PIPE CONNECTION

1. Indoor unit connection

• Connect both liquid and gas piping to the indoor unit.

- Apply a thin coat of refrigerant oil on the seat surface

of pipe.

- For connection first align the center, then hand tighten

the first 3 to 4 turns of flare nut.

- Use tightening torque table below as a guideline for

the indoor unit side union joint section, and tighten us-
ing two wrenches. Excess tightening damages the
flared section.

Pipe diameter

Tightening torque

mm

N·m

kgf·cm

6.35

13.7 to 17.7

140 to 180

12.7

49.0 to 56.4

500 to 575

15.88

73.5 to 78.4

750 to 800

2. Outdoor unit connection

• Connect pipes to stop valve pipe joint of the outdoor unit in

the same manner applied for the indoor unit.

- For tightening, use a torque wrench or spanner, and

use the same tightening torque applied for the indoor
unit.

3. Refrigerant pipe insulation

• Use pipe cover (foam polyethylene 8 mm thickness) which

is contained in accessories, insulate both liquid and gas
pipes together. Put the refrigerant piping and apply piping
tape 

C

.

a

Indoor unit refrigerant pipe

b

Flare joint

d

Pipe cover

A

Refrigerant pipe

C

Piping tape

4. Knockout cover

• Attach knockout cover 

9

 to close knockout hole to prevent

rat or something strange from getting into the indoor unit.

9

Knockout cover

0

Screw for 

9

 4 

×

 10 mm

A

b

a

c

d

c

9

0

Connecting wire and
refrigerant pipes
must be separated.

6-4

PURGING PROCEDURES · LEAK TEST

• Use the vacuum pump for air purging for the purpose of environmental protection.

PURGING PROCEDURES

Connect the refrigerant pipes (both liquid pipe and the gas pipe) between the indoor and the outdoor unit.

Remove the service port cap of the stop valve on the side of the outdoor unit gas pipe. (The stop valve will
not work in it initial state fresh out of the factory (totally closed with cap on).)

Connect the gauge manifold valve and the vacuum pump to the service port of the stop valve on the gas
pipe side of the outdoor unit.

Run the vacuum pump. (Vacuumize for more than 15 minutes.)

Check the vacuum with the gauge manifold valve, then close the gauge manifold valve, and stop the vacuum
pump.

Leave as it is for one or two minutes. Make sure the pointer gauge manifold valve remains in the same
position. Confirm that the pressure gauge shows–0.101 Mpa [Gauge] (–760 mmHg).

Remove the gauge manifold valve quickly from the service port of the stop valve.

After refrigerant pipes are connected and evacuated, fully open all stop valves on both sides of gas pipe and
liquid pipe.
Operating without fully opening lowers the performance and this causes trouble.

Pipe length up to 7 m

No gas charge is needed.

Pipe length exceeding 7 m

Charge the prescribed amount of

gas. (refer to 4)

Tighten the cap to the service port to obtain the initial status.

Retighten the cap.

Leak test

Tightening torque

N·m

kgf·cm

Cap for service port

13.7 to 17.7

140 to 180

Cap for stop valve

19.6 to 29.4

200 to 300

*Close

*Open

Hexagonal wrench

Stop valve

*4 to 5 turns

Stop valve

(or the vacuum pump with
the function to prevent the
back flow)

Gauge manifold
valve (for R410A)

Pressure gauge
    (for R410A)

Compound pressure
gauge (for R410A)

-0.101MPa
(-760 mmHg)

Handle
Low

Handle High

Window

Charge hose
(for R410A)

Vacuum
pump

Adapter for preventing the
back flow

Charge hose
(for R410A)

Service port

Stop
valve

Содержание MCFZ-A18WV

Страница 1: ...C utilized R410A CONTENTS 1 THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY 2 2 SELECTING THE INSTALLATION LOCATION 2 3 INSTALLATION DIAGRAM ACCESSORIES 3 4 INDOOR UNIT INSTALLATION 4 5 OUTDOOR UNI...

Страница 2: ...frigerant circuit Any presence of foreign substance such as air can cause abnormal pressure rise or an explo sion 330 mm 360 mm 500 mm 840 mm 1 THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY Pleas...

Страница 3: ...gerant pipe 1 set B Indoor outdoor connecting wire 2 core 1 0 mm2 1 C Piping tape 1 D Drain pipe PVC pipe OD 26 1 E Pipe fixing band for refrigerant pipe The quantity depends on the pipe length 2 to 5...

Страница 4: ...lack of thickness may cause dew drippage 4 1 A CASE OF SUSPENDING INDOOR UNIT FROM THE CEILING 4 1 1 MOUNTING INSTALLATION PLATE FIXING BOLTS 4 INDOOR UNIT INSTALLATION 1 Determine the locations of in...

Страница 5: ...own in Fig 2 Be sure to confirm letters FRONT in installation plates 1 set FRONT side to air outlet side of indoor unit a FRONT 1 Installation plate 2 In case of fixing installation plates 1 above the...

Страница 6: ...m the dimensions as below 4 2 4 FRONT GRILLE REMOVAL See to 4 1 4 Page 5 4 2 5 OPENING KNOCKOUT HOLE See to 4 1 5 Page 5 Installation pattern Remove installation pattern after installing Horizontal ba...

Страница 7: ...e to fix the cable by cable clamp 3 Replace the terminal cover securely Cable clamp Screw Terminal cover Warning Attach the electrical part cover securely If it is attached incorrectly it could result...

Страница 8: ...ve 8 Drain pipe cover D Drain pipe VP 20 c 8 D b a d b a 30 2 In case of connecting drain pipe D to drain joint bush through drain hose Drain hose 7 which is contained in accessories is flexible so us...

Страница 9: ...or less 25 m or less Power supply cord Specification Indoor and Outdoor connecting wire Specification 3 core 2 5 mm2 or more in conformity with Design 245 IEC 57 3 core 4 0 mm2 or more in conformity w...

Страница 10: ...ble for R410A Electronic scale for re frigerant charging 6 2 FLARING WORK Main cause of gas leakage is defect in flaring work Carry out correct flaring work in the following procedure 2 Burrs removal...

Страница 11: ...liquid pipe and the gas pipe between the indoor and the outdoor unit Remove the service port cap of the stop valve on the side of the outdoor unit gas pipe The stop valve will not work in it initial...

Страница 12: ...Operating Instruction Book EMERGENCY OPERATION switch 6 5 TEST RUN Before performing the test run recheck for any wrong wiring Wrong wiring prevents normal operation or results in blown fuse disabling...

Страница 13: ...rge refrigerant into the atmosphere during installation reinstallation or re pairs to the refrigerant circuit For additional charging charge the refrigerant from liquid phase of the gas cylinder If th...

Страница 14: ...TOKYO 100 8310 JAPAN This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Volta...

Отзывы: