2. In case that pipes jut out from bottom surface of the indoor unit. (Fig. 2)

Process figure

(Fig. 2)

48

°

R50 (R2"

-

 

R60

80

38

°

R30 - R40 (R1.5") 

80

Refrigerant pipe

Refrigerant pipe

Flare nut

Refrigerant pipe (gas)
OD ø12.7 (A18)
OD ø15.88 (A24)

Flare nut

Refrigerant pipe (liquid)
OD ø6.35

Wall hole sealing and fixing pipe to wall

4-7

DRAIN PIPE CONNECTION

• Use hard PVC (ø26 mm O.D.) for drain pipe 

D

.

• Use drain pipe cover 

8

 which is provided in accessories, wind it around drain pipe 

D

 in the indoor unit side.

• Use vinyl chloride adhesive for joints prevent leakage.
• When the drain pipe 

D

 has to go through an indoor space, be sure to cover the drain pipe 

D

 with insulation

readily available in the market.

• For drain pipe connection, use care so as no extra force applies to unit side piping.

1. In case of connecting drain pipe 

D

 to drain-joint bush directly.

• Be sure to connect drain pipe 

D

 to drain-joint bush securely as shown in the right.

• Be sure to pass drain pipe 

D

 with drain pipe cover through knockout hole on bottom surface so as to

keep an inclination.

a

Drain-joint bush

b

Knockout

c

PVC adhesive tape

d

Adhesive

8

Drain pipe cover

D

Drain pipe (VP-20)

c

8

D

b

a

d

b

a

30

2. In case of connecting drain pipe 

D

 to drain-joint bush through drain hose.

• Drain hose 

7

 which is contained in accessories is flexible, so use it when drain pipe 

D

 should be

alternated direction.

• Be sure to wind pipe cover which is provided in accessories around drain hose with vinyl tape.
• Cut VP-20 in dimension as shown at the right, and connect drain-joint bush with drain hose with adhe-

sive.

a

Drain-joint bush

b

Tape

c

Adhesive

7

Drain hose

8

Drain pipe cover

D

Drain pipe (VP-20)

G

Drain-joint pipe (VP-20)

3.

• Be sure that drain pipe 

D

 tilts downward (1/100 or more) on outdoor side (drain side), and no traps or

heaving exist.

• When the drain pipe 

D

 is relatively long, provide support metal fixtures midway to eliminate waving.

• Odor trap at the end of drain pipe 

D

 is not required.

a

Insulation

b

Supporting metal fixture

c

Downward inclination of 1/100 or more

d

Air bleeder

e

Do not raise

f

Odor trap

g

The end of drain hose is immersed in water

h

Gap from the ground level is 50 mm or less

i

Sewage ditch

b

c

a

0.75 m - 1.5 m

i

g

h

f

e

d

8

7

a

G

50 mm

8

a

G

b

7

D

c

c

Indoor unit

Wall hole cover 

I

Seal the wall hole
gap with putty 

I

.

Fix the pipe to wall with
pipe fixing band 

E

.

Cut off the
extra length.

Pipe fixing
band 

E

Fixing screw 

F

Содержание MCFZ-A18WV

Страница 1: ...C utilized R410A CONTENTS 1 THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY 2 2 SELECTING THE INSTALLATION LOCATION 2 3 INSTALLATION DIAGRAM ACCESSORIES 3 4 INDOOR UNIT INSTALLATION 4 5 OUTDOOR UNI...

Страница 2: ...frigerant circuit Any presence of foreign substance such as air can cause abnormal pressure rise or an explo sion 330 mm 360 mm 500 mm 840 mm 1 THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY Pleas...

Страница 3: ...gerant pipe 1 set B Indoor outdoor connecting wire 2 core 1 0 mm2 1 C Piping tape 1 D Drain pipe PVC pipe OD 26 1 E Pipe fixing band for refrigerant pipe The quantity depends on the pipe length 2 to 5...

Страница 4: ...lack of thickness may cause dew drippage 4 1 A CASE OF SUSPENDING INDOOR UNIT FROM THE CEILING 4 1 1 MOUNTING INSTALLATION PLATE FIXING BOLTS 4 INDOOR UNIT INSTALLATION 1 Determine the locations of in...

Страница 5: ...own in Fig 2 Be sure to confirm letters FRONT in installation plates 1 set FRONT side to air outlet side of indoor unit a FRONT 1 Installation plate 2 In case of fixing installation plates 1 above the...

Страница 6: ...m the dimensions as below 4 2 4 FRONT GRILLE REMOVAL See to 4 1 4 Page 5 4 2 5 OPENING KNOCKOUT HOLE See to 4 1 5 Page 5 Installation pattern Remove installation pattern after installing Horizontal ba...

Страница 7: ...e to fix the cable by cable clamp 3 Replace the terminal cover securely Cable clamp Screw Terminal cover Warning Attach the electrical part cover securely If it is attached incorrectly it could result...

Страница 8: ...ve 8 Drain pipe cover D Drain pipe VP 20 c 8 D b a d b a 30 2 In case of connecting drain pipe D to drain joint bush through drain hose Drain hose 7 which is contained in accessories is flexible so us...

Страница 9: ...or less 25 m or less Power supply cord Specification Indoor and Outdoor connecting wire Specification 3 core 2 5 mm2 or more in conformity with Design 245 IEC 57 3 core 4 0 mm2 or more in conformity w...

Страница 10: ...ble for R410A Electronic scale for re frigerant charging 6 2 FLARING WORK Main cause of gas leakage is defect in flaring work Carry out correct flaring work in the following procedure 2 Burrs removal...

Страница 11: ...liquid pipe and the gas pipe between the indoor and the outdoor unit Remove the service port cap of the stop valve on the side of the outdoor unit gas pipe The stop valve will not work in it initial...

Страница 12: ...Operating Instruction Book EMERGENCY OPERATION switch 6 5 TEST RUN Before performing the test run recheck for any wrong wiring Wrong wiring prevents normal operation or results in blown fuse disabling...

Страница 13: ...rge refrigerant into the atmosphere during installation reinstallation or re pairs to the refrigerant circuit For additional charging charge the refrigerant from liquid phase of the gas cylinder If th...

Страница 14: ...TOKYO 100 8310 JAPAN This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Volta...

Отзывы: