OUTLINES AND DIMENSIONS

377

284

60

(

)

Ceiling hole

Branch duct hole

Drain pipe

connected to VP-25

Ceiling

Grille

Drain hole

Models

 Auto vane

(Air outlet)

Air intake grille

Ceiling

Cut out hole

Cut out hole

Cut out hole

Burring hole pitch

Burring hole pitch

Burring hole

Burring hole

Power supply wire,

Indoor unit/Outdoor unit 

connecting wire entry

Indoor unit/Outdoor unit 

connecting terminal block

Indoor power supply

terminal block(Option part)

Control wire entry

Air intake hole

Air intake hole

Air outlet hole

Air outlet hole

Connect the attached

drain socket.

Keep approximately 

10 to 15mm space

between unit ceiling 

and ceiling slab.

Branch duct hole

Fresh air 

intake hole

Ceiling hole

Suspension bolt pitch

Suspension bolt pitch

Remote controller 

terminal block

Suspension bolt 

M10 or W3/8

(7.5)

(7.5)

605

+35

           - 5

620

DEFROST/STAND BY lamp

Receiver

Operation lamp

In case of standard grille : PLP-6BA / PLP-6BAMD

In case of wireless remote controller : PLP-6BALM Auto grille

Air intake grille up/down distance

Emergency operation 

switch<Cooling>and

Emergency Up/Down switch<Up>

160

160

500

500

597

83

36

950

83

36

950

597

281

17

+5  0

288

35

190

156

105

140

50~70

160

840

150

90

85

77

840

187.5

20~45

860~910

20~45

810

20~45

860~910

20~45

24

160

+

+

+

+

+

+

+

+

+

M

M

M

M

120°

120°

:

175

:

125

167

158

Vane motor

2

1

Drain pump clean hole

and Drain emergency 

drainage hole

130

100

70°

155

350

90

100

100

90

2

1

Refrigerant pipe

···

:

9.52

Flared connection
···3/8 inch

Refrigerant pipe

···

:

15.88

Flared connection

···5/8 inch

PLA-RP100BA3

Detail drawing of fresh air intake hole

Detail connecting of branch duct(Both aspects)

3-

:

2.8

14-

:

2.8

:

150

:

100

Emergency operation 

switch<Heating>and

Emergency Up/Down switch<Down>

In case of auto-grille : PLP-6BAJ

Suspension bolt 

lower edge

170

+

Ceiling

Air intake grille

Max. 4.0m

L.L Filter

Ceiling

Grille

Indoor unit

1500mm

or more

1000mm or more

3000mm or more

1800mm or more

from floor

For high 

attachment

Indoor unit

Obstacle

Floor

Note1. Please choose the grille from a standard grille, auto-grille.

 

2. As for drain pipe, please use VP-25(O.D. 

:

32 PVC TUBE).

 

Drain pump is included.

 

Max. lifting height is 850mm from the ceiling.  

 

3. As for suspension bolt, please use M10 or W3/8.  

 

(Procured at local site)

 

4. Electrical box may be removed for the service purpose.

 

Make sure to slack the electrical wire little bit for control/power wires connection.

 

5. The height of the indoor unit can be adjusted with the grille attached.

 

6. For the installation of the optional high efficiency filter or optional multi-functional casement.

 

1) Requires 440 mm or more space between transom and ceiling for the installation.

 

2) Add 135 mm to the dimensions 

+

 marked on the figure.

 

3) Optional high efficiency filter must be used jointly with optional multi-functional casement.

 

7. When installing the branch ducts, be sure to insulate adequately.

 

Otherwise condensation and dripping may occur.

 

(It becomes the cause of dew drops/Water dew.)

 

8. As for necessary installation/service space, please refer to the left figure. 

PLA-RP100BA3

Unit: mm

Содержание Mr.Slim PLA-RP100BA3

Страница 1: ...SE CRITERION CURVES 8 7 OUTLINES AND DIMENSIONS 9 8 WIRING DIAGRAM 10 9 REFRIGERANT SYSTEM DIAGRAM 11 10 TROUBLESHOOTING 12 11 SPECIAL FUNCTION 27 12 DISASSEMBLY PROCEDURE 36 Indoor unit Model names S...

Страница 2: ...PU H P100YHAR3 UK OC379 PUHZ P100VHA3 UK OCH415 OCB415 PUHZ P200YHA3 OCH424 OCB424 PUHZ HRP100VHA2 PUHZ HRP100YHA2 OCH425 OCB425 PUHZ RP100VKA PUHZ RP100 200YKA OCH451 OCB451 1 TECHNICAL CHANGES PLP...

Страница 3: ...following tools are necessary to use R410A refrigerant Handle tools with care If dirt dust or moisture enters into refrigerant cycle that can cause deterioration of refrigerant oil or malfunction of c...

Страница 4: ...hose Only for R410A Use pressure performance of 5 09MPa G or over 3 Electronic scale 4 Gas leak detector Use the detector for R134a R407C or R410A 5 Adaptor for reverse flow check Attach on vacuum pu...

Страница 5: ...The room temperature display range is 8 39 The display blinks if the temperature is less than 8 or 39 or more Louver display Indicates the action of the swing louver Does not appear if the louver is...

Страница 6: ...lay Displays whether timer is on or off Buttons used to set the hour and minute of the current time and timer settings h and min buttons display display FAN SPEED display indicates which fan speed has...

Страница 7: ...in kg lbs W D H INDOOR UNIT PLA RP100BA3 Service Ref Mode Power supply phase cycle voltage Input Running current External finish Panel Heat exchanger Fan Fan drive No Fan motor output Airflow Low Medi...

Страница 8: ...Medium2 34 Low 32 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 OCTAVE BAND SOUND PRESSURE LEV...

Страница 9: ...pipe 9 52 Flared connection 3 8 inch Refrigerant pipe 15 88 Flared connection 5 8 inch PLA RP100BA3 Detail drawing of fresh air intake hole Detail connecting of branch duct Both aspects 3 2 8 14 2 8...

Страница 10: ...N FAN MOTOR VANE MOTOR DRAIN PUMP DRAIN FLOAT SWITCH TERMINAL BLOCK Indoor unit Power option TERMINAL BLOCK INDOOR OUTDOOR CONNECTING LINE TERMINAL BLOCK REMOTE CONTROLLER TRANSMISSION LINE REACTOR RO...

Страница 11: ...stor TH5 Cond Eva temperature Thermistor TH1 Room temperature Refrigerant flow in cooling Refrigerant flow in heating Strainer 50 Strainer 50 Heat exchanger Refrigerant GAS pipe connection Flare Refri...

Страница 12: ...ting by inferior phenomena The trouble is not reoccurring Logged Not logged Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor poor c...

Страница 13: ...ode is cancelled Procedure 1 Press the CHECK button twice 2 Press the temperature buttons 3 Point the remote controller at the sensor on the indoor unit and press the HOUR button 4 Point the remote co...

Страница 14: ...flashes Check code Number of times Wireless remote controller Wired remote controller 1 P1 Intake sensor error P9 Pipe TH5 sensor error 2 P2 Pipe TH2 sensor error 3 E6 E7 Indoor outdoor unit communica...

Страница 15: ...ction device is not connected Reverse or open phase wiring for the outdoor unit s power terminal block L1 L2 L3 Incorrect wiring between indoor and outdoor units incorrect polarity of S1 S2 S3 Remote...

Страница 16: ...o P1 above 2 Check contact failure of connector CN44 on the indoor controller board Refer to 10 7 Turn the power on and recheck operation after inserting connector again 4 Check pipe liquid temperatur...

Страница 17: ...nge 4 Defective indoor fan motor Fan motor is defective Indoor controller board is defec tive 5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit clogs 8 Bypass...

Страница 18: ...onnecting remote control ler max 2 units When it is not the above mentioned problem of 1 3 4 Diagnose remote controllers a When RC OK is displayed Remote controllers have no problem Turn the power off...

Страница 19: ...uit board to transmit signals Indoor controller board Abnormal if data cannot be read normally from the nonvolatile memory of the indoor controller board 1 Defective indoor controller board 1 Replace...

Страница 20: ...al block S1 and S2 When AC 220 240V is not detected check indoor outdoor unit connecting wire for miswiring When AC 220 240V is detected check 4 below 4 Check the fuse on indoor controller board Check...

Страница 21: ...ontroller Check indoor outdoor unit connecting wire for connection failure 1 Check the connection of remote con troller wires in case of twin triple indoor unit system When 2 or more indoor units are...

Страница 22: ...on it is possible to activate Emergency Operation by using the indoor unit Emergency operation switch SW1 SW2 of the wireless signal receiver board However if the indoor unit microcomputer has failed...

Страница 23: ...tor for i see sensor Option Abnormal Open or short Red Yellow Red Blue Red Orange Red White Connector Normal 300 Measure the resistance between the terminals with a tester At the ambient temperature o...

Страница 24: ...uble of the indoor controller circuit board and fan motor Self check Symptom The indoor fan cannot rotate Wiring contact check Contact of fan motor connector CNMF No No NG Power supply check Remove th...

Страница 25: ...t to the Terminal Block TB4 Indoor outdoor connecting line Between 3 and 5 220 240V AC CN3G Connect to the auto grille controller board CN3G 13V pulse output CNV Vane motor output MV 12V pulse output...

Страница 26: ...he table on the left in the table indicates the jumper wire is dis connected There is no jumper JP1 because these models have the cond eva temperature thermistor TH5 Marks in the table below Jumper wi...

Страница 27: ...in the above table Airflow outreach distance is different depending on indoor units and air volume ceiling height so airflow may not reach the indicated ceiling height as shown in the above table Init...

Страница 28: ...m 3 2 m 3 6 m and 4 0 m These should be used only as a guide You should lower the air intake grille yourself to check the exact distance You cannot stop the operation while the air intake grille is ri...

Страница 29: ...gerant address No can be changed by using the TEMP buttons when the panel displays a or b Every time you press the Mode selection button the target of operation will change as illustrated below 6 Cont...

Страница 30: ...when the intake grille has been raised the set distance but the storage detection switch is not engaged In this case the operation below will be repeated up to 4 times 10 cm down 30 cm up 10 cm down 3...

Страница 31: ...cy switch heating down UK1 Up down machine SW2 Emergency switch cooling up MU1 Motor Up down LS1 Limit switch storage detection LS21 Limit switch tension detection R B Wired remote controller I B Indo...

Страница 32: ...take grille Lower the air intake grille again and check whether the filter is installed in the correct position Lower the air intake grille again and hook on the air intake grille This is normal This...

Страница 33: ...ction with the 1st unit Once the actual room temperature goes down to 4degrees C below set point the 2nd unit stops operation automatically set point set temperature by R C remote controller 4 6 8 sel...

Страница 34: ...ng Initial setting 2nd unit cut in setting Setting contents Setting No Request code No 7 316 No 8 317 No 9 318 Rotation and Back up OFF Normal group control operation Monitoring the request code of cu...

Страница 35: ...rs on the screen when Maintenance monitor is activated The display now allows you to set a request code No 4 Press the TEMP and buttons to select the desired refrigerant address 5 Press the CLOCK and...

Страница 36: ...ove the reactor 4 Removing the indoor controller board I B 1 Remove the air intake grille and the filter See Figure 1 2 Remove the 2 screws from the electrical box cover 3 Disconnect the connectors CN...

Страница 37: ...ve the bell mouth 3 screws See Photo 2 3 Remove the turbo fan nut 4 Pull out the turbo fan 5 Remove the wire cover 3 screws 6 Remove 2 wiring clamps 7 Disconnect the connector of the fan motor CNMF 8...

Страница 38: ...8 Drain pump Hose band Float switch Drain pump assembly fixing screw Drain pump fixing screw Float switch fixing screw 11 Removing the heat exchanger 1 Remove the drain pan See Photo 6 2 Remove the 3...

Страница 39: ...39...

Страница 40: ...8310 JAPAN CCopyright 2009 MITSUBISHI ELECTRIC ENGINEERING CO LTD Distributed in Oct 2009 No OCH459 REVISED EDITION A PDF 7 Distributed in Apr 2009 No OCH459 PDF 7 Made in Japan New publication effect...

Отзывы: