FLARED CONNECTIONS

• This unit has flared connections on both indoor and outdoor sides.
• Refrigerant pipes are used to connect the indoor and outdoor units as shown in the figure below.
• Insulate both refrigerant and drain piping completely to prevent condensation.

Limits

Pipe length

30 m max.

Height difference

15 m max.

No. of bends

10 max.

• Refrigerant adjustment … If pipe length exceeds 7 m, additional refrigerant (R410A) charge is required.

(The outdoor unit is charged with refrigerant for 7 m pipe length.)

Pipe length

Up to 7 m

No additional charge required

Exceeding 7 m

Additional charge required

Refrigerant to be added 20 g/m

PIPING PREPARATION

1

Table below shows the specifications of pipes commercially available.

Pipe

Outside diameter

Insulation thickness

Insulation material

For liquid

6.35 mm

8 mm

Heat resisting foam plastic

For gas

A18

12.7 mm

8 mm

0.045 specific gravity

A24

15.88 mm

8 mm

• Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm (for ø6.35) or 1.0 mm (for

ø12.7 and ø15.88). Never use any pipe with a thickness less than 0.8 mm (for ø6.35) or 1.0 mm (for ø12.7
and ø15.88), as the pressure resistance is insufficient.

2

Ensure that the 2 refrigerant pipes are well insulated to prevent condensation.

3

Refrigerant pipe bending radius must be 100 mm or more.

 Caution:

Be sure to use the insulation of specified thickness. Excessive thickness may cause incorrect installa-
tion of the indoor unit and lack of thickness may cause dew drippage.

4-1

A CASE OF SUSPENDING INDOOR UNIT FROM THE CEILING

4-1-(1)

MOUNTING INSTALLATION PLATE FIXING BOLTS

4. INDOOR UNIT INSTALLATION

1. Determine the locations of installation plate fixing bolts.

• Use installation pattern to determine the locations of instal-

lation plate fixing bolts 

J

.

a

Installation pattern

Details are printed on pattern.
Attention:

Surrounding temperature and humidity conditions
may cause paper pattern to shrink or expand.
(Measure dimensions before drilling holes.)

2. Suspension structure (Give site of suspension strong struc-

ture).

Wood structure

• Select tie beam (one-story houses) or second-floor

girder (two story houses) as reinforcement member.

• Use sturdy beams of at least 60 mm square for beam

pitch of 900 mm or less or of at least 90 mm square for
beam pitch of 900-1800 mm.

a

Pitch

b

Ceiling

c

Rafter

d

Bracket

e

Roof beam

Ferroconcrete Structures

• Secure installation plate fixing bolts 

J

 as shown at the

right or use angle-stock bracework to install installa-
tion plate fixing bolts 

J

.

f

Use inserts rated at 100-150 kg each

g

Steel reinforcing rod

J

Installation plate fixing bolts

3. Installation plate fixing bolts pitch.

• Use the installation plate fixing bolts 

J

 M10 (

×

 4 procure

locally).

a

Indoor unit

b

Air outlet

1

Installation plate

• Projecting dimension of installation fixing bolts 

J

 from hori-

zontal base line against which you fix installation plate 

1

as within at the right.

c

Horizontal base line

1

Installation plate

J

Installation fixing bolts

a

*Remove installation pattern after installation.

b

c

d

e

a

a

b

a

1

300 mm

150 mm

1065 mm

f

J

g

c

J

1

max. 40 mm

Содержание MCFZ-A18WV

Страница 1: ...C utilized R410A CONTENTS 1 THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY 2 2 SELECTING THE INSTALLATION LOCATION 2 3 INSTALLATION DIAGRAM ACCESSORIES 3 4 INDOOR UNIT INSTALLATION 4 5 OUTDOOR UNI...

Страница 2: ...frigerant circuit Any presence of foreign substance such as air can cause abnormal pressure rise or an explo sion 330 mm 360 mm 500 mm 840 mm 1 THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY Pleas...

Страница 3: ...gerant pipe 1 set B Indoor outdoor connecting wire 2 core 1 0 mm2 1 C Piping tape 1 D Drain pipe PVC pipe OD 26 1 E Pipe fixing band for refrigerant pipe The quantity depends on the pipe length 2 to 5...

Страница 4: ...lack of thickness may cause dew drippage 4 1 A CASE OF SUSPENDING INDOOR UNIT FROM THE CEILING 4 1 1 MOUNTING INSTALLATION PLATE FIXING BOLTS 4 INDOOR UNIT INSTALLATION 1 Determine the locations of in...

Страница 5: ...own in Fig 2 Be sure to confirm letters FRONT in installation plates 1 set FRONT side to air outlet side of indoor unit a FRONT 1 Installation plate 2 In case of fixing installation plates 1 above the...

Страница 6: ...m the dimensions as below 4 2 4 FRONT GRILLE REMOVAL See to 4 1 4 Page 5 4 2 5 OPENING KNOCKOUT HOLE See to 4 1 5 Page 5 Installation pattern Remove installation pattern after installing Horizontal ba...

Страница 7: ...e to fix the cable by cable clamp 3 Replace the terminal cover securely Cable clamp Screw Terminal cover Warning Attach the electrical part cover securely If it is attached incorrectly it could result...

Страница 8: ...ve 8 Drain pipe cover D Drain pipe VP 20 c 8 D b a d b a 30 2 In case of connecting drain pipe D to drain joint bush through drain hose Drain hose 7 which is contained in accessories is flexible so us...

Страница 9: ...or less 25 m or less Power supply cord Specification Indoor and Outdoor connecting wire Specification 3 core 2 5 mm2 or more in conformity with Design 245 IEC 57 3 core 4 0 mm2 or more in conformity w...

Страница 10: ...ble for R410A Electronic scale for re frigerant charging 6 2 FLARING WORK Main cause of gas leakage is defect in flaring work Carry out correct flaring work in the following procedure 2 Burrs removal...

Страница 11: ...liquid pipe and the gas pipe between the indoor and the outdoor unit Remove the service port cap of the stop valve on the side of the outdoor unit gas pipe The stop valve will not work in it initial...

Страница 12: ...Operating Instruction Book EMERGENCY OPERATION switch 6 5 TEST RUN Before performing the test run recheck for any wrong wiring Wrong wiring prevents normal operation or results in blown fuse disabling...

Страница 13: ...rge refrigerant into the atmosphere during installation reinstallation or re pairs to the refrigerant circuit For additional charging charge the refrigerant from liquid phase of the gas cylinder If th...

Страница 14: ...TOKYO 100 8310 JAPAN This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Volta...

Отзывы: