79
Disturbance in comfort
■ External switch for changing the room heating activ- ated.
– Check any external switches.
■ Air in the climate system.
– Vent the climate system.
■ Closed valves to the climate system.
– Open the valves.
■ Incorrectly adjusted fl ow across the heat pump.
– Check whether alarm high condenser in (163) or high
condenser out (162) is in the alarm log. Follow the
instructions for adjusting charge fl ow.
High room temperature
■ Too high set value on the automatic heating control.
– Enter menu 1.1 (temperature) and reduce the offset
heating curve. If the room temperature is only high in
cold weather the curve slope in menu 1.9.1 "heating
curve" needs adjusting down.
■ External switch for changing the room heating activated.
– Check any external switches.
Low system pressure
■ Not enough water in the climate system.
– Top up the water in the climate system.
The compressor does not start
■ There is no heating requirement.
– The heat pump does not call on heating nor hot water.
■ Temperature conditions tripped.
– Wait until the temperature condition has been re- set.
■ Minimum time between compressor starts has not been
reached.
– Wait 30 minutes and check if the compressor has started.
■ Alarm tripped.
– Follow the display instructions.
Additional heating only
If you are unsuccessful in rectifying the fault and are unable to
heat the house, you can, whilst waiting for assistance, continue
running the heat pump in ”add. heat only”. This means that
additional heating only is used to heat the house.
Set the installation to additional heat
mode
1. Go to menu 4.2 op. mode.
2. Mark ”add. heat only” using the control knob and then press
OK button.
Return to the main menus by pressing the Back button.
CAUTION
When commissioning without MTH air/water heat pump an
alarm communication error may appear in the display.
The alarm is reset if the relevant heat pump is deactivated
in menu 5.2.2 ("installed heat pump").
Содержание HMK60
Страница 2: ...1 2 ...
Страница 87: ...85 Technical data Electrical circuit diagram HSB60 ...
Страница 88: ...86 Technical data HMK60 RC HY FDCW60VNX A FDCW60VNX A 2 FDCW60VNX A 3 ...
Страница 89: ...87 Technical data FDCW60VNX A 2 FDCW60VNX A 3 RC HY RC HY RC HY ...
Страница 90: ...88 Technical data RC HY RC HY RC HY ...
Страница 93: ...91 Technical data sheet 3 ...
Страница 94: ...92 Technical data sheet 4 ...
Страница 97: ...95 Technical data sheet 3 ...
Страница 98: ...96 Technical data sheet 4 ...
Страница 99: ...97 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Страница 100: ...98 Technical data sheet 6 ...
Страница 101: ......
Страница 104: ...1 2 FDCW71VNX FDCW100VNX LEK LEK ...
Страница 189: ...85 Technical data Electrical circuit diagram HSB100 ...
Страница 190: ...86 Technical data HMK100 RC HY FDCW FDCW FDCW ...
Страница 191: ...87 Technical data FDCW FDCW RC HY RC HY RC HY ...
Страница 192: ...88 Technical data RC HY RC HY RC HY ...
Страница 195: ...91 Technical data sheet 3 ...
Страница 196: ...92 Technical data sheet 4 ...
Страница 199: ...95 Technical data sheet 3 ...
Страница 200: ...96 Technical data sheet 4 ...
Страница 201: ...97 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Страница 202: ...98 Technical data sheet 6 ...
Страница 203: ......
Страница 206: ......
Страница 277: ...71 Technical data Electrical circuit diagram HSB140 ...
Страница 280: ...74 Technical data sheet 3 ...
Страница 281: ...75 Technical data sheet 4 ...
Страница 284: ...78 Technical data sheet 3 ...
Страница 285: ...79 Technical data sheet 4 ...
Страница 286: ...80 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Страница 287: ...81 Technical data sheet 6 ...