Fan speed is switched according to the number of operating indoor unit and the compressor frequency.
Note
• When the indoor coil thermistor is 57
:
or more on HEAT operation, fan speed is fixed to Low speed.
Or, the indoor coil thermistor is 45
:
or less on HEAT operation, fan speed is back to normal.
4-7. OUTDOOR FAN CONTROL
COOL
Fan speed
Up
Down
Up
Down
Mode
HEAT
Compressor frequency
<Relation between compressor frequency and fan speed.>
40Hz
30Hz
40Hz
30Hz
Up
Down
Fan speed
High
Low
Compressor frequency
Min.
Max.