E6

E7

Error Code

Abnormal point and detection method 

Cause

Countermeasure

Fb

E1

or

E2

1

 Contact failure, short circuit or, 

miswiring (converse wiring) of 
indoor/outdoor unit connecting 
wire

2

 Defective transmitting receiving 

circuit of indoor controller board

3

 Defective transmitting receiving 

circuit of indoor controller board

4

 Noise has entered into indoor/ 

outdoor unit connecting wire.

* Check LED display on the outdoor control 

circuit board. (Connect A-control service 
tool, PAC-SK52ST)

  Refer to outdoor unit service manual.

Check disconnection or looseness of indoor/ 
outdoor unit connecting wire of indoor unit or 
outdoor unit.

    Check all the units in case of twin triple   
    indoor unit system.

2

-

4

 Turn the power off, and on again to check. 

If abnormality generates again, replace 
indoor controller board or outdoor 

 

controller circuit board.

* Other indoor controller board may have 
  defect in case of twin triple indoor unit 
 system.

Indoor/outdoor unit communication 
error (Transmitting error)

Abnormal if “1” receiving is detected 30 
times continuously though indoor controller 
board has transmitted “0”.

1

 Defective transmitting receiving 

circuit of indoor controller board 

2

 Noise has entered into power 

supply.

3

 Noise has entered into outdoor 

control wire.

1

-

3

 Turn the power off, and on again to check. 

If abnormality generates again, replace 
indoor controller board.

Indoor/outdoor unit communication 
error (Signal receiving error)

1

 Abnormal if indoor controller board 

  cannot receive any signal normally for 6 

minutes after turning the power on.

2

 Abnormal if indoor controller board 

  cannot receive any signal normally for 3 

minutes. 

3

 Consider the unit abnormal under the fol-

lowing condition: When 2 or more indoor 
units are connected to an 

  outdoor unit, indoor controller board 
  cannot receive a signal for 3 minutes 

from outdoor controller circuit board, a 
signal which allows outdoor controller 
circuit board to transmit signals. 

Indoor controller board

Abnormal if data cannot be read normally 
from the nonvolatile memory of the indoor 
controller board.

1

 Defective indoor controller 

board

1

 Replace indoor controller board.

Remote controller control board

1

 Abnormal if data cannot be read nor-

mally from the nonvolatile memory of the 
remote controller control board.

    (Error code: E1)

2

 Abnormal if the clock function of remote 

controller cannot be operated normally.

    (Error code: E2)

1

 Defective remote controller

1

 Replace remote controller.

PA

 Forced compressor stop 
 (due to water leakage abnormality)

1

 The unit has a water leakage abnor-

mality when the following conditions, a) 
and b), are satisfied while the above-
mentioned detection is performed.

a) The intake temperature subtracted 

with liquid pipe temperature detects 
to be less than -10

:

 for a total of 

30 minutes. (When the drain sensor 
is detected to be NOT soaked in the 
water, the detection record of a) and b) 
will be cleared.)

b) Drain float switch detects to be in the 

water for more than 15 minutes.

*Once the water leakage abnormality is 

detected, abnormality state will not be 
released until the main power is reset.

1

 Drain pump trouble

2

 Drain defective

 

· Drain pump clogging

 

· Drain pipe clogging

3

 Open circuit of float switch

4

 Contact failure of float switch 

connector

5

 Dew condensation on float 

switch

 

· Drain water descends along 
lead wire.

 

· Drain water waving due to 
filter clogging. 

6

 Extension piping connection 

difference at twin, triple, quad-
ruple system.

7

 Miswiring of indoor/ outdoor 

connecting at twin, triple, quad-
ruple system.

8

 Room temperature thermistor/ 

liquid pipe temperature thermis-
tor detection is defective.

1

 Check the drain pump. 

2

 Check whether water can be drained.

3

 Check the resistance of the float switch.

4

 Check the connector contact failure.

5

 Check the float switch leadwire mounted. 

   Check the filter clogging.

6

 Check the piping connection.

7

 Check the indoor/outdoor connecting wires.

8

 Check the room temperature display of 

    remote controller.

  Check the indoor liquid pipe temperature dis 

play of outdoor controller board.

Содержание Mr.Slim PLA-RP100BA3

Страница 1: ...SE CRITERION CURVES 8 7 OUTLINES AND DIMENSIONS 9 8 WIRING DIAGRAM 10 9 REFRIGERANT SYSTEM DIAGRAM 11 10 TROUBLESHOOTING 12 11 SPECIAL FUNCTION 27 12 DISASSEMBLY PROCEDURE 36 Indoor unit Model names S...

Страница 2: ...PU H P100YHAR3 UK OC379 PUHZ P100VHA3 UK OCH415 OCB415 PUHZ P200YHA3 OCH424 OCB424 PUHZ HRP100VHA2 PUHZ HRP100YHA2 OCH425 OCB425 PUHZ RP100VKA PUHZ RP100 200YKA OCH451 OCB451 1 TECHNICAL CHANGES PLP...

Страница 3: ...following tools are necessary to use R410A refrigerant Handle tools with care If dirt dust or moisture enters into refrigerant cycle that can cause deterioration of refrigerant oil or malfunction of c...

Страница 4: ...hose Only for R410A Use pressure performance of 5 09MPa G or over 3 Electronic scale 4 Gas leak detector Use the detector for R134a R407C or R410A 5 Adaptor for reverse flow check Attach on vacuum pu...

Страница 5: ...The room temperature display range is 8 39 The display blinks if the temperature is less than 8 or 39 or more Louver display Indicates the action of the swing louver Does not appear if the louver is...

Страница 6: ...lay Displays whether timer is on or off Buttons used to set the hour and minute of the current time and timer settings h and min buttons display display FAN SPEED display indicates which fan speed has...

Страница 7: ...in kg lbs W D H INDOOR UNIT PLA RP100BA3 Service Ref Mode Power supply phase cycle voltage Input Running current External finish Panel Heat exchanger Fan Fan drive No Fan motor output Airflow Low Medi...

Страница 8: ...Medium2 34 Low 32 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 OCTAVE BAND SOUND PRESSURE LEV...

Страница 9: ...pipe 9 52 Flared connection 3 8 inch Refrigerant pipe 15 88 Flared connection 5 8 inch PLA RP100BA3 Detail drawing of fresh air intake hole Detail connecting of branch duct Both aspects 3 2 8 14 2 8...

Страница 10: ...N FAN MOTOR VANE MOTOR DRAIN PUMP DRAIN FLOAT SWITCH TERMINAL BLOCK Indoor unit Power option TERMINAL BLOCK INDOOR OUTDOOR CONNECTING LINE TERMINAL BLOCK REMOTE CONTROLLER TRANSMISSION LINE REACTOR RO...

Страница 11: ...stor TH5 Cond Eva temperature Thermistor TH1 Room temperature Refrigerant flow in cooling Refrigerant flow in heating Strainer 50 Strainer 50 Heat exchanger Refrigerant GAS pipe connection Flare Refri...

Страница 12: ...ting by inferior phenomena The trouble is not reoccurring Logged Not logged Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor poor c...

Страница 13: ...ode is cancelled Procedure 1 Press the CHECK button twice 2 Press the temperature buttons 3 Point the remote controller at the sensor on the indoor unit and press the HOUR button 4 Point the remote co...

Страница 14: ...flashes Check code Number of times Wireless remote controller Wired remote controller 1 P1 Intake sensor error P9 Pipe TH5 sensor error 2 P2 Pipe TH2 sensor error 3 E6 E7 Indoor outdoor unit communica...

Страница 15: ...ction device is not connected Reverse or open phase wiring for the outdoor unit s power terminal block L1 L2 L3 Incorrect wiring between indoor and outdoor units incorrect polarity of S1 S2 S3 Remote...

Страница 16: ...o P1 above 2 Check contact failure of connector CN44 on the indoor controller board Refer to 10 7 Turn the power on and recheck operation after inserting connector again 4 Check pipe liquid temperatur...

Страница 17: ...nge 4 Defective indoor fan motor Fan motor is defective Indoor controller board is defec tive 5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit clogs 8 Bypass...

Страница 18: ...onnecting remote control ler max 2 units When it is not the above mentioned problem of 1 3 4 Diagnose remote controllers a When RC OK is displayed Remote controllers have no problem Turn the power off...

Страница 19: ...uit board to transmit signals Indoor controller board Abnormal if data cannot be read normally from the nonvolatile memory of the indoor controller board 1 Defective indoor controller board 1 Replace...

Страница 20: ...al block S1 and S2 When AC 220 240V is not detected check indoor outdoor unit connecting wire for miswiring When AC 220 240V is detected check 4 below 4 Check the fuse on indoor controller board Check...

Страница 21: ...ontroller Check indoor outdoor unit connecting wire for connection failure 1 Check the connection of remote con troller wires in case of twin triple indoor unit system When 2 or more indoor units are...

Страница 22: ...on it is possible to activate Emergency Operation by using the indoor unit Emergency operation switch SW1 SW2 of the wireless signal receiver board However if the indoor unit microcomputer has failed...

Страница 23: ...tor for i see sensor Option Abnormal Open or short Red Yellow Red Blue Red Orange Red White Connector Normal 300 Measure the resistance between the terminals with a tester At the ambient temperature o...

Страница 24: ...uble of the indoor controller circuit board and fan motor Self check Symptom The indoor fan cannot rotate Wiring contact check Contact of fan motor connector CNMF No No NG Power supply check Remove th...

Страница 25: ...t to the Terminal Block TB4 Indoor outdoor connecting line Between 3 and 5 220 240V AC CN3G Connect to the auto grille controller board CN3G 13V pulse output CNV Vane motor output MV 12V pulse output...

Страница 26: ...he table on the left in the table indicates the jumper wire is dis connected There is no jumper JP1 because these models have the cond eva temperature thermistor TH5 Marks in the table below Jumper wi...

Страница 27: ...in the above table Airflow outreach distance is different depending on indoor units and air volume ceiling height so airflow may not reach the indicated ceiling height as shown in the above table Init...

Страница 28: ...m 3 2 m 3 6 m and 4 0 m These should be used only as a guide You should lower the air intake grille yourself to check the exact distance You cannot stop the operation while the air intake grille is ri...

Страница 29: ...gerant address No can be changed by using the TEMP buttons when the panel displays a or b Every time you press the Mode selection button the target of operation will change as illustrated below 6 Cont...

Страница 30: ...when the intake grille has been raised the set distance but the storage detection switch is not engaged In this case the operation below will be repeated up to 4 times 10 cm down 30 cm up 10 cm down 3...

Страница 31: ...cy switch heating down UK1 Up down machine SW2 Emergency switch cooling up MU1 Motor Up down LS1 Limit switch storage detection LS21 Limit switch tension detection R B Wired remote controller I B Indo...

Страница 32: ...take grille Lower the air intake grille again and check whether the filter is installed in the correct position Lower the air intake grille again and hook on the air intake grille This is normal This...

Страница 33: ...ction with the 1st unit Once the actual room temperature goes down to 4degrees C below set point the 2nd unit stops operation automatically set point set temperature by R C remote controller 4 6 8 sel...

Страница 34: ...ng Initial setting 2nd unit cut in setting Setting contents Setting No Request code No 7 316 No 8 317 No 9 318 Rotation and Back up OFF Normal group control operation Monitoring the request code of cu...

Страница 35: ...rs on the screen when Maintenance monitor is activated The display now allows you to set a request code No 4 Press the TEMP and buttons to select the desired refrigerant address 5 Press the CLOCK and...

Страница 36: ...ove the reactor 4 Removing the indoor controller board I B 1 Remove the air intake grille and the filter See Figure 1 2 Remove the 2 screws from the electrical box cover 3 Disconnect the connectors CN...

Страница 37: ...ve the bell mouth 3 screws See Photo 2 3 Remove the turbo fan nut 4 Pull out the turbo fan 5 Remove the wire cover 3 screws 6 Remove 2 wiring clamps 7 Disconnect the connector of the fan motor CNMF 8...

Страница 38: ...8 Drain pump Hose band Float switch Drain pump assembly fixing screw Drain pump fixing screw Float switch fixing screw 11 Removing the heat exchanger 1 Remove the drain pan See Photo 6 2 Remove the 3...

Страница 39: ...39...

Страница 40: ...8310 JAPAN CCopyright 2009 MITSUBISHI ELECTRIC ENGINEERING CO LTD Distributed in Oct 2009 No OCH459 REVISED EDITION A PDF 7 Distributed in Apr 2009 No OCH459 PDF 7 Made in Japan New publication effect...

Отзывы: