Remarks to the table:
The parameter setting is ignored, if the general purpose flux vector control is activated.
Since calibration is made before shipment from the factory, the setting differs slightly be-
tween inverters.
The setting depends on the inverter capacity. Range splitting: (0.4–3.7k = 5s) /
(5.5–7.5k = 10s).
Set to 85% of the rated inverter current for 0.4k and 7.5k type.
If “2” is set in parameter 77 (parameter write inhibit selection), the setting cannot be
changed during operation.
These parameters allow their settings to be changed during operation if “0” (factory setting)
has been set in parameter 77.
The setting depends on the inverter capacity. Range splitting: 4% for FR-E 540-5.5 k EC
and FR-E 540-7.5 k EC.
To set “10” or “11” in parameter 73, first “801” must be set in parameter 77.
Parameter 338 to 340 are displayed only when the communication option is fitted or when
Pr. 119 is “100”, “101”, “110” or “111”.
New setting ranges or parameter available from firmware version V7471C
Pr. 345 to Pr. 348 are displayed only when the option FR-E5ND is fitted.
Pr. 500 to Pr. 502 are displayed only when the communication option is fitted.
NOTE
To change the inverter settings a parameter unit (FR-PA02-02 or FR-PU04 with extension
cable FR-A5 CBL1) or a personal computer with installed VFD Setup Software in conjunc-
tion with a converter (RS232
→
RS485) is required.
Parameter
FR-E 500 EC
23
Func-
tion
Para-
meter
Meaning
Setting range
Default
Additional
functions
251
Output phase failure protection selection
0 / 1
1
254
Analog polarity reversible lower limit
0–100% / 9999
9999
338
Operation command write
0 / 1
0
339
Speed command write
0 / 1
0
340
Link start mode selection
0 / 1
0
342
E²PROM write selection
0 / 1
0
DeviceNet-
functions
345
DeviceNet address (lower byte)
0–255
63 (0x3F)
346
DeviceNet baudrate (lower byte)
0–255
132 (0x84)
347
DeviceNet Address (higher byte)
0–255
160 (0xA0)
348
DeviceNet Baudrate (higher byte)
0–255
80 (0x50)
Additional
function
500
Communication error recognition waiting time
0–999.8s
0
501
Communication error occurrence
count display
0
0
502
Error time stop mode selection
0 / 1 / 2
0
Calibration
functions
901
AM terminal calibration
Calibration range
—
902
Frequency setting voltage bias
0–60Hz / [0–10V]
0Hz / [0V]
903
Frequency setting voltage gain
1–400Hz / [0–10V]
50Hz / [5V]
904
Frequency setting current bias
0–60Hz / [0–20mA]
0Hz / [4mA]
905
Frequency setting current gain
1–400Hz/[0–20mA]
50Hz / [20mA]
Help
functions
990
Beep signal at key operation
0 / 1
1
991
Contrast setting for LCD display
0–63
53