90
-
Notes (1) Do not use the refrigerant pressure to expel air.
(2) Do not use the compressor for evacuation.
(3) Do not operate the compressor in the vacuum condition.
Service hose
Liquid side
Gas side
Check joint
Charge hose
Vacuum
pump
Refrigerant
cylinder
Gauge
manifold
(2) Refrigerant charge
(a) Discharge refrigerant entirely from the unit and evacuate the unit.
Note: Addition of refrigerant without evacuation is unreasonable, because it will result in low charge or overcharge.
(b) Keep the gauge manifold and connect a refrigerant cylinder to the unit.
(c) Record the weight of the refrigerant cylinder on the balance. This is necessary for making sure of the charged refrigerant
amount.
(d) Purge air from the charge hose A
Firstly loose the connecting portion of the charge hose A at the gauge manihold side and open the valve
③
for a few seconds,
and then immediately retighten it after observing that gas is blow out from the loosened portion.
(e) Open the valve
①
and
③
after discharging air from the charge hose A , then the liquid refrigerant begins flowing from the
cylinder into the unit. Be sure to erect the refrigerant cylinder upright to let liquid refrigerant flow into the unit.
(f) When refrigerant has been charged into the system to some extent, refrigerant flow becomes stagnant, when that happens,
start the compressor in cooling cycle until the unit is filled with refrigerant to the specified weight.
(g) Making sure of the refrigerant amount, close the valve
③
(h) Disconnect the charge hose from the unit. Cover the valve ports of the refrigerant piping with caps and tighten them securely.
(i) Check for gas leakage applying a gas leak detector along the piping line.
(j) Start the air conditioner and make sure of its operating condition......high side and low side pressures and temperature dif-
ference between return air and supply air.
3.2 Servicing
(1) Evacuation
The evacuation is an procedure to purge impurities......noncondensable gas, air, moisture from the refrigerant equipment by us
-
ing a vacuum pump. Since the refrigerant R410A is very insoluble in water, even a small amount of moisture left in the refriger-
ant equipment will freeze, causing what is called water clogging.
¡
Evacuation procedure
(a) Check to ensure that there is no internal pressure in the unit. If there is an internal pressure,
it should be relieved through the check joint.
(b) Connect the service hoses of the gauge manifold to the check joint of the gas & liquid piping.
(c)
Connect a vacuum pump to the charge hose A . Repeat evacuation in the following sequence.
Airtighteness test completed
Vacuuming begins
Vacuuming completed
Vacuum gauge check
Fill refrigrant
Run the vacuum pump for at least one hour after the vacuum
gauge shows-101kPa or lower. (-755mmHg or lower)
Confirm that the vacuum gauge indicator does not rise even if
the system is left for one hour or more.
When the system has remaining moisture
inside or leaky point, the vacuum gauge
indicator will rise.
Check the system for a leaky point and
then draw air to create a vacuum again.