7

3. Operation

 About the operation method, refer to the operation manual that comes with each remote controller.

3.1. Turning ON/OFF
[ON] [OFF]

Press the [ON/OFF] button.
The ON/OFF lamp will light up in 
green, and the operation will start.

Press the [ON/OFF] button again. 
The ON/OFF lamp will come off, and 
the operation will stop.

 Operation status memory

Remote controller setting

Operation mode

Operation mode before the power was turned off

Preset temperature

Preset temperature before the power was turned off

Fan speed

Fan speed before the power was turned off

 Settable preset temperature range

Operation mode

Preset temperature range

Cool/Dry

19 ~ 30 ºC

Heat

17 ~ 28 ºC

Auto

19 ~ 28 ºC

Fan/Ventilation

Not settable 

Note:
Even if you press the ON/OFF button immediately after shutting down the operation is progress, the air conditioner will not start for about 3 minutes.
This is to prevent the internal components from being damaged.

3.2. Mode Selection

Press the [F1] button to go through the op-
eration modes in the order of “Cool”, “Dry”, 
“Fan”, “Auto”, and “Heat”. Select the desired 
operation mode.

Cool

Dry

Fan

Auto

Heat

 • Operation modes that are not available 

to the connected outdoor unit models will 
not appear on the display.

What the blinking mode icon means

The mode icon will blink when other indoor units in the same refriger-
ant system (connected to the same outdoor unit) are already operated 
in a different mode. In this case, the rest of the unit in the same group 
can only be operated in the same mode.

Automatic operation

 According to a set temperature, cooling operation starts if the room 

temperature is too hot and heating operation starts if the room 
temperature is too cold.

 During automatic operation, if the room temperature changes and 

remains 2.0 °C or more above the set temperature for 15 minutes, the 
air conditioner switches to cool mode. In the same way, if the room 
temperature remains 2.0 °C or more below the set temperature for 
15 minutes, the air conditioner switches to heat mode.

Cool mode

15 minutes (switches 
from heating to cooling)

Set tempe2.0°C

Set temperature

Set temperature -2.0°C

15 minutes (switches 
from cooling to heating)

F1

F2

F3

F4

Cool

Room

Auto

Set temp.

Mode

Temp.

Fan

Fri

3.3. Temperature setting

<Cool, Dry, Heat, and Auto>

Cool

Room

28.5

Auto

Set temp.

Mode

Temp.

Fan

Fri

28.5

Example display
(Centigrade in 0.5-degree 
increments)

F1

F2

F3

F4

Cool

Room

Auto

Set temp.

Mode

Temp.

Fan

Fri

Press the [F2] button to decrease the preset temperature, and press the  
[F3] button to increase.
•  

Refer to the table on page 7 for the settable temperature range for dif-
ferent operation modes.

•  

Preset temperature range cannot be set for Fan/Ventilation operation.

•  

Preset temperature will be displayed either in Centigrade in 0.5- or 
1-degree increments, or in Fahrenheit, depending on the indoor unit 
model and the display mode setting on the remote controller.

Содержание Mr.Slim PCA-RP HAQ

Страница 1: ...u de airconditioner gebruikt MANUAL DE INSTRUCCIONES Lea este manual de instrucciones hasta el final antes de poner en marcha la unidad de aire acondicionado para garantizar un uso seguro y correcto...

Страница 2: ...top operation turn off the power switch and contact your dealer Never insert fingers sticks etc into the intakes or outlets If you detect odd smells stop using the unit turn off the power switch and c...

Страница 3: ...er Manual Manual Manual Filter Normal Long life Oil Filter cleaning indication 100 hr 2 500 hr 100 hr 2 Parts Names PCA RP KAQ Ceiling Suspended Vane Air outlet Air intake Filter Inside of Air intake...

Страница 4: ...ing up the Main menu 5 Backlit LCD Operation settings will appear When the backlight is off pressing any button turns the backlight on and it will stay lit for a certain period of time depending on th...

Страница 5: ...e 2 Appears when the buttons are locked Full mode All icons are displayed for explanation Fri Mode Temp Fan Room Cool Auto Set temp Basic mode Fri Cool Mode Temp Fan Auto Set temp 2 1 5 6 7 8 9 0 1 3...

Страница 6: ...te controller wet or leave it in a location with high hu midity To avoid misplacing the remote controller install the holder included with the remote controller on a wall and be sure to always place t...

Страница 7: ...ted to the same outdoor unit are already operated in a different mode In this case the rest of the unit in the same group can only be operated in the same mode Automatic operation According to a set t...

Страница 8: ...n automatic fan speed is not set at default setting It is not necessary to set for wired remote controller with automatic fan speed at default setting 1 Press the SET button with something sharp at th...

Страница 9: ...ng to move the vanes up and down automatically When set to Step 1 through Step 5 the vane will be fixed at the se lected angle under the vane setting icon This icon will appear when the vane is set to...

Страница 10: ...tion switch heating D Emergency operation switch cooling E Receiver Starting operation To operate the cooling mode press the button D for more than 2 seconds To operate the heating mode press the butt...

Страница 11: ...filter sign is reset the cumulative operation time of all units will be reset The icon is scheduled to appear after a certain duration of opera tion based on the premise that the indoor units are inst...

Страница 12: ...leaning the frame of the oil filter Tools to be prepared Protective goods such as a rubber glove Scrubbing brush or brush Note Avoid using a metal scrubbing brush or brush since the aluminum materials...

Страница 13: ...is emitted from the indoor unit If the indoor temperature and the humidity are high this condition may occur when operation starts During defrosting mode cool airflow may blow down and appear like a m...

Страница 14: ...ler Be sure to provide the dealer with the model name 7 Trouble Shooting Model PKA RP35HAL PKA RP50HAL Power source voltage V Frequency Hz N 230 50 Rated Input Indoor only kW 0 04 0 03 0 04 0 03 Rated...

Страница 15: ...146 1 PAR 31MAA 8 R410A 1 146 2 147 3 151 4 154 5 154 6 155 7 157 8 158...

Страница 16: ...147 PKA RP HAL PCA RP KAQ PCA RP HAQ 3 4 2 100 2 500 100 2 PCA RP KAQ PKA RP HAL PCA RP HAQ...

Страница 17: ...5 6 7 8 9 0 Fri Room Set temp Mode Temp Fan Cool Auto Main Main display Cursor Page Main menu Vane Louver Vent Lossnay High power Timer Weekly timer OU silent mode 7 8 9 0 7 8 9 0 1 2 3 4 5 6 7 F1 8...

Страница 18: ...149 2 Fri Mode Temp Fan Room Cool Auto Set temp Fri Cool Mode Temp Fan Auto Set temp 2 1 5 6 7 8 9 0 1 3 9 4 2 3 4 5 6 7 8 1 2 3 4 5 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 1 8 9...

Страница 19: ...150 1 AAA 2 Reset 1 2 3 2 7 45 AAA Reset Reset ON OFF Test Reset Power Earth Service Panel Indoor Outdoor Connection wire Ref Pipes...

Страница 20: ...at Cool Dry Fan Auto Heat 2 0 C 15 2 0 C 15 15 2 0 C 2 0 C 15 F1 F2 F3 F4 Cool Room Auto Set temp Mode Temp Fan Fri 3 3 Cool Dry Heat Auto Cool Room28 5 Auto Set temp Mode Temp Fan Fri 28 5 0 5 F1 F2...

Страница 21: ...nt mode F1 F2 Auto 1 STAND BY DEFROST 2 3 HEAT 4 DRY 1 SET MODELSELECT A 2 AUTO STOP B 01 3 02 02 ON OFF 2 4 SET MODELSELECT 3 ON OFF TEMP RESET SET CLOCK MODELSELECT FAN VANE TEST RUN AUTO STOP AUTO...

Страница 22: ...ouver Vent Lossnay High power Timer Weekly timer OU silent mode Vane Louver Vent Lossnay Lossnay 152 F1 F2 F3 F4 Fri Swing Off Off Louver Vent Vane Cool Room Auto Set temp Mode Temp Fan Fri F1 F2 F3 F...

Страница 23: ...154 4 1 4 E O SW 5 PKA RP HAL Fig 5 1 Fig 5 2 Fig 5 1 A DEFROST STAND BY B C D E D 2 C 2 D C 2 Fig 5 2 A DEFROST STAND BY OPAH EB l B E EH I C D COOL HEAT 5 STOP 5 COOL HEAT 24 C 24 C 4 5...

Страница 24: ...k Filter information Error information F1 F2 F3 F4 Main menu Filter information Reset Please clean the filter Press Reset button after filter cleaning F1 F2 F3 F4 Filter information Filter information...

Страница 25: ...156 6 1 1 2 A B C D B A D C RP71 3 RP125 4 PCA RP HAQ 1 1 2 1 2 1 2 3 PAC SG38KF 12 4 5 A C B D 3 1 100 2 1 10 50 C 1 PKA RP HAL PCA RP KAQ PCA RP HAQ...

Страница 26: ...157 7 10 1 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF PLEASE WAIT 3...

Страница 27: ...0 06 0 06 0 06 0 09 0 09 0 11 0 11 0 14 0 14 A 0 29 0 27 0 37 0 37 0 39 0 39 0 42 0 42 0 65 0 65 0 76 0 76 0 90 0 90 230 960 1280 1600 680 2 1 3 10 11 12 14 10 11 13 15 15 16 17 19 16 17 18 20 22 24...

Страница 28: ...ra compilar o ficheiro t cnico o seguinte Vores autoriserede repr sentant i EU som er autoriseret til udarbejdelse af den tekniske fil er f l gende V r EG representant som r auktoriserad att sammanst...

Страница 29: ...C9612 JIS B8616 ISO 5151 T1 et ISO 13523 T1 SVENSKA Engelska r originalspr ket De vriga spr kversionerna r vers ttningar av ori ginalet F RSIKTIGHET K ldmedelsl ckage kan leda till kv vning Tillhanda...

Страница 30: ...ATE Sequential number for each unit 00001 99999 A indoor unit A Month of manufacture 4 5 6 7 8 9 X 10 Y 11 Z 12 1 2 3 Last digit of the company s fiscal year western calendar 2014 4 2015 5 00001 99999...

Страница 31: ...I CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDE MIDDLESEX UB8 1QQ U K 115054 52 1 Please be sure to put the contact address...

Отзывы: