background image

4

2. Installation location 

2.4. Ventilation and service space

2.4.1. Windy location installation

When  installing  the  outdoor  unit  on  a  rooftop  or  other  location  unprotected  from 
the wind, situate the air outlet of the unit so that it is not directly exposed to strong 
winds.  Strong  wind  entering  the  air  outlet  may  impede  the  normal  airflow  and  a 
malfunction may result.
The following shows three examples of precautions against strong winds.

1

  Face the air outlet towards the nearest available wall about 50 cm away from the 

wall. (Fig. 2-3)

2

  Install an optional air guide if the unit is installed in a location where strong winds 

from a typhoon, etc. may directly enter the air outlet. (Fig. 2-4)

 

A

   Air outlet guide

3

  Position the unit so that the air outlet blows perpendicularly to the seasonal wind 

direction, if possible. (Fig. 2-5)

 

B

   Wind direction

Fig. 2-4

Fig. 2-3

A

B

Fig. 2-5

2.4.2. When installing a single outdoor unit (Refer to the last page)

Minimum dimensions are as follows, except for Max., meaning Maximum dimen-
sions, indicated.
Refer to the 

Þ

 gures for each case.

1

 Obstacles at rear only (Fig. 2-6)

2

 Obstacles at rear and above only (Fig. 2-7)

3

 Obstacles at rear and sides only (Fig. 2-8)

4

 Obstacles at front only (Fig. 2-9)

 

*   When using the optional air outlet guides, the clearance is 500 mm or more.

5

 Obstacles at front and rear only (Fig. 2-10)

 

*   When using the optional air outlet guides, the clearance is 500 mm or more.

6

 Obstacles at rear, sides, and above only (Fig. 2-11)

 

•   Do not install the optional air outlet guides for upward air

ß

 ow.

2.4.3. When installing multiple outdoor units (Refer to the last page)

Leave 10 mm space or more between the units.

1

 Obstacles at rear only (Fig. 2-12)

2

 Obstacles at rear and above only (Fig. 2-13)

 

•   No more than 3 units must be installed side by side. In addition, leave space as shown.

 

•   Do not install the optional air outlet guides for upward air

ß

 ow.

3

 Obstacles at front only (Fig. 2-14)

 

*   When using the optional air outlet guides, the clearance is 1000 mm or more.

4

 Obstacles at front and rear only (Fig. 2-15)

 

*   When using the optional air outlet guides, the clearance is 1000 mm or more.

5

 Single parallel unit arrangement (Fig. 2-16)

 

*   When using the optional air outlet guides installed for upward air

ß

 ow, the clearance is 

 

 

1000 mm or more.

6

 Multiple parallel unit arrangement (Fig. 2-17)

 

*   When using the optional air outlet guides installed for upward air

ß

 ow, the clearance is 

 

 

1500 mm or more.

7

 Stacked unit arrangement (Fig. 2-18)

 

•   The units can be stacked up to 2 units high.

 

•   No more than 2 stacked units must be installed side by side. In addition, leave space as 

shown.

2.2. Choosing the outdoor unit installation location

•   Avoid locations exposed to direct sunlight or other sources of heat.
•   Select  a  location  from  which  noise  emitted  by  the  unit  will  not  inconvenience 

neighbors.

•   Select  a  location  permitting  easy  wiring  and  pipe  access  to  the  power  source 

and indoor unit.

•   Avoid locations where combustible gases may leak, be produced, 

ß

 ow, or accu-

mulate.

•   Note that water may drain from the unit during operation.
•   Select a level location that can bear the weight and vibration of the unit.
•   Avoid locations where the unit can be covered by snow. In areas where heavy 

snow fall is anticipated, special precautions such as raising the installation loca-
tion or installing a hood on the air intake must be taken to prevent the snow from 
blocking the air intake or blowing directly against it. This can reduce the air

ß

 ow 

and a malfunction may result.

•   Avoid locations exposed to oil, steam, or sulfuric gas.
•   Use the transportation handles of the outdoor unit to transport the unit. If the unit 

is carried from the bottom, hands or 

Þ

 ngers may be pinched.

2.3. Outline dimensions (Outdoor unit) (Fig. 2-2)

Fig. 2-2

(

 HRP200

10

50

33

0+

25

1

3

3

8

22

5

60

0

37

0

(

 HRP71,100,125

95

0

33

0+

30

1

3

5

0

17

5

60

0

37

0

01̲RG79D564H02̲EN.indd   4

2009/08/26   8:33:56

Содержание Mr. Slim PUHZ-HRP-HA2

Страница 1: ...ees deze handleiding en de installatiehandleiding van het binnenapparaat zorgvuldig door voordat u met het installeren van de airconditioner begint MANUAL DE INSTALACI N Para un uso correcto y seguro...

Страница 2: ...ctly overheating or re may result The terminal block cover panel of the outdoor unit must be rmly attached If the cover panel is mounted incorrectly and dust and moisture enter the unit electric shock...

Страница 3: ...uch the pipes burns or frostbite may result After stopping operation be sure to wait at least ve minutes before turn ing off the main power switch Otherwise water leakage or breakdown may result 1 5 U...

Страница 4: ...e space as shown Do not install the optional air outlet guides for upward air ow 3 Obstacles at front only Fig 2 14 When using the optional air outlet guides the clearance is 1000 mm or more 4 Obstacl...

Страница 5: ...ible Vent Max 30 Set deep in the ground 600 600 Min 360 175 175 Min 10 950 25 330 370 4 Installing the refrigerant piping 4 1 Precautions for devices that use R410A refrigerant Refer to 1 5 for precau...

Страница 6: ...C Local piping without oxygen 2 Connect the E Joint pipe to the gas side Stop valve Use 2 wrenches to tighten the are nut If order is reversed refrigerant leak occurs because of the part damaging by...

Страница 7: ...to its original position Refrigerant pipes are protectively wrapped The pipes can be protectively wrapped up to a diameter of 90 before or after connecting the pipes Cut out the knockout in the pipe...

Страница 8: ...The existing pipe thickness does not meet speci cations or the pipes are damaged Fig 4 9 Indoor unit Outdoor unit Main piping Branch piping Multi distribution pipe option Outdoor unit HRP200 A 9 52 65...

Страница 9: ...efrigerant piping HRP71 100 125 HRP200 Drain socket PAC SG61DS E Drain pan PAC SG64DP E PAC SH97DP E 5 Drainage piping work Outdoor unit drainage pipe connection When drain piping is necessary use the...

Страница 10: ...ire which is longer than the other cords so that it will not become disconnected when tension is applied A Control Outdoor Unit 3 poles isolator Power supply Isolator A Control Indoor Unit Warning In...

Страница 11: ...operation Starting operation immediately after turning on the main power switch can result in severe damage to internal parts Keep the power switch turned on during the operational season The followi...

Страница 12: ...the unit is stopped How ever even if the unit is stopped and the SWP switch is set to ON less than three minutes after the compressor stops the refrigerant collecting operation cannot be performed Wai...

Страница 13: ...door unit C Master remote controller D Subordinate remote controller E Standard 1 1 Refrigerant address 00 F Simultaneous twin Refrigerant address 01 G Simultaneous triple Refrigerant address 02 E SW...

Отзывы: