NOTE
It is recommended to use a shielded motor cable in order to reduce cable radiation.
The maximum wiring length of the motor cable
The following table shows the terminal assignment of circuit terminals
E
CAUTION
:
Switching the unit off and on repeatedly with the mains power supply at short inter-
vals can damage the switch-on current limiter. Because of this the unit should always
be started and stopped with the control unit or via the STF/STR and STOP control sig-
nals.
Wiring
FR-E 500 EC
15
Capacity Classes FR-E 500
0.4 k
0.75 k
1.5 k
2.2 k
3.7 k
Non-low acoustic noise mode
200V class
300m
500m
500m
500m
500m
400V class
200m
200m
300m
500m
500m
Low acoustic noise mode
200V class
200m
300m
500m
500m
500m
400V class
30m
100m
200m
300m
500m
Terminal
Terminal name
Description
Main
circuit
c
onnector
L1, N
L1, L2, L3
Mains supply connection
Mains power supply of the inverter
+,
−
External brake unit connection
An external brake unit can be connected to the
ter and
−
.
+, PR
Optional external brake
resistor connection
An optional external brake resistor can be
connected to the ter and PR.
P1, +
DC choke coil connection
An optional choke coil can be connected to the
terminals P1 and +. Remove the jumper before in-
stalling the optional choke coil.
U, V, W
Motor connection
Voltage output of the inverter (3-phase, 0V up to
power supply voltage, 0.2–400Hz)
PE
Protective earth connection of inverter
1-phase
power supply
3-phase
power supply
Q1
U
V
W
I
I
L1
−
N
N
PE
+
P1
L1
FR-E 520 S EC
U
V
W
−
PE
+
P1
FR-E 540 EC
Q1
I
I
L1
L2
L2
I
L3
L3
L1
PR