'22 • PAC-SM-412
-
20
-
Individual operation (Factory default)
All units operation (Local setting)
CnT-6 or
CnTA
ON
OFF
ON
OFF
Only the unit
directly connected
to the remote control
can be operated.
Only the unit
directly connected
to the remote
control can be
stopped opeartion.
All units in one
remote control
system can be
operated.
All units in one
remote control
system can be
stopped operation.
Unit
①
only
Unit
①
only
Units
①-Ⓕ
Units
①-Ⓕ
When more than one indoor unit (Max. 16 indoor units) are connected in one wired remote control system:
(1) With the factory default, external input to CnT-6 or CnTA is effective for only the unit
①
.
(2) When setting “For all unit” (Local setting), all units in one remote control system can be controlled by external
input to CnT-6 or CnTA on the indoor unit
①
.
(3) External input to CnT-6 or CnTA on the other indoor unit than the unit
①
is not effective.
(21) Operation permission/prohibition
(In case of adopting card key switches or commercially available timers)
When the indoor function setting of wired remote control for “Operation permission/prohibition” is changed from
“Invalid (Factory default)” to “ Valid”, following control becomes effective.
・
CnT
・
CnTA
XR5
XR1
1
2
3
4
5
6
XR3
XR4
XR2
Option
XR5
Note (1)
CnTA function can be
changed by RC-EXZ3A.
XR6
1
2
Normal operation
(Factory default)
Operation permission/prohibition mode
“Valid” (Local setting)
CnT-6 or
CnTA
ON
OFF
ON
OFF
Operation
Stop
Operation
permission
*1
Operation prohibition
(Unit stops)
*1
Only the “LEVEL INPUT” is acceptable for external input
, however when the indoor function setting of
“
Level input (Factory default)
” or “Pulse input” is selected by the function for “External input” of the wired
remote control, operation status will be changed as follows.
In case of “Level input” setting
In case of “Pulse input” setting
Unit operation from the wired
remote control becomes
available
※
1
Unit starts operation
※
2
※
1) In case that “Operation permission/prohibition mode” setting is “Valid” and “External input” setting is “Level
input (Factory default)”;
①
When card key switch is ON (CnT-6 or CnTA ON: Operation permission), start/stop operation of the unit
from the wired remote control becomes available.
②
When card key switch is OFF (CnT-6 or CnTA OFF: Operation prohibition), the unit stops operation in
conjunction with OFF signal, and start/stop operation of the unit from the wired remote control becomes
unavailable.
※
2) In case that “Operation permission/prohibition mode” setting is “Valid” and “External input” setting is
“Pulse input (Local setting)”;
①
When card key switch is ON (Operation permission), the unit starts operation in conjunction with ON signal,
and also start/stop operation of the unit from the wired remote control becomes available.
②
When card key switch is OFF (Operation prohibition), the unit stops operation in conjunction with OFF signal,
and start/stop operation of the unit from the wired remote control becomes unavailable.
3) This function is invalid only at “Center mode” setting done by central control.