NOTES
Special notes referring to the table:
When undervoltage or instantaneous power failure has occurred, alarm display or alarm
output is not provided but the inverter itself is protected. Overcurrent, regenerative
overvoltage or other protection may be activated at power restoration according to the op-
erating condidition.
Temperature applicable for a short period in transit, etc.
The braking torque indicated is short-duration average torque (which varies with motor
loss) when the motor alone is decelerated from 50Hz in the shortest time and is not a con-
tinuous regenerative torque. When the motor is decelerated from the frequency higher than
the base frequency, the average deceleration torque will reduce. Since the inverters of the
FR-E500 EC Series does not contain a brake resistor, use the optional brake resistor when
regenerative energy is large. A brake unit BU may also be used.
Not valid for the inverters FR-E 520S-0.4 k, -0.75 k EC and FR-E 540-0.4 k, -0.75 k EC
which are not equipped with a cooling fan.
FR-E 500 EC
11
Specifications
Type
Description
Control
inputs
Operation functions
Maximum and minimum frequency setting, frequency jump operation, external thermal input se-
lection, instantaneous power failure restart operation, forward run/reverse run prevention, slip
compensation, operation mode selection, off-line auto tuning function, PID control, computer link
operation (RS485), open network operation
Output
signals
Operation
status
2 output types (open collector output) can be selected: inverter running, frequency reached, fre-
quency detection, overload warning, zero return detection, output current detection, maximum
PID, minimum PID, PID forward run, PID reverse run, operation ready, minor failure and error.
1 relay contact can be selected for the output (230V AC; 0.3A / 30V DC; 0.3A)
Analog
signal
One of the following output types can be selected:
output frequency, motor current, output voltage, analog output (0–10V DC).
Dis
p
la
y
option
Displayed on
control panel
(FR-PU04/
FR-PA02-02)
Operating
state
Output frequency, motor current, output voltage, frequency setting value, operation speed
Alarm display
Error messages are displayed after a protective function is activated.
Up to 4 error codes can be stored.
Additional
diplays on
control panel
FR-PU04
Operating
state
Signal status of input and output terminals
Interactive
operating
guide
Interactive guide for operation and troubleshooting via help function
Protection
Functions
Overcurrent cutoff (during acceleration, deceleration, constant speed), regenerative overvoltage
cutoff, undervoltage
���
, instantaneous power failure
���
, overload cutoff (electronic thermal relay),
brake transistor error, ground fault overcurrent, output short circuit, stall prevention, overload
warning, brake transistor overheating, fin overheating, fan error
���
, option error, parameter error,
PU connection error, output phase error
Ambient
humidity
Ambient temperature
−
10°C to +50°C (non-freezing)
(For selection of the overload capacity of 150% the max. temperature is 40°C)
Storage temperature
���
−
20°C to +65°C
Ambient humidity
Max. 90% RH (non-condensing)
Ambient conditions
For indoor use only, avoid environments containing corrosive gases, install in a dust-free location.
Altitude
Max. 1000m above sea level;
After that derate by 3% for every extra 500m up to 2500m (91 %).
Shock resistance
10g (3 times each in 3 directions)
Vibration resistance
0.6g: resistance to vibrations from 10 to 55Hz for 2 hours along all 3 axes
Certifications
UL / CSA / CE / EN