background image

90

o

p

0.5

o

ø

A

R0.4~R0.8

45

op

 2

o

6

4.2. Connecting pipes (Fig. 4-1)

•   When commercially available copper pipes are used, wrap liquid and gas pipes 

with  commercially  available  insulation  materials  (heat-resistant  to  100°C  or 
more, thickness of 12 mm or more).

•   Be sure to separate thermal insulation for gas and liquid refrigerant pipes.
•   The  indoor  parts  of  the  drain  pipe  should  be  wrapped  with  polyethylene  foam 

insulation materials (speci

Þ

 c gravity of 0.03, thickness of 9 mm or more).

•   Apply thin layer of refrigerant oil to pipe and joint seating surface before tighten-

ing 

ß

 are nut. 

A

•   Use 2 wrenches to tighten piping connections. 

B

•   Use leak detector or soapy water to check for gas leaks after connections are 

completed.

•   Apply refrigerating machine oil over the entire 

ß

 are seat surface. 

C

•   Use the 

ß

 are nuts for the following pipe size. 

D

HRP71, 100, 125

HRP200

Gas side

Pipe size (mm)

[

15.88

[

25.4

Liquid side

Pipe size (mm)

[

9.52

[

9.52

•   When bending the pipes, be careful not to break them. Bend radii of 100 mm to 

150 mm are suf

Þ

 cient.

•   Make sure the pipes do not contact the compressor. Abnormal noise or vibration 

may result.

1

 Pipes must be connected starting from the indoor unit.

  Flare nuts must be tightened with a torque wrench.

2

  Flare the liquid pipes and gas pipes and apply a thin layer of refrigeration oil (Ap-

plied on site).

•   When usual pipe sealing is used, refer to Table 1 for 

ß

 aring of R410A refrigerant 

pipes.

  The size adjustment gauge can be used to con

Þ

 rm A measurements.

A

 (Fig. 4-1)

Copper pipe O.D.

(mm)

Flare dimensions

øA dimensions (mm)

ø6.35

8.7 - 9.1

ø9.52

12.8 - 13.2

ø12.7

16.2 - 16.6

ø15.88

19.3 - 19.7

ø19.05

23.6 - 24.0

B

 (Fig. 4-1)

Copper pipe O.D. 

(mm)

Flare nut O.D. 

(mm)

Tightening torque 

(N·m)

ø6.35

17

14 - 18

ø6.35

22

34 - 42

ø9.52

22

34 - 42

ø12.7

26

49 - 61

ø12.7

29

68 - 82

ø15.88

29

68 - 82

ø15.88

36

100 - 120

ø19.05

36

100 - 120

A

  Flare cutting dimensions

B

  Flare nut tightening torque

A

B

C

D

A

  Die

B

  Copper pipe

A

B

Fig. 4-1

Fig. 4-2

A

Table 1 (Fig. 4-2)

Copper pipe O.D. 

(mm)

A (mm)

Flare tool for R410A

Flare tool for R22·R407C

Clutch type

ø6.35 (1/4")

0 - 0.5

1.0 - 1.5

ø9.52 (3/8")

0 - 0.5

1.0 - 1.5

ø12.7 (1/2")

0 - 0.5

1.0 - 1.5

ø15.88 (5/8")

0 - 0.5

1.0 - 1.5

ø19.05 (3/4")

0 - 0.5

1.0 - 1.5

3

 Use the following procedure for connecting the gas-side piping. (Fig.4-3) (HRP200)

1  Braze the 

E

 Joint pipe provided to the outdoor unit using locally procured braz-

ing materials and 

C

 Local piping without oxygen.

2  Connect the 

E

 Joint pipe to the gas-side Stop valve.

    Use 2 wrenches to tighten the 

ß

 are nut.

     * If order is reversed, refrigerant leak occurs because of the part damaging by 

brazinig  

Þ

 re.

4. Installing the refrigerant piping

Fig. 4-4

A

Front piping cover

B

Piping cover

C

Stop valve

D

Service panel

E

Bend radius : 100mm -150mm

4.3. Refrigerant piping (Fig. 4-4)

Remove the service panel 

D

 (3 screws) and the front piping cover 

A

 (2 screws) 

and rear piping cover 

B

 (2 screws: HRP71-125) (4 screws: HRP200).

1

  Perform refrigerant piping connections for the indoor/outdoor unit when the out-

door unit’s stop valve is completely closed.

2

  Vacuum-purge air from the indoor unit and the connection piping.

3

  After connecting the refrigerant pipes, check the connected pipes and the indoor 

unit for gas leaks. (Refer to 4.4 Refrigerant pipe airtight testing method)

4

  A high-performance vacuum pump is used at the stop valve service port to main-

tain a vacuum for an adequate time (at least one hour after reaching –101 kPa 
(5 Torr)) in order to vacuum dry the inside of the pipes. Always check the degree 
of vacuum at the gauge manifold. If there is any moisture left in the pipe, the de-
gree of vacuum is sometimes not reached with short-time vacuum application. 

   After vacuum drying, completely open the stop valves (both liquid and gas) for 

the outdoor unit. This completely links the indoor and outdoor refrigerant circuits.

  •   If the vacuum drying is inadequate, air and water vapor remain in the refriger-

ant circuits and can cause abnormal rise of high pressure, abnormal drop of 
low pressure, deterioration of the refrigerating machine oil due to moisture, etc.

  •   If the stop valves are left closed and the unit is operated, the compressor and 

control valves will be damaged.

  •   Use a leak detector or soapy water to check for gas leaks at the pipe connec-

tion sections of the outdoor unit.

  •   Do not use the refrigerant from the unit to purge air from the refrigerant lines.
  •   After the valve work is completed, tighten the valve caps to the correct torque: 

20 to 25 N·m (200 to 250 kgf·cm).

     Failure to replace and tighten the caps may result in refrigerant leakage. In 

addition, do not damage the insides of the valve caps as they act as a seal to 
prevent refrigerant leakage.

5

  Use sealant to seal the ends of the thermal insulation around the pipe connec-

tion sections to prevent water from entering the thermal insulation.

Fig. 4-3

A

Stop valve

B

Seal section

C

Local piping

D

Double spanner section

E

Joint pipe

F

Pipe cover

01̲RG79D564H02̲EN.indd   6

2009/08/26   8:34:11

Содержание Mr. Slim PUHZ-HRP-HA2

Страница 1: ...ees deze handleiding en de installatiehandleiding van het binnenapparaat zorgvuldig door voordat u met het installeren van de airconditioner begint MANUAL DE INSTALACI N Para un uso correcto y seguro...

Страница 2: ...ctly overheating or re may result The terminal block cover panel of the outdoor unit must be rmly attached If the cover panel is mounted incorrectly and dust and moisture enter the unit electric shock...

Страница 3: ...uch the pipes burns or frostbite may result After stopping operation be sure to wait at least ve minutes before turn ing off the main power switch Otherwise water leakage or breakdown may result 1 5 U...

Страница 4: ...e space as shown Do not install the optional air outlet guides for upward air ow 3 Obstacles at front only Fig 2 14 When using the optional air outlet guides the clearance is 1000 mm or more 4 Obstacl...

Страница 5: ...ible Vent Max 30 Set deep in the ground 600 600 Min 360 175 175 Min 10 950 25 330 370 4 Installing the refrigerant piping 4 1 Precautions for devices that use R410A refrigerant Refer to 1 5 for precau...

Страница 6: ...C Local piping without oxygen 2 Connect the E Joint pipe to the gas side Stop valve Use 2 wrenches to tighten the are nut If order is reversed refrigerant leak occurs because of the part damaging by...

Страница 7: ...to its original position Refrigerant pipes are protectively wrapped The pipes can be protectively wrapped up to a diameter of 90 before or after connecting the pipes Cut out the knockout in the pipe...

Страница 8: ...The existing pipe thickness does not meet speci cations or the pipes are damaged Fig 4 9 Indoor unit Outdoor unit Main piping Branch piping Multi distribution pipe option Outdoor unit HRP200 A 9 52 65...

Страница 9: ...efrigerant piping HRP71 100 125 HRP200 Drain socket PAC SG61DS E Drain pan PAC SG64DP E PAC SH97DP E 5 Drainage piping work Outdoor unit drainage pipe connection When drain piping is necessary use the...

Страница 10: ...ire which is longer than the other cords so that it will not become disconnected when tension is applied A Control Outdoor Unit 3 poles isolator Power supply Isolator A Control Indoor Unit Warning In...

Страница 11: ...operation Starting operation immediately after turning on the main power switch can result in severe damage to internal parts Keep the power switch turned on during the operational season The followi...

Страница 12: ...the unit is stopped How ever even if the unit is stopped and the SWP switch is set to ON less than three minutes after the compressor stops the refrigerant collecting operation cannot be performed Wai...

Страница 13: ...door unit C Master remote controller D Subordinate remote controller E Standard 1 1 Refrigerant address 00 F Simultaneous twin Refrigerant address 01 G Simultaneous triple Refrigerant address 02 E SW...

Отзывы: