2N
-16LNK-M MELSEC-I/O LINK REMOTE I/O SYSTEM MASTER BLOCK
Operation 4
4-8
4.4
Program
Set the station Nos., set the mode and perform wiring in accordance with "4.1 Operating procedure".
Set the station Nos. and the mode using the following procedure.
Standard mode
1 )
Set the I/O occupation setting switch MOD2 to ON (initial value). I/O No. assignment in the standard
mode is selected.
2 )
By turning on/off the switches MOD0 and MOD1, determine the number of I/O points occupied by the
remote I/O system.
3 )
Assign a station No. and I/O Nos. to each remote I/O unit to be used. (Refer to the assignment table
offered as attachment.)
When 128 points are occupied
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Station No.
X (input)
Y (output)