FX
2N
-16LNK-M MELSEC-I/O LINK REMOTE I/O SYSTEM MASTER BLOCK
Operation 4
4-2
4.2
Setting and function of each portion
The table below shows the setting contents and the function of each setting switch provided on a master
block.
For layout of the each setting switch, refer to Paragraph 2.2.
Setting switches
Name
Description
I/O point occupation
setting switch
Set the number of points occupied by a master block.
The number of occupied points indicates the number of points used by the I/O
link system. The number of points of connected remote I/O units is equivalent
to or smaller than this. Use the standard mode usually.
If remote I/O units dedicated to input or output are used, the dedicated I/O
type unit mode is also available.
MOD3 is not used.
ON
OFF
0 1 2 3
MOD3
MOD2
MOD1
MOD0
MOD2
MOD0 MOD1
Number of
occupied points
Default
value
ON
Standard mode
ON
ON
128 points
{
OFF
ON
96 points
ON
OFF
64 points
OFF
OFF
32 points
OFF
Dedicated I/O
type unit mode
ON
ON
64 points
OFF
ON
48 points
ON
OFF
32 points
OFF
OFF
16 points
Содержание FX2N-16LNK-M
Страница 1: ...USER S MANUAL FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK ...
Страница 8: ...FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK Contents vi MEMO ...
Страница 50: ...FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK Troubleshooting 5 5 6 Memo ...
Страница 58: ...FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK Appendix A 6 Memo ...
Страница 59: ...FX2N 16LNK M MELSEC I O LINK REMOTE I O SYSTEM MASTER BLOCK ...