81
-
Current safe stop
Overload operation, compressor
lock, overcharge
Secure space for inlet and outlet.
Adjust the refrigerant amount properly.
Is the refrigerant amount mormal?
Is outdoor ventilation condition good?
Inspect compressor.
Inspect outdoor air temp sensor
YES
YES
NO
NO
YES
Defective outdoor PCB
Replace compressor.
Replace sensor.
Current cut
NO
In the service valves of the outdoor
unit open?
Is output voltage applied to all 3
phases of power transistor?
Inspect compressor.
Defective outdoor PCB
Secure space for suction
and blow out.
¡
Check compressor wiring visually.
¡
Check insulation resistance. (1 M
Ω
or over)
¡
Check coil wire resistance.
Model 20~35 : 1.703
Ω
or more at 20ºC
Model 50, 60 : 0.953
Ω
or more at 20ºC
If check results are normal,
compressor is locked.
Compressor lock, Compressor wiring short circuit, Compressor output is open phase,
Outdoor PCB is faulty, Service valve is closed, EEV is faulty, Compressor faulty.
Is there any shortcircuit?
Does electronic expansion valve
operate normally?
When the inverter is operated
after disconnecting the wires of
compressor, does the current cut
operate within 10 minutes? (
*
1)
YES
NO
YES
NO
Open the service valves
Defective EEV
Defective outdoor PCB
Defective outdoor PCB
For inspection of electronic expansion valve, see page 89
*
1
If it is normal, it is the rotor lock problem.
For the output voltage check of power transistor,
see page 86
YES
NO
YES
NO
YES