull the wires slightly to verify whether they are tightened.

Fix the service board of outdoor unit well. Otherwise, fire and electric shock 

may result from entry of dust and moisture.

4.Complete  indoor/outdoor  unit  connection  and  perform 

test run

First, align with the center, tighten the pipe nut with hand until you 

can’t proceed.

Refer to the following torque table, use two wrenches to tighten the 

indoor unit side connection pipe connector. Take care not to tighten 

it excessively to avoid damaging the flared part. 

Heat insulation and wrapping band

Pipes  and  valves  connected  at  side  of  indoor  unit  should  be  heat 

insulated.

All pipes starting from the outdoor unit’s pipe entrance shall be wrapped 

with band 

E

.

As the same connection with that of indoor unit, connect the pipe to 

the outdoor unit stop valve (two or three-way) pipe connector.

4-2 Vacuumizing and leak detection test

The mounting surface of the air conditioner should be solid enough 

to bear the weight. The bearing capacity shall not be lower than 

actually born weight (at least 200kg/m2).

The mounting surface is decorated with wooden, metallic or non-

metallic  structure.  Corresponding  measures  like  reinforcement, 

support  and  anti-vibration  shall  be  taken  in  case  of  insufficient 

strength.

Installation rack shall be such a fixture that the air conditioner can 

be fixed securely on the mounting surface.

Confirm the diameter and depth of the mounting hole for the fixture 

based on hardness of the mounting surface material, select applicable 

expansion bolt to ensure unit’s stability, firmness and reliability.

Try to avoid rainy days, windy and snowy days as well as thundery 

days during installation. If necessary, relevant measures shall be 

taken to protect people from injury.

·

Connect  the  wires  from  the  indoor  unit  to  the  terminal  block 

correctly.

Take care not to enable the wires to contact pipe.

·

·

·
·

·

·

·

·

·

Indoor unit piping

Connect liquid and gas pipes to the unit.

·

·

Outdoor unit connection

Tighten the connector with the same torque as that of indoor unit by 

torque wrench or common wrench.

·

·
·

Fix the end of band 

E

 with tape.

If the pipe goes through ceiling, toilet or other locations with high 

temperature and high humidity, please wrap the pipe with commercially 

available heat insulated band to avoid condensation.

50

   

Note

   

Note

   

Note

When manifold gauge is recommended to be used

Remove the stop valve;s service cap at the gas.pipe of outdoor unit 

(Vacuumizing can't be done without removing the cap)

Connect the refrigerant pipe(liquidnd gas) between the indoor and out door unit

Connect  the  manifold  valve  with  gauge  and  manifold  gauge  to  the  stop 

valve's service port at the gas pipe of outdoor unit

Run the manifold gauge(vacuumize the pipe over 15 minutes)

Check the vacuum with the manifold valve with gauge, close the valve and stop the pump.

Remove the manifold valve with gauge from the stop valve service port quickly.

Open all the stop valves at liquid and gas pipes, or performance reduction or failure may result.

It's unnecessary to add refrigerant if pipe 

length is within the scope.

It's necessary to add proper refrigerant 

if pipe length exceeds the scops

Screw the service cap securely.

Screw the caps of two stop valves securely.

Make a leakage detection test.

Vacuumizing

Stop valvev

Liquid pipe

hexagon

wrench

Gas pipe

Cap

Stop valve

Service port

Manifold valve 

with gauge

Connection 

pipe

Manifold gauge

4-1 Piping connection

When installing the unit, securely connect the refrigerant pipes 

before starting the compressor.

  

!

WARNING

·

Unscrew terminal screws

Terminal block

Line

Be sure to use this wire clip to fix indoor/outdoor unit’s 

connection wire 

A

 in good order.

Fixed screw

A

Pipe diameter

Torque tightened

mm

6.35
9.52
12.7

Inch

1/4
3/8
1/2

N

·

m

13.7-17.7
34.3-41.2
49.0-56.4

kgf

·

cm

140-180
350-420
500-575

Содержание MSZ-YK09VA-H1

Страница 1: ...imer operation OFF TIMER ON TIMER When the air conditioner is not used for a long time Maintenance Front panel cleaning Filter Cleaning Please check the following items before connecting a serviceman...

Страница 2: ...1 2 5...

Страница 3: ...80 2 2...

Страница 4: ...3...

Страница 5: ...4 1 5 4 1 1 10 2 3 50cm 50cm 50cm...

Страница 6: ...30 30 24 2 5 6 7 LR03 1 2 24 1 E O SW...

Страница 7: ...I FEEL 15 1 1 2 25 25 23 24 26 2 2 2 2 6...

Страница 8: ...1 1 20 24 1 2 7 70 60 75 55 70...

Страница 9: ...4 150 o 150 20 50 30 8...

Страница 10: ...9 3 4 8...

Страница 11: ...10 1 2 3 4...

Страница 12: ...1 1 2 1 4 1 4 0 5 1 1 2 2 3 4 11 4 4 2 4 2 4...

Страница 13: ...30 28 17 30 1 2 5 6 1 2 12...

Страница 14: ...10 10 10 10 1 2 13 2 2...

Страница 15: ...3 3 4 3 1 2 3 1 2 15 14...

Страница 16: ...15 1 2 3 50 2 S MAC 621YK 2 S MAC 621YK 5 2 S MAC 621YK 4 2 S MAC 621YK...

Страница 17: ...3 16 1 1 2 10 10...

Страница 18: ...17 1...

Страница 19: ...18 2 R410A C1220 R410A R410A R410A R410A R22 R410A GB17790 2 1 R410A 2 2 R410A 6 35 0 8 6 35 0 8 MSZ YK09 12VA H1 MSZ YK18VA H1 9 52 0 8 12 7 0 8...

Страница 20: ...3 1 1m 3m 3 2 3m 3 19 1...

Страница 21: ...1 4 25 7 1 1 5 2 1 1 1 1 1 1 1 1 1 1 1 1 1 6 35 12 8 10 R410A 6 MSZ 30 20 9 52 12 7 YK18 H1 1 1 2 E 5 C H D 2 1 4 3 170 10 65 161 140 A B C D E G F 1 2 3 4 5...

Страница 22: ...2 2 1 2 2 C 2 3 0 65 1 35 1 5 YZW 2 4 45 11 20 11 26 65 C H 1 1 65 C 350 315 5 5 2 10 21 100 65 1 1 1 4 50cm AAA 1 5V 21 4 25 2 1 65 161 170 140 A...

Страница 23: ...2 5 I FEEL CONTROL I FEEL CONTROL 10 3 2 6 5 MSZ N L 22 S1 S2 S3 S1 S2 S3 A 5 4 CN151 CN111 CN112 CN110 JR07 MSZ YK09 12VA H1 MSZ YK18VA H1 3...

Страница 24: ...C 1 1 5 1 3 1 2 3 4 1 B 1 2 7 1 2 3 1 2 3 4 5 E 5 E 5 5 5 1 1 F 23...

Страница 25: ...3 4 4 1 2 3 E E 4 2 200kg m2 24 15 6 35 9 52 12 7 1 4 3 8 1 2 N m 13 7 17 7 34 3 41 2 49 0 56 4 kgf cm 140 180 350 420 500 575 A A...

Страница 26: ...13 7 17 7 19 6 29 4 140 180 200 300 30 30 30 24 30 3 4 4 5 5 1 3 10 5 2 5 3 3 40 4 3 MSZ 25 R410A 6 35 9 52 12 7 YK18 H1 E O SW...

Страница 27: ...26 0 05 0MPa 0 5 0kgf cm 25 0 05 0MPa 3 30 5 4...

Страница 28: ...ectly with pesticide disinfector and combustible spraying material Fire and distortion may result If the installation stand is antiquated don t ignore it The unit may tumble and cause injury Standing...

Страница 29: ...upply High speed revolving fan may cause injury in operation Change two new batteries of the same type Combination of new and old batteries can cause heating leakage or explosion If the battery fluid...

Страница 30: ...let Air outlet Drainage hose Piping Air inlet Display section Remote controller receiver MOVE EYE sensor Emergency operation switch Horizontal vane Front panel Heat exchanger Air inlet Display section...

Страница 31: ...t 3 The details of SLIDE SWITCH Each press of the Forward button increases one minute Each press of the Backward button decreases one minute If you press and hold down the button for a long time the s...

Страница 32: ...roperly When the indoor unit is controlled by the remote controller the unit will automatically remember the operation mode set temperature and fan speed If power cut or power off occurs during operat...

Страница 33: ...operate following the same set points with the previous operation Once the set points are set the operation will not vary with the room temperature If you don t like the set points you can press butt...

Страница 34: ...n the air that is to say the humidity is high Humidity is concerned with temperature and airflow Generally speaking a humidity of 60 75 in summer and that of 55 70 in winter shall be the ideal conditi...

Страница 35: ...re the room and floor wall tempera tures to automatically adjust to the set temperature by estimating the temperature actually perceived by a person inside the room sensible temperature Advantages The...

Страница 36: ...ture is the lowest in the room If AREA setting is set to AUTO in cooling operation the indoor unit automatically delivers cool air to the area where the floor wall temperature is the highest in the ro...

Страница 37: ...flow velocity press the button Lo Me Hi SHi Auto How to select fan speed Principle of the air conditioner The greater the air volume the more effective the energy saving and the higher the noise The a...

Страница 38: ...position Set position When the air is hot Start of heating Horizontal position After the air conditioner starts to operate the vane stops in horizontal position Once the temperature of the airflow fro...

Страница 39: ...emperature is as follows Sleep mode cooling 28 Sleep mode heating 17 Thetemperaturesetpriortopressing button about 30 minutes Set temperature in Sleep mode Set temperature in Sleep mode In Cooling mod...

Страница 40: ...not set timer operation will be disabled Note If main power supply is switched off or power failure occurs during timer operation timer setting will be canceled 2 1 2 Enable this mode to enjoy healthy...

Страница 41: ...ore cleaning Switch off the power supply and remove the power plug Warning When cleaning the unit you have to stop unit operation by removing the power plug and switch off the power supply Because fan...

Страница 42: ...all the PM2 5 Electrostatic Filter Install PM2 5 Electrostatic Filter into Air Filter by the arrows PM2 5 Electrostatic Filter must be limited by the hook of Air Filter 2 S MAC 621YK Keeping 5 Switch...

Страница 43: ...ion and remove power plug or turn off the power supply Otherwise there is a risk of damaging the electrical part in the air conditioner A crack is heard The noise results from the expansion shrinkage...

Страница 44: ...be connected properly as specified and connecting terminals for the cables be fixed firmly without being affected by external force Poor connection or fixture may cause fire Installation shall be imp...

Страница 45: ...tlention for R410A refrigerant systems 2 1 Using R410A refigerant air conditioners Caution Caution Use C1220 copper phosphorus for copper and copper alloy seamless pipes to connect the refrigerant pip...

Страница 46: ...operation noise or vibration you shall install the unit in a solid frame A place where there is no leaked combustible gas When installing the unit in a higher place you have to fix the foot of the un...

Страница 47: ...gure below refrigerant pipe is used to connect indoor outdoor unit Connector Stop valve Service port 6 35 Indoor unit Outdoor unit Indoor unit Installation plate Screw 4 25mm Battery No 7 Remote contr...

Страница 48: ...furniture will be wet and contaminated by water drop from the unit Installation dimension Always use the wall hole sleeve C which prevents the connection wires between indoor and outdoor unit from co...

Страница 49: ...tart automatically according to the memory 10 seconds after operating the remote controller the operation setting will be reserved When the Auto ON OFF timer is activated the timer setting will be can...

Страница 50: ...drainage pipe shall be connected tilting downwards figure 1 Don t connect the pipe as shown in figure2 3 If it is not long enough for the drainage hose installed at the indoor unit you can use the ho...

Страница 51: ...ecessary relevant measures shall be taken to protect people from injury Connect the wires from the indoor unit to the terminal block correctly Take care not to enable the wires to contact pipe Indoor...

Страница 52: ...in operation 5 Relocation and maintenance after installation Set the horizontal vane to position No 3 page 36 before installing the front panel Insert the bottom side of front panel under the horizont...

Страница 53: ...ion manual for detailed instructions on test run NOTE When the pressure gauge reaches 0 05 0MPa gauge approximately 0 5 0kgf cm fully close the stop valve on gas pipe and stop the operation of the air...

Страница 54: ...CTRIC CORPORATION TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN SHANGHAI MITSUBISHI ELECTRIC SHANGLING AIR CONDITIONER AND ELECTRIC APPLIANCE CO LTD NO 505 NAN YANGJING RD PUDONG NEW ARE...

Отзывы: