85
-
(9) Checking the indoor electrical equipment
(a) Indoor PCB check procedure
(b) Outdoor unit
Is there voltage between terminal
blocks
①
and
②
? (AC 220/230/240
V)
Indoor electrical components
are normal.
Is the voltage between terminal
blocks
②
and
③
oscillating between
DC 0 and 20V?
Inspect power source
for outdoor unit.
Replace fuse.
Replace indoor PCB.
Is the fuse burnt out? (3.15 A)
YES
YES
YES
NO
NO
NO
(b) Indoor unit fan motor check procedure
This is a diagnostic procedure for determining if the indoor unit’s fan motor or the indoor PCB is broken down.
1) Indoor PCB output check
a) Turn off the power.
b) Remove the front panel, then disconnect the fan motor lead wire connector.
c) Turn on the power. If the unit operates when the ON/OFF button is pressed, if trouble is detected after the voltages
in the following figure are output for approximately 30 seconds, it means that the indoor PCB is normal and the
fan motor is broken down.
If the voltages in the following figure are not output at connector pins No.
①
,
④
and
⑤
, the indoor PCB has failed
and the fan motor is normal.
2) Fan motor resistance check
Notes (1) Remove the fan motor and measure it without power connected to it.
Notes
(2) If the measured value is below the value when the motor is normal, it means
that the fan motor is faulty.
⑥
⑤
④
③
②
①
⑥
⑤
④
③
②
①
FM
I
DC15V
Indoor PCB
DC 308~336V
DC several V
(4~6 V)
CNU
(–)
GND
Blue
Yellow
White
Black
Red
Sensor
Operation
mode
Phenomenon
Shortcircuit
Disconnected wire
Heat exchanger
sensor
Cooling
System can be operated normally.
Compressor stop.
Heating
Defrosting is not performed.
Defrosting is performed for 10 minutes at approx. 35 minutes.
Ourdoor air
temperature sensor
Cooling
System can be operated normally.
Compressor stop.
Heating
Defrosting is not operated.
Defrosting is performed for 10 minutes at approx. 35 minutes.
Discharge pipe
sensor
All modes
Compressor overload protection is disabled.
(Can be operated.)
Compressor stop
Measuring point
Resistance when normal
① - ③
(Red
-
Black)
20 MΩ or higher
④ - ③
(White
-
Black)
20 MΩ or higher
Measuring
point
Resistance when
normal
① - ③
DC 308~336V
④ - ③
DC 15V
⑤ - ③
DC several V (4~6V)
⑥ - ③
DC several V (4~6V)