Trouble of outdoor unit
Insufficient refregerant amount, Faulty power transistor, Broken compressor wire
Service valve close, Defective EEV, Defective outdoor PCB
Check power supply.
Is the service valves of the outdoor
unit open?
Is the refrigerant amount normal?
Does electronic expansion valve
operate properly?
Is the output voltage applied to all
3 phases of power transistor?
Is the connector for compressor
connection good?
Is the checked result of insulation
resistance and coil resistance (
*
1)
of compressor motor OK?
Replace compressor
.
Open the service valves.
Adjust the refrigerant
amount properly
Defective EEV or outdoor PCB.
Defective outdoor PCB.
Correct connection
Defective outdoor PCB.
Is the power supply voltage OK?
*
1
Model 20~35 : 1.703
Ω
or more at 20ºC
Model 50, 60 : 0.953
Ω
or more at 20ºC
220V : 198~242V
230V : 207~253V
240V : 216~264V
Proper power supply voltages are as follows.
(At the power supply outlet)
◆
Judgment of refrigerant quantity
(1)
Phenomenon of insufficient refrigerant
(a) Loss of capacity
(b) Poor defrosting
(Frost is not removed completely.)
(c) Longer time of hot keep
(5 minute or more)
(Normal time: Approx. 1 – 1 minute and 30 seconds)
For inspection of electronic expansion valve, see page89
For the output voltage check of power transistor, see page86
YES
NO
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO