2
1.1.2 On-Line Monitor(via G-50)
The
On-Line Monitor
is connected to the unit by the central controller(G-50A) and can monitor such areas
as system data, unit data and operating data.
(1) In case for local connection
By directly connecting the PC installed with Maintenance Tools and G-50A through LAN, various
monitoring/setting can be performed from the Maintenance Tools.
(2)-1 In case for remote connection (Dialup connection mode)
By connecting the PC installed with Maintenance Tools and G-50A through public network remotely,
various monitoring/setting can be performed from the Maintenance Tools.
(2)-2 In case for remote connection (E-mail connection mode)
Under E-mail connection mode, communication can be executed with G-50A through E-mail transmission
via mail server. All communication with G-50A is converted into E-mail in this case.
Maintenance
Tools PC
G-50A
LAN
HUB
M-NET
M-NET
MODEM etc
Public
network
Dial-up
Router
Maintenance
Tool PC
HUB
G-50A
LAN
Maintenance
Tools PC
LAN
G-50A
POP
Internet
Provider 2
Access point
Provider 1
Access point
Provider1
Mail server
Provider2
Mail server
SMTP
POP
SMTP
Mail server
Mail server
Notice
•
To use the E-mail connection mode, the version of G-50 should be above 2.60.
•
When using E-mail connection mode, the local G-50A is required to be initially set with Maintenance Tool and
the mail address by the G-50A initial setting tool.
- For each mail address, it is required to obtain and set an exclusive one. To transmit mail via an internet
provider, obtain the mail address from the provider. When a mail server is existing on the LAN, obtain the
mail address from the LAN administrator.
- Set the [Pop receive interval] within 3 minutes. However to monitor operating status [Operation Monitor], set it within 1
minute.
- Setting of initial information to G-50A can not be executed from Maintenance Tool. Make sure to set it from the G-50A
initial setting tool locally. If dialup connection environment is available, it can be set from a remote position.
(For detail, please refer to 6-1 Mail Basic Setting in the instruction manual of the G-50A initial setting tool.)
•
The communication speed under E-mail connection mode largely depends on the transfer rate of each mail
server. Under the circumstance, the action of Maintenance Tool may take a lot of time under some internet
environments or routing mail servers.