Installation instructions

1.Installation diagram and accessory

(Before installation, users are advised to verify the amount 

of parts based on the packing list)

Part name

Guarantee

Amout

1
1
5
2
1
1

Outdoor 

unit

Outdoor unit

A

B

C

D

E

G

Limit

Pipe length

Height difference

Amount of bends

 

12m

8m

10 pieces

Adjustment of refrigerant

···

If the pipe length exceeds the scope in 

the table below, refrigerant (R410A) should be supplemented. (Filling 

refrigerant to the outdoor unit with refrigerant shall be subject to the 

following pipe length.)

Note: Excessive extension of piping will cause cooling and heating 

capacity to decrease.

Pipe length

Over 6 meters

Type

MSZ (Inverter)

Dosage of refrigerant

30g

×

(pipe length (m)-6)

F

Packing list 

Installation No.

Indoor 

Unit

1
2

3

4

5

Flared joint

The unit is equipped with flared joints at indoor/outdoor unit side.

As  shown  in  the  figure  below,  refrigerant  pipe  is  used  to  connect 

indoor/outdoor unit.

Connector 

Stop valve

Service port 

Φ6.35

Indoor unit

Outdoor 

unit

Indoor unit

Installation plate

Screw 4

×

25mm

Battery (No.7)
Remote controller
Felt strap

Operating and

installing instructions

Connection cable

Connection pipe

Wall hole sleeve

Wall hole cover

Pipe strap

Extension

drainage hose

Putty 

1

Part name

Installation No.

Amout

Outdoor 

unit

1
1
1
1
1
1

1

H

Drain Plug

1

·

·

46

1
1

·

·

Note:

(1)  Don't  use  the  drainage  pipe 

connector  and  rubber  stopper 

in cold areas. Failure may result 

from drainage freezing.

(1) Select a drain hole in the base 

for  draining  and  connect  the 

drainage pipe connector to the 

hole.

(2) Connect the drainage pipe to the 

connector.  Keep  the  drainage 

pipe to tilt downsards to make a 

smooth draining.

Steps for installing drainage pipe

65mm or more,161 mm or more for left 

and left rear piping (use pad).

140mm or 

more

1 7 0 mm 

or more

100mm or more

100mm or more

200mm or more

350mm or more

※ 

This components need to be purchased.

Φ9.52

Φ12.7(YK18)-H1

E

5

C

H

D

2

1

4

3

10mm or more

Содержание MSZ-YK09VA-H1

Страница 1: ...imer operation OFF TIMER ON TIMER When the air conditioner is not used for a long time Maintenance Front panel cleaning Filter Cleaning Please check the following items before connecting a serviceman...

Страница 2: ...1 2 5...

Страница 3: ...80 2 2...

Страница 4: ...3...

Страница 5: ...4 1 5 4 1 1 10 2 3 50cm 50cm 50cm...

Страница 6: ...30 30 24 2 5 6 7 LR03 1 2 24 1 E O SW...

Страница 7: ...I FEEL 15 1 1 2 25 25 23 24 26 2 2 2 2 6...

Страница 8: ...1 1 20 24 1 2 7 70 60 75 55 70...

Страница 9: ...4 150 o 150 20 50 30 8...

Страница 10: ...9 3 4 8...

Страница 11: ...10 1 2 3 4...

Страница 12: ...1 1 2 1 4 1 4 0 5 1 1 2 2 3 4 11 4 4 2 4 2 4...

Страница 13: ...30 28 17 30 1 2 5 6 1 2 12...

Страница 14: ...10 10 10 10 1 2 13 2 2...

Страница 15: ...3 3 4 3 1 2 3 1 2 15 14...

Страница 16: ...15 1 2 3 50 2 S MAC 621YK 2 S MAC 621YK 5 2 S MAC 621YK 4 2 S MAC 621YK...

Страница 17: ...3 16 1 1 2 10 10...

Страница 18: ...17 1...

Страница 19: ...18 2 R410A C1220 R410A R410A R410A R410A R22 R410A GB17790 2 1 R410A 2 2 R410A 6 35 0 8 6 35 0 8 MSZ YK09 12VA H1 MSZ YK18VA H1 9 52 0 8 12 7 0 8...

Страница 20: ...3 1 1m 3m 3 2 3m 3 19 1...

Страница 21: ...1 4 25 7 1 1 5 2 1 1 1 1 1 1 1 1 1 1 1 1 1 6 35 12 8 10 R410A 6 MSZ 30 20 9 52 12 7 YK18 H1 1 1 2 E 5 C H D 2 1 4 3 170 10 65 161 140 A B C D E G F 1 2 3 4 5...

Страница 22: ...2 2 1 2 2 C 2 3 0 65 1 35 1 5 YZW 2 4 45 11 20 11 26 65 C H 1 1 65 C 350 315 5 5 2 10 21 100 65 1 1 1 4 50cm AAA 1 5V 21 4 25 2 1 65 161 170 140 A...

Страница 23: ...2 5 I FEEL CONTROL I FEEL CONTROL 10 3 2 6 5 MSZ N L 22 S1 S2 S3 S1 S2 S3 A 5 4 CN151 CN111 CN112 CN110 JR07 MSZ YK09 12VA H1 MSZ YK18VA H1 3...

Страница 24: ...C 1 1 5 1 3 1 2 3 4 1 B 1 2 7 1 2 3 1 2 3 4 5 E 5 E 5 5 5 1 1 F 23...

Страница 25: ...3 4 4 1 2 3 E E 4 2 200kg m2 24 15 6 35 9 52 12 7 1 4 3 8 1 2 N m 13 7 17 7 34 3 41 2 49 0 56 4 kgf cm 140 180 350 420 500 575 A A...

Страница 26: ...13 7 17 7 19 6 29 4 140 180 200 300 30 30 30 24 30 3 4 4 5 5 1 3 10 5 2 5 3 3 40 4 3 MSZ 25 R410A 6 35 9 52 12 7 YK18 H1 E O SW...

Страница 27: ...26 0 05 0MPa 0 5 0kgf cm 25 0 05 0MPa 3 30 5 4...

Страница 28: ...ectly with pesticide disinfector and combustible spraying material Fire and distortion may result If the installation stand is antiquated don t ignore it The unit may tumble and cause injury Standing...

Страница 29: ...upply High speed revolving fan may cause injury in operation Change two new batteries of the same type Combination of new and old batteries can cause heating leakage or explosion If the battery fluid...

Страница 30: ...let Air outlet Drainage hose Piping Air inlet Display section Remote controller receiver MOVE EYE sensor Emergency operation switch Horizontal vane Front panel Heat exchanger Air inlet Display section...

Страница 31: ...t 3 The details of SLIDE SWITCH Each press of the Forward button increases one minute Each press of the Backward button decreases one minute If you press and hold down the button for a long time the s...

Страница 32: ...roperly When the indoor unit is controlled by the remote controller the unit will automatically remember the operation mode set temperature and fan speed If power cut or power off occurs during operat...

Страница 33: ...operate following the same set points with the previous operation Once the set points are set the operation will not vary with the room temperature If you don t like the set points you can press butt...

Страница 34: ...n the air that is to say the humidity is high Humidity is concerned with temperature and airflow Generally speaking a humidity of 60 75 in summer and that of 55 70 in winter shall be the ideal conditi...

Страница 35: ...re the room and floor wall tempera tures to automatically adjust to the set temperature by estimating the temperature actually perceived by a person inside the room sensible temperature Advantages The...

Страница 36: ...ture is the lowest in the room If AREA setting is set to AUTO in cooling operation the indoor unit automatically delivers cool air to the area where the floor wall temperature is the highest in the ro...

Страница 37: ...flow velocity press the button Lo Me Hi SHi Auto How to select fan speed Principle of the air conditioner The greater the air volume the more effective the energy saving and the higher the noise The a...

Страница 38: ...position Set position When the air is hot Start of heating Horizontal position After the air conditioner starts to operate the vane stops in horizontal position Once the temperature of the airflow fro...

Страница 39: ...emperature is as follows Sleep mode cooling 28 Sleep mode heating 17 Thetemperaturesetpriortopressing button about 30 minutes Set temperature in Sleep mode Set temperature in Sleep mode In Cooling mod...

Страница 40: ...not set timer operation will be disabled Note If main power supply is switched off or power failure occurs during timer operation timer setting will be canceled 2 1 2 Enable this mode to enjoy healthy...

Страница 41: ...ore cleaning Switch off the power supply and remove the power plug Warning When cleaning the unit you have to stop unit operation by removing the power plug and switch off the power supply Because fan...

Страница 42: ...all the PM2 5 Electrostatic Filter Install PM2 5 Electrostatic Filter into Air Filter by the arrows PM2 5 Electrostatic Filter must be limited by the hook of Air Filter 2 S MAC 621YK Keeping 5 Switch...

Страница 43: ...ion and remove power plug or turn off the power supply Otherwise there is a risk of damaging the electrical part in the air conditioner A crack is heard The noise results from the expansion shrinkage...

Страница 44: ...be connected properly as specified and connecting terminals for the cables be fixed firmly without being affected by external force Poor connection or fixture may cause fire Installation shall be imp...

Страница 45: ...tlention for R410A refrigerant systems 2 1 Using R410A refigerant air conditioners Caution Caution Use C1220 copper phosphorus for copper and copper alloy seamless pipes to connect the refrigerant pip...

Страница 46: ...operation noise or vibration you shall install the unit in a solid frame A place where there is no leaked combustible gas When installing the unit in a higher place you have to fix the foot of the un...

Страница 47: ...gure below refrigerant pipe is used to connect indoor outdoor unit Connector Stop valve Service port 6 35 Indoor unit Outdoor unit Indoor unit Installation plate Screw 4 25mm Battery No 7 Remote contr...

Страница 48: ...furniture will be wet and contaminated by water drop from the unit Installation dimension Always use the wall hole sleeve C which prevents the connection wires between indoor and outdoor unit from co...

Страница 49: ...tart automatically according to the memory 10 seconds after operating the remote controller the operation setting will be reserved When the Auto ON OFF timer is activated the timer setting will be can...

Страница 50: ...drainage pipe shall be connected tilting downwards figure 1 Don t connect the pipe as shown in figure2 3 If it is not long enough for the drainage hose installed at the indoor unit you can use the ho...

Страница 51: ...ecessary relevant measures shall be taken to protect people from injury Connect the wires from the indoor unit to the terminal block correctly Take care not to enable the wires to contact pipe Indoor...

Страница 52: ...in operation 5 Relocation and maintenance after installation Set the horizontal vane to position No 3 page 36 before installing the front panel Insert the bottom side of front panel under the horizont...

Страница 53: ...ion manual for detailed instructions on test run NOTE When the pressure gauge reaches 0 05 0MPa gauge approximately 0 5 0kgf cm fully close the stop valve on gas pipe and stop the operation of the air...

Страница 54: ...CTRIC CORPORATION TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN SHANGHAI MITSUBISHI ELECTRIC SHANGLING AIR CONDITIONER AND ELECTRIC APPLIANCE CO LTD NO 505 NAN YANGJING RD PUDONG NEW ARE...

Отзывы: