FX
2N
-16LNK-M MELSEC-I/O LINK REMOTE I/O SYSTEM MASTER BLOCK
Product Specifications 2
2-5
Performance specifications
Specifications item
Description
Maximum number of con-
trolled I/O points
128 points (16 remote units with 4 points each) per master block
I/O refresh time
Approx. 5.4 ms (without regard to number of I/O points)
Communication speed
38400 bps
Communication method
Register insertion method
Synchronization method
Frame synchronization and bit synchronization used together
Comm
unication
specifications
Error control method
Adjacent phase inversion check and parity check used together (retry by
timeout)
Transmission path
type
Bus (multi-drop) type (T branches are available. Terminal resistors are not
required.)
Transmission distance
Maximum total extension distance: 200 m
Maximum number of
connected units
16 stations per master block
Error (RUN) indication/out-
put
Indication by LEDs
Confirmation of 24V DC power supplied from outside to master block by
M8009 (24V DC down) in basic unit
External outputs by RUNA and RUNB
Number of occupied I/O
points
Selectable among 16, 32, 48, 64, 96 and 128
Supply voltage from outside
21.6 to 27.6V DC (for communication path)
Current consumption of
power supply from outside
90 mA (TYP 24V DC)
Current consumption inside
(5 VDC)
200 mA
Weight
0.5 kg
Содержание FX2N-16LNK-M
Страница 1: ...USER S MANUAL FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK ...
Страница 8: ...FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK Contents vi MEMO ...
Страница 50: ...FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK Troubleshooting 5 5 6 Memo ...
Страница 58: ...FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK Appendix A 6 Memo ...
Страница 59: ...FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK ...