FX
2N
-16LNK-M MELSEC-I/O LINK REMOTE I/O SYSTEM MASTER BLOCK
Operation 4
4-3
On-line station setting
switch
Set the station Nos. of connected remote I/O units. "0" to "F" indicate station
Nos.
ON: To be communicated (with error check)
OFF: Not to be communicated (without error check)
* Station Nos. are not necessarily serial numbers.
If an unconnected station No. is set to OFF, communication error will not be
indicated. (For setting of station Nos., refer to Paragraph 4.3.)
If an unconnected station No. is set to ON, an error will occur in that station
No. and the RUN terminals will be set to OFF. Make sure to set unused sta-
tions to OFF when the RUN terminals are used.
Name
Description
ON
OFF
0 1 2 3 4 5 6 7
ON
OFF
8 9 A B C D E F