Please refer to the following information to design your ducted air-conditioning system.
Attention
•
This unit can control up to 4 zones, including common zones (A zone in which a damper is
not installed).
Do not exceed 4 zones.
Advice
Common zone: A zone in which a damper is not installed.
Spill zone: A zone in which a damper open automatically.
a) With comon zone
Zone 1
Relay Parts
Common zone
Master Zone
Remote Control
Slave Zone
Remote Control
Damper 1
Zone 2
Damper 2
Zone 3
Damper 3
Ducted indoor unit
<Fig 1>
Fig 1 shows a system example, where common zone, 3 damper motors 2 remote controls are connected.
b) No comon zone
(Spill zone setting required)
Zone 2
Relay Parts
Zone
1
Spill zone
Damper 2
Zone 3
Damper 3
Zone 4
Damper 4
Damper 1
Ducted indoor unit
Master Zone
Remote Control
Slave Zone
Remote Control
<Fig 2>
Fig 2 shows a system example, where no common zone, 4 damper motors, 2 remote controls are connected.
Zone remote
control
Maximum 2 remote controls can be
connected.
Damper motor
(Locally supplied)
Only drive open, drive close damper motor
can be connected. (Spring motor damper
can not be used.)
If you use 24V AC motors, ensure the
transformer is adequately sized for the zone
motors connected and is suitable for the
installation conditions.
Symbol
Legend
Air
Duct
Damper
Damper moter
Spill zone
③
Relay parts and transformer
①
System outline
Choosing the relay parts and transformer installation lacation
• Do not install in outdoor location.
•
Avoid
locations where the relay parts and transformer are exposed to direct sunlight or other
sources of heat.
• Select a location where easy wiring access to the power source is available.
•
Avoid locations where combustible gases may leak, be produced, flow, or accumulate.
• Select a level location that can bear the weight and prevent vibration of the relay parts and
transformer.
• Avoid locations where the relay parts and transformer are exposed to oil, steam, or sulfuric
gas.
• Do not install in location that ambient temperature exceeds 60°C and relative humidity exceeds
80%.
• Do not install on top of the indoor unit.
b) In the case of 3 zones
Zone 1
Relay Parts
Common zone
Damper 1
Zone 2
Damper 2
Ducted indoor unit
50% of
total air flow
25% of
total air flow
25% of
total air flow
Master Zone
Remote Control
Slave Zone
Remote Control
c) In the case of 2 zones
Relay Parts
Common zone
Damper 1
Ducted indoor unit
50% of
total air flow
Zone 1
50% of
total air flow
Master Zone
Remote Control
Slave Zone
Remote Control
• In zone control system, one or two remote controls (Master and slave) can not control multiple indoor units.
Connect one or two remote controls with one indoor unit.
②
Duct design
Attention
• Design the duct so that the common zone or spill zone equal
50% of total air
• Ducts in zones other than common zone or spill zone should have equal static pressure
(equal air
• Be sure to also refer to the indoor unit installation manual.
• Common zone installation is recommended. However if you prefer no common zone system,
you must set spill zones with the remote control.
a) In the case of 4 zones
Zone 1
Relay Parts
Common zone
Damper 1
Zone 2
Damper 2
Zone 3
Damper 3
Ducted indoor unit
50% of
total air flow
17% of
total air flow
17% of
total air flow
17% of
total air flow
Master Zone
Remote Control
Slave Zone
Remote Control
2.3 Zone control installation manual (FDU, FDUA series only)
'22 • PAC-SM-412
-
96
-