E
CAUTIO
N
:
Terminals 10 and 5 must not be connected to each other. Otherwise the internal volt-
age output for the connection of the potentiometer will be damaged.
NOTE
The control terminals RL/RM/RH/MRS (input terminals) and RUN/FU/A, B, C (output termi-
nals) can be assigned to other functions or signals with the help of the control unit
(FR-PA02-02 or FR-PU04), the PC software or a field bus system. Please see the frequency
inverter manual for details on the procedure for this.
Please note the following important points for proper frequency inverter control performance:
쎲
The following conditions must be fulfilled for the frequency inverter to output a rotating field
correctly:
–
The inverter lock must be deactivated (see below).
–
You must input both a direction of rotation signal and a frequency setpoint value to the
inverter.
쎲
If the frequency inverter does not work properly even though the wiring of the control termi-
nals block appears to be correct please check the following points:
–
Is the frequency inverter reporting an error condition (red alarm LED)?
–
Is the correct operating mode selected (EXT mode for control via the terminal block, PU
mode for control via the control unit)?
–
Is the inverter lock (terminal MRS) deactivated and is the inverter receiving a rotation
start signal (terminal STF or STR)?
–
Is the inverter receiving a valid frequency setpoint value > the start frequency (voltage
signal on terminal 2, current signal on terminal 4, preset frequency digital inputs)?
–
Are the control terminals you are using programmed correctly?
Wiring
FR-E 500 EC
19
Signal
Terminal
Terminal name
Description
Output
signals
Analog
AM
Analog output
One of the following monito-
ring functions can be selec-
ted: output frequency, motor
current or motor voltage.
E.g. a DC voltmeter can be
connected.
Factory setting
of output item:
output frequency
The max. output
voltage is 10V,
the max. current
is 1mA.
Comm
un.
RS485
—
Connection of control panel
(RS485)
Communication operation can be performed
through RS485. I/O standard: RS485,
Multi-Drop operation, max. 19200 Baud, over all
length max. 500m