5. OUTDOOR UNIT INSTALLATION

INDOOR/OUTDOOR UNIT CONNECTING WIRE CONNECTION AND
OUTDOOR POWER SUPPLY CORD CONNECTION

• Connect the indoor/outdoor unit connecting wire 

B

 from the indoor unit correctly on the terminal block.

• For future servicing, give extra length to connecting wire.

Connect to the supply terminals and leave a contact separation of at least 3 mm
at each pole to disconnect the source power pole. (When the power switch is shut
off, it must disconnect all poles.)

Rated Voltage

Breaker capacity

230 V

20 A

• Peel off both ends of connecting wire (extension wire). When too

long, or connected by cutting off the middle, peel off power sup-
ply wire to the size as shown in the right.

• Be careful not to contact connecting wire with piping.
• Make earth wire a little longer than the others. (more than 35 mm)

• For the power supply cord and the indoor/outdoor unit connecting wires, be sure to use the ones in compli-

ance with the standards.

• Be sure to push the core until it is hidden and pull each cable to make sure that it is not pulled up incomplete

10 m or less
15 m or less
25 m or less

Power supply cord Specification

Indoor and Outdoor connecting wire
Specification

3-core 2.5 mm

2

 or more, in conformity with Design 245 IEC 57.

3-core 4.0 mm

2

 or more, in conformity with Design 245 IEC 57.

3-core 6.0 mm

2

 or more, in conformity with Design 245 IEC 57.

Cable 2-core 1.0 mm

2

, in conformity with Design 245 IEC 57.

Loosen terminal screw.

Terminal block

Lead wire

<Connection details>

insertion may cause a risk of burning the terminal blocks.

 Caution:

• Use care not to make mis-wiring.
• Firmly tighten the terminal screws to prevent them from loosening.

Service panel

Fixing screws

• After tightening, pull the wires lightly to confirm that they do not move.

 Warning:

Be sure to attach the service panel of the outdoor unit securely. If it is not attached correctly, it could
result in a fire or an electric shock due to dust, water, etc.

Indoor terminal block

Outdoor terminal block

3 N

3 N

Indoor/outdoor unit
connecting wire 

B

2-core 1.0 mm

2

Be sure to put the left por-
tion into the square hole of
the service panel.

Be sure to fix the indoor/outdoor
unit connecting wire 

B

 and power

supply cord 

H

 using this cord

clamp.

Remove two fixing
screws to open the
service panel.

Valve cover

35 mm

15 mm

Three core with
ground IEC cord

Power supply cord 

H

N~

L~

Содержание MCFZ-A18WV

Страница 1: ...C utilized R410A CONTENTS 1 THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY 2 2 SELECTING THE INSTALLATION LOCATION 2 3 INSTALLATION DIAGRAM ACCESSORIES 3 4 INDOOR UNIT INSTALLATION 4 5 OUTDOOR UNI...

Страница 2: ...frigerant circuit Any presence of foreign substance such as air can cause abnormal pressure rise or an explo sion 330 mm 360 mm 500 mm 840 mm 1 THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY Pleas...

Страница 3: ...gerant pipe 1 set B Indoor outdoor connecting wire 2 core 1 0 mm2 1 C Piping tape 1 D Drain pipe PVC pipe OD 26 1 E Pipe fixing band for refrigerant pipe The quantity depends on the pipe length 2 to 5...

Страница 4: ...lack of thickness may cause dew drippage 4 1 A CASE OF SUSPENDING INDOOR UNIT FROM THE CEILING 4 1 1 MOUNTING INSTALLATION PLATE FIXING BOLTS 4 INDOOR UNIT INSTALLATION 1 Determine the locations of in...

Страница 5: ...own in Fig 2 Be sure to confirm letters FRONT in installation plates 1 set FRONT side to air outlet side of indoor unit a FRONT 1 Installation plate 2 In case of fixing installation plates 1 above the...

Страница 6: ...m the dimensions as below 4 2 4 FRONT GRILLE REMOVAL See to 4 1 4 Page 5 4 2 5 OPENING KNOCKOUT HOLE See to 4 1 5 Page 5 Installation pattern Remove installation pattern after installing Horizontal ba...

Страница 7: ...e to fix the cable by cable clamp 3 Replace the terminal cover securely Cable clamp Screw Terminal cover Warning Attach the electrical part cover securely If it is attached incorrectly it could result...

Страница 8: ...ve 8 Drain pipe cover D Drain pipe VP 20 c 8 D b a d b a 30 2 In case of connecting drain pipe D to drain joint bush through drain hose Drain hose 7 which is contained in accessories is flexible so us...

Страница 9: ...or less 25 m or less Power supply cord Specification Indoor and Outdoor connecting wire Specification 3 core 2 5 mm2 or more in conformity with Design 245 IEC 57 3 core 4 0 mm2 or more in conformity w...

Страница 10: ...ble for R410A Electronic scale for re frigerant charging 6 2 FLARING WORK Main cause of gas leakage is defect in flaring work Carry out correct flaring work in the following procedure 2 Burrs removal...

Страница 11: ...liquid pipe and the gas pipe between the indoor and the outdoor unit Remove the service port cap of the stop valve on the side of the outdoor unit gas pipe The stop valve will not work in it initial...

Страница 12: ...Operating Instruction Book EMERGENCY OPERATION switch 6 5 TEST RUN Before performing the test run recheck for any wrong wiring Wrong wiring prevents normal operation or results in blown fuse disabling...

Страница 13: ...rge refrigerant into the atmosphere during installation reinstallation or re pairs to the refrigerant circuit For additional charging charge the refrigerant from liquid phase of the gas cylinder If th...

Страница 14: ...TOKYO 100 8310 JAPAN This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Volta...

Отзывы: