– 65 –
4.
Press Upper/Lower limit (°C) of SET TEMP. in Heating. Select temperature by pressing
or
button, and press OK button.
If you do not want to make the setting, press the cancel button.
Setting temperatures can be set in the following ranges.
<When Air-Conditioner/Other is selected (
page 47)>
Lower limit value
Upper limit value
Cool/Dry/Auto
16 - 28°C
30 - 35°C
Heat
10 - 18°C
22 - 30°C
<When HMU is selected (
page 47)>
Lower limit value
Upper limit value
Cool/Dry/Auto
5 - 28°C
28 - 30°C
Heat
15 - 22°C
22 - 55°C
5.
Select VALID or INVALID of Limit SET TEMP.
When you select VALID, the set temperature of the indoor unit which exceeds the upper limit
or is lower than the lower limit is changed to the upper or lower limit.
6.
Press the SET button. Press the Yes button on the con
fi
rmation screen.
When you do not want to set, press the No button.
Control Function Setting
You can set the temperature for energy saving setting and auto switch mode.
1.
Press FUNCTION SETTING button on the OPERATOR MENU screen.
page 11
2.
Press the CONTROL FUNCTION SETTING button on the FUNCTION SETTING screen.
5
4
3
6
11
8
7
9
10
<Energy Saving setting>
3.
Press Start TEMP. (°C) in COOL Mode of Energy saving Setting.
You can set the outside temperature to start the energy saving in cool and dry mode.
4.
Press Release TEMP. (°C) in COOL Mode of Energy saving Setting.