background image

29

[Remarks:]

[Remarks:]

Up/down operation mode

Up/down operation mode

Unit No.

Refrigerant address No.

Individually-specified up/down operation mode

(a) "Unit No." selection 
      display

(c) "Standby for up/down operation" display

(b) "Refrigerant address No." selection display

Operation status display

Mode selection

PAR-21MAA

ON/OFF

FILTER

CHECK

OPERATION

CLEAR

TEST

TEMP.

MENU

BACK

DAY

MONITOR/SET

CLOCK

ON/OFF

If the number of the target air-
conditioner is unknown, go to 4).

In the upper right figure, the air-conditioner 
for which the refrigerant address is "00"
and the unit No. is "1" is currently 
selected.

If the number of the target air-
conditioner is known, go to 5).

1) Ensure that the air-conditioner is not running.

* The up/down operation mode is only available when the 
  air-conditioner is "OFF".

2) Press both the "FILTER" and "Ventilation" buttons simultaneously for 2 seconds or more to enter the up/down 

operation mode.

3) Press the "Ventilation" button. After a while, it will switch to the "individually-specified up/down operation 

mode".

4) If you press the "FILTER" button when the "Unit No." or "Refrigerant address No." is blinking, after a while, 

the up/down airflow direction of the displayed air-conditioner will be switched downward; and the airflow 
direction of the other vents will all be blocked.

5) Select the "Unit No." and "Refrigerant address No.".

"Unit No." and "Refrigerant address No." can be changed by using the "TEMP." buttons (   ) (   ) when the panel 

displays (a) or (b).

Every time you press the "Mode selection" button, the target of operation will change as illustrated below.

6) Continue to press the "Mode selection" button until "Waiting for up/down operation" is displayed.

The following steps are the same as steps 3) - 6) described in the "General Operation" section. Refer to that 
section.

In Step 5) described below, identify the target  

air-conditioner by changing the "Unit No." and 
"Refrigerant address No." and by pressing the "FILTER" 
button to check the up/down airflow direction.

Each pressing action changes the unit No. from "1 - 4" to "0".

   (Unit No. "0" means that all of 1 - 4 are targeted.)

Each press changes the "Refrigerant address" from "0 to 15".

If "Err" is displayed when you press the "FILTER" button to check the target 

air-conditioner, the air-conditioner with that "Unit No." or "Refrigerant 
address" may not exist. Check and set that air-conditioner again.

Down/Up buttons (for selecting 
unit No. and refrigerant 
address)

Button to exit the up/down 
operation mode

Buttons to enter the up/down 
operation mode (Hold them 
down simultaneously for 2 
seconds.)

Up/down operation with the individual specified air-conditioner (when used in combination with Mr. SLIM model)

* Raise or lower the air intake grille of the specific air-conditioner that you select from all that are managed by that remote controller.

"Waiting for up/down operation" display

Ensure that the air-conditioner is not running.

• Otherwise, it may cause an injury or a failure.

Warning:

Содержание Mr.Slim PLA-RP100BA3

Страница 1: ...SE CRITERION CURVES 8 7 OUTLINES AND DIMENSIONS 9 8 WIRING DIAGRAM 10 9 REFRIGERANT SYSTEM DIAGRAM 11 10 TROUBLESHOOTING 12 11 SPECIAL FUNCTION 27 12 DISASSEMBLY PROCEDURE 36 Indoor unit Model names S...

Страница 2: ...PU H P100YHAR3 UK OC379 PUHZ P100VHA3 UK OCH415 OCB415 PUHZ P200YHA3 OCH424 OCB424 PUHZ HRP100VHA2 PUHZ HRP100YHA2 OCH425 OCB425 PUHZ RP100VKA PUHZ RP100 200YKA OCH451 OCB451 1 TECHNICAL CHANGES PLP...

Страница 3: ...following tools are necessary to use R410A refrigerant Handle tools with care If dirt dust or moisture enters into refrigerant cycle that can cause deterioration of refrigerant oil or malfunction of c...

Страница 4: ...hose Only for R410A Use pressure performance of 5 09MPa G or over 3 Electronic scale 4 Gas leak detector Use the detector for R134a R407C or R410A 5 Adaptor for reverse flow check Attach on vacuum pu...

Страница 5: ...The room temperature display range is 8 39 The display blinks if the temperature is less than 8 or 39 or more Louver display Indicates the action of the swing louver Does not appear if the louver is...

Страница 6: ...lay Displays whether timer is on or off Buttons used to set the hour and minute of the current time and timer settings h and min buttons display display FAN SPEED display indicates which fan speed has...

Страница 7: ...in kg lbs W D H INDOOR UNIT PLA RP100BA3 Service Ref Mode Power supply phase cycle voltage Input Running current External finish Panel Heat exchanger Fan Fan drive No Fan motor output Airflow Low Medi...

Страница 8: ...Medium2 34 Low 32 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 OCTAVE BAND SOUND PRESSURE LEV...

Страница 9: ...pipe 9 52 Flared connection 3 8 inch Refrigerant pipe 15 88 Flared connection 5 8 inch PLA RP100BA3 Detail drawing of fresh air intake hole Detail connecting of branch duct Both aspects 3 2 8 14 2 8...

Страница 10: ...N FAN MOTOR VANE MOTOR DRAIN PUMP DRAIN FLOAT SWITCH TERMINAL BLOCK Indoor unit Power option TERMINAL BLOCK INDOOR OUTDOOR CONNECTING LINE TERMINAL BLOCK REMOTE CONTROLLER TRANSMISSION LINE REACTOR RO...

Страница 11: ...stor TH5 Cond Eva temperature Thermistor TH1 Room temperature Refrigerant flow in cooling Refrigerant flow in heating Strainer 50 Strainer 50 Heat exchanger Refrigerant GAS pipe connection Flare Refri...

Страница 12: ...ting by inferior phenomena The trouble is not reoccurring Logged Not logged Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor poor c...

Страница 13: ...ode is cancelled Procedure 1 Press the CHECK button twice 2 Press the temperature buttons 3 Point the remote controller at the sensor on the indoor unit and press the HOUR button 4 Point the remote co...

Страница 14: ...flashes Check code Number of times Wireless remote controller Wired remote controller 1 P1 Intake sensor error P9 Pipe TH5 sensor error 2 P2 Pipe TH2 sensor error 3 E6 E7 Indoor outdoor unit communica...

Страница 15: ...ction device is not connected Reverse or open phase wiring for the outdoor unit s power terminal block L1 L2 L3 Incorrect wiring between indoor and outdoor units incorrect polarity of S1 S2 S3 Remote...

Страница 16: ...o P1 above 2 Check contact failure of connector CN44 on the indoor controller board Refer to 10 7 Turn the power on and recheck operation after inserting connector again 4 Check pipe liquid temperatur...

Страница 17: ...nge 4 Defective indoor fan motor Fan motor is defective Indoor controller board is defec tive 5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit clogs 8 Bypass...

Страница 18: ...onnecting remote control ler max 2 units When it is not the above mentioned problem of 1 3 4 Diagnose remote controllers a When RC OK is displayed Remote controllers have no problem Turn the power off...

Страница 19: ...uit board to transmit signals Indoor controller board Abnormal if data cannot be read normally from the nonvolatile memory of the indoor controller board 1 Defective indoor controller board 1 Replace...

Страница 20: ...al block S1 and S2 When AC 220 240V is not detected check indoor outdoor unit connecting wire for miswiring When AC 220 240V is detected check 4 below 4 Check the fuse on indoor controller board Check...

Страница 21: ...ontroller Check indoor outdoor unit connecting wire for connection failure 1 Check the connection of remote con troller wires in case of twin triple indoor unit system When 2 or more indoor units are...

Страница 22: ...on it is possible to activate Emergency Operation by using the indoor unit Emergency operation switch SW1 SW2 of the wireless signal receiver board However if the indoor unit microcomputer has failed...

Страница 23: ...tor for i see sensor Option Abnormal Open or short Red Yellow Red Blue Red Orange Red White Connector Normal 300 Measure the resistance between the terminals with a tester At the ambient temperature o...

Страница 24: ...uble of the indoor controller circuit board and fan motor Self check Symptom The indoor fan cannot rotate Wiring contact check Contact of fan motor connector CNMF No No NG Power supply check Remove th...

Страница 25: ...t to the Terminal Block TB4 Indoor outdoor connecting line Between 3 and 5 220 240V AC CN3G Connect to the auto grille controller board CN3G 13V pulse output CNV Vane motor output MV 12V pulse output...

Страница 26: ...he table on the left in the table indicates the jumper wire is dis connected There is no jumper JP1 because these models have the cond eva temperature thermistor TH5 Marks in the table below Jumper wi...

Страница 27: ...in the above table Airflow outreach distance is different depending on indoor units and air volume ceiling height so airflow may not reach the indicated ceiling height as shown in the above table Init...

Страница 28: ...m 3 2 m 3 6 m and 4 0 m These should be used only as a guide You should lower the air intake grille yourself to check the exact distance You cannot stop the operation while the air intake grille is ri...

Страница 29: ...gerant address No can be changed by using the TEMP buttons when the panel displays a or b Every time you press the Mode selection button the target of operation will change as illustrated below 6 Cont...

Страница 30: ...when the intake grille has been raised the set distance but the storage detection switch is not engaged In this case the operation below will be repeated up to 4 times 10 cm down 30 cm up 10 cm down 3...

Страница 31: ...cy switch heating down UK1 Up down machine SW2 Emergency switch cooling up MU1 Motor Up down LS1 Limit switch storage detection LS21 Limit switch tension detection R B Wired remote controller I B Indo...

Страница 32: ...take grille Lower the air intake grille again and check whether the filter is installed in the correct position Lower the air intake grille again and hook on the air intake grille This is normal This...

Страница 33: ...ction with the 1st unit Once the actual room temperature goes down to 4degrees C below set point the 2nd unit stops operation automatically set point set temperature by R C remote controller 4 6 8 sel...

Страница 34: ...ng Initial setting 2nd unit cut in setting Setting contents Setting No Request code No 7 316 No 8 317 No 9 318 Rotation and Back up OFF Normal group control operation Monitoring the request code of cu...

Страница 35: ...rs on the screen when Maintenance monitor is activated The display now allows you to set a request code No 4 Press the TEMP and buttons to select the desired refrigerant address 5 Press the CLOCK and...

Страница 36: ...ove the reactor 4 Removing the indoor controller board I B 1 Remove the air intake grille and the filter See Figure 1 2 Remove the 2 screws from the electrical box cover 3 Disconnect the connectors CN...

Страница 37: ...ve the bell mouth 3 screws See Photo 2 3 Remove the turbo fan nut 4 Pull out the turbo fan 5 Remove the wire cover 3 screws 6 Remove 2 wiring clamps 7 Disconnect the connector of the fan motor CNMF 8...

Страница 38: ...8 Drain pump Hose band Float switch Drain pump assembly fixing screw Drain pump fixing screw Float switch fixing screw 11 Removing the heat exchanger 1 Remove the drain pan See Photo 6 2 Remove the 3...

Страница 39: ...39...

Страница 40: ...8310 JAPAN CCopyright 2009 MITSUBISHI ELECTRIC ENGINEERING CO LTD Distributed in Oct 2009 No OCH459 REVISED EDITION A PDF 7 Distributed in Apr 2009 No OCH459 PDF 7 Made in Japan New publication effect...

Отзывы: