6.2. Field electrical wiring

Outdoor unit model

HRP71V

HRP100V

HRP100, 125Y

HRP200Y

Outdoor unit power supply

~/N (single), 50 Hz, 230 V

~/N (single), 50 Hz, 230 V

3N~ (3 ph 4-wires), 

50 Hz, 400 V

3N~ (3 ph 4-wires), 

50 Hz, 400 V

Outdoor unit input capacity Main switch (Breaker)

*1

32 A

40 A

16 A

32 A

Wiring 

Wire No. × 

size (mm

2

)

Outdoor unit power supply

3 × Min. 4

3 × Min. 6

5 × Min. 1.5

5 × Min. 4

Indoor unit-Outdoor unit

*2

3 × 1.5 (Polar)

3 × 1.5 (Polar)

3 × 1.5 (Polar)

Cable length 50m:3×4 (Polar)/

Cable length 80m:3×6 (Polar)

Indoor unit-Outdoor unit earth

*2

1 × Min. 1.5

1 × Min. 1.5

1 × Min. 1.5

1 × Min. 2.5

Remote controller-Indoor unit

*3

2 × 0.3 (Non-polar)

2 × 0.3 (Non-polar)

2 × 0.3 (Non-polar)

2 × 0.3 (Non-polar)

Circuit rating

Outdoor unit L-N (single)
Outdoor unit L1-N, L2-N, L3-N (3 phase)

*4

AC 230 V

AC 230 V

AC 230 V

AC 230 V

Indoor unit-Outdoor unit S1-S2

*4

AC 230 V

AC 230 V

AC 230 V

AC 230 V

Indoor unit-Outdoor unit S2-S3

*4

DC 24 V

DC 24 V

DC 24 V

DC 24 V

Remote controller-Indoor unit

*4

DC 12 V

DC 12 V

DC 12 V

DC 12 V

*1. A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use earth leakage breaker (NV).
*2. (HRP71-125)
 

Max. 45 m

 

If 2.5 mm

2

 used, Max. 50 m

 

If 2.5 mm

2

 used and S3 separated, Max. 80 m

 

(HRP200)

 

Max. 80 m Total Max. including all indoor/indoor connection is 80 m.
• Use one cable for S1 and S2 and another for S3 as shown in the picture.

*3. The 10 m wire is attached in the remote controller accessory.
*4.  The 

Þ

 gures are NOT always against the ground.

 

S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device.

Notes:  1.  Wiring size must comply with the applicable local and national code.
      2.  Power supply cords and Indoor/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed 

ß

 exible cord. (Design 60245 IEC 57)

      3.  Use an earth wire which is longer than the other cords so that it will not become disconnected when tension is applied.

A-Control

Outdoor Unit

3 poles isolator

Power supply

Isolator

A-Control

Indoor Unit

 Warning:

·   In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between 

power line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when 
the power is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.

·   Turn on the main power when the ambient temperature is - 20°C or higher.
·   In below - 20°C condition, it needs at least 4hr stand by to operate in order to warm the electrical parts.

6. Electrical work

INDOOR-OUTDOOR CONNECTING CABLE (HRP200) 

Cross section of cable

Wire size (mm

2

)

Number of wires

Polarity

L (m)*6

Round

2.5

3

Clockwise : S1-S2-S3
*Pay attention to stripe of yellow and green

(30)

*2

Flat

2.5

3

Not applicable
(Because center wire has no cover 

Þ

nish)

Not applicable

*5

Flat

1.5

4

From left to right : S1-Open-S2-S3

(18)

*3

Round

2.5

4

Clockwise : S1-S2-S3-Open
*Connect S1 nad S3 to the opposite angle

(30)

*4

*1 :Power supply cords of appliances shall not be lighter than design 60245 IEC or
     227 IEC.
*2 :In case that cable with stripe of yellow and green is available.
*3 :In case of regular polarity connection (S1-S2-S3), wire size is 1.5 mm

2

.

*4 :In case of regular polarity connection (S1-S2-S3).
*5 :In the 

ß

at cables are connected as this picture, they can be used up to 30 m.

*6 :Mentioned cable length is just a reference value.
     It may be different depending on the condition of installation, humidity or 
     materials, etc.

(3C Flat cable × 2)

Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate connections).
Intermediate connections can lead to communication error if water enters the cables and causes insufficient insulation to ground or a poor electrical contact at the inter-
mediate connection point.

S1

S3

S2

01̲RG79D564H02̲EN.indd   10

2009/08/26   8:34:20

Содержание Mr. Slim PUHZ-HRP-HA2

Страница 1: ...ees deze handleiding en de installatiehandleiding van het binnenapparaat zorgvuldig door voordat u met het installeren van de airconditioner begint MANUAL DE INSTALACI N Para un uso correcto y seguro...

Страница 2: ...ctly overheating or re may result The terminal block cover panel of the outdoor unit must be rmly attached If the cover panel is mounted incorrectly and dust and moisture enter the unit electric shock...

Страница 3: ...uch the pipes burns or frostbite may result After stopping operation be sure to wait at least ve minutes before turn ing off the main power switch Otherwise water leakage or breakdown may result 1 5 U...

Страница 4: ...e space as shown Do not install the optional air outlet guides for upward air ow 3 Obstacles at front only Fig 2 14 When using the optional air outlet guides the clearance is 1000 mm or more 4 Obstacl...

Страница 5: ...ible Vent Max 30 Set deep in the ground 600 600 Min 360 175 175 Min 10 950 25 330 370 4 Installing the refrigerant piping 4 1 Precautions for devices that use R410A refrigerant Refer to 1 5 for precau...

Страница 6: ...C Local piping without oxygen 2 Connect the E Joint pipe to the gas side Stop valve Use 2 wrenches to tighten the are nut If order is reversed refrigerant leak occurs because of the part damaging by...

Страница 7: ...to its original position Refrigerant pipes are protectively wrapped The pipes can be protectively wrapped up to a diameter of 90 before or after connecting the pipes Cut out the knockout in the pipe...

Страница 8: ...The existing pipe thickness does not meet speci cations or the pipes are damaged Fig 4 9 Indoor unit Outdoor unit Main piping Branch piping Multi distribution pipe option Outdoor unit HRP200 A 9 52 65...

Страница 9: ...efrigerant piping HRP71 100 125 HRP200 Drain socket PAC SG61DS E Drain pan PAC SG64DP E PAC SH97DP E 5 Drainage piping work Outdoor unit drainage pipe connection When drain piping is necessary use the...

Страница 10: ...ire which is longer than the other cords so that it will not become disconnected when tension is applied A Control Outdoor Unit 3 poles isolator Power supply Isolator A Control Indoor Unit Warning In...

Страница 11: ...operation Starting operation immediately after turning on the main power switch can result in severe damage to internal parts Keep the power switch turned on during the operational season The followi...

Страница 12: ...the unit is stopped How ever even if the unit is stopped and the SWP switch is set to ON less than three minutes after the compressor stops the refrigerant collecting operation cannot be performed Wai...

Страница 13: ...door unit C Master remote controller D Subordinate remote controller E Standard 1 1 Refrigerant address 00 F Simultaneous twin Refrigerant address 01 G Simultaneous triple Refrigerant address 02 E SW...

Отзывы: