Pipe installation
Water circuit
Connection to heating system
Connect XL1 to supply line and X2 to return line from
heating system.
■ All required safety devices and shut-off valves must be
installed as close to the indoor unit as possible.
■ Install bleed valves where necessary, highest point of the
water system in usual case.
■ When connecting to a system with thermostats on all
radiators, install an overfl ow valve or remove some of the
thermostats to ensure suffi
cient fl ow.
■ See section Dockings on page 25 for outline diagram.
■ Install a safety valve with manometer on heating circuit and
hot water circuit. (FL2)
For HSB100 install a safety valve for heating circuit on the
water pipe returning to indoor unit since it doesn’t have
port for FL2.
The entire length of the overfl ow water pipe from the safety
valves must be inclined to prevent water pockets and must
also be frost proof.
■ The end of overfl ow water pipe from the safety valves must be
left open to the atmosphere. The water may drip from the pipe.
HSB100
XL14 XL1 XL13 XL2
Install safety valve as close to XL2 as possible.
HMK100
XL9
XL8
XL3
XL5
XL4
XL2
XL1
XL10
XL11
Install safety valve FL2 on XL11.
Connection to hot water heater
For HSB100 indoor unit, it is necessary to connect PT storage
tank unit applying 3 way valve in order to use domestic hot
water function.
For HMK100 indoor unit, 180L tank unit is integrated in
indoor unit.
Housing disassembly of tank unit
Removable housing with thermal insulation facilitates trans-
port and installation of the storage tank. Disassembly the ho-
using in the following order (see next pages fi gure):
1. Remove the Temperature gauge, plug of the heating ele-
ment connector pipe and blanking plate of the inspection
opening.
2 Remove the upper cover of the housing together with
thermal insulation.
3. Remove the plugs from the connector pipes and black
bushings.
4. Remove the fixing screws and the strip connecting the
housing jacket.
5. Remove the jacket surrounding the tank (housing jacket.)
6. Remove the four-piece thermal insulation.
After the installation of the storage tank in its fi nal location,
reinstall the removed components in the reverse order.
Содержание HMK60
Страница 2: ...1 2 ...
Страница 87: ...85 Technical data Electrical circuit diagram HSB60 ...
Страница 88: ...86 Technical data HMK60 RC HY FDCW60VNX A FDCW60VNX A 2 FDCW60VNX A 3 ...
Страница 89: ...87 Technical data FDCW60VNX A 2 FDCW60VNX A 3 RC HY RC HY RC HY ...
Страница 90: ...88 Technical data RC HY RC HY RC HY ...
Страница 93: ...91 Technical data sheet 3 ...
Страница 94: ...92 Technical data sheet 4 ...
Страница 97: ...95 Technical data sheet 3 ...
Страница 98: ...96 Technical data sheet 4 ...
Страница 99: ...97 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Страница 100: ...98 Technical data sheet 6 ...
Страница 101: ......
Страница 104: ...1 2 FDCW71VNX FDCW100VNX LEK LEK ...
Страница 189: ...85 Technical data Electrical circuit diagram HSB100 ...
Страница 190: ...86 Technical data HMK100 RC HY FDCW FDCW FDCW ...
Страница 191: ...87 Technical data FDCW FDCW RC HY RC HY RC HY ...
Страница 192: ...88 Technical data RC HY RC HY RC HY ...
Страница 195: ...91 Technical data sheet 3 ...
Страница 196: ...92 Technical data sheet 4 ...
Страница 199: ...95 Technical data sheet 3 ...
Страница 200: ...96 Technical data sheet 4 ...
Страница 201: ...97 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Страница 202: ...98 Technical data sheet 6 ...
Страница 203: ......
Страница 206: ......
Страница 277: ...71 Technical data Electrical circuit diagram HSB140 ...
Страница 280: ...74 Technical data sheet 3 ...
Страница 281: ...75 Technical data sheet 4 ...
Страница 284: ...78 Technical data sheet 3 ...
Страница 285: ...79 Technical data sheet 4 ...
Страница 286: ...80 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Страница 287: ...81 Technical data sheet 6 ...