background image

3-2. FLARE CONNECTION

1) Cut the copper pipe as straight as possible with a pipe cutter.  (Fig. 1, 2)
2) Remove all burrs from the cut section of the pipe, ensuring that precautions are taken to 

avoid getting metal shavings into the piping. (Fig. 3)

Y$Z"M\    O&"&&
4)  Flaring work (Fig. 4, 5). Firmly hold copper pipe in the dimension shown in the table. Select 

A inch (mm) from the table according to the tool you use.

5) Check 

 ^"& \ %
 QN\ NMONN & &

3-3. PIPE CONNECTION

 % \  _ & ; ;M
 `N O\ " +M +;   N  
 z &  &&{ ; &&" +

in burns or frostbite.

Indoor unit connection

Connect both liquid and gas piping to indoor unit.
 &&+  NN |$\ N&&{ &&+-

frigeration oil on screw threads. Excessive tightening torque will result in damage on the 
screw.

 @O OYN\
 }_ ; ;M  N~O 

=M " \

Outdoor unit connection

Connect pipes to stop valve pipe joint of the outdoor unit following the same procedure 
detailed in Indoor unit connection.
 %O _&

3-4. INSULATION AND TAPING

1) Cover piping joints with pipe cover.
2) For outdoor unit side, insulate the piping, including valves.
3) Apply piping tape (G) starting from the connection on the outdoor unit.

 `&& ;  O"&

 "+ O  && &M -
tion.

Copper 
pipe

Good

Tilted

No good

Fig. 1

Fig. 2

Burr

Copper pipe

Spare reamer

Pipe cutter

Fig. 4

Fig. 3

Smooth all around

Even length 
all around

Inside is shin-
ing without any 
scratches.

Fig. 5

Fig. 6

Flare nut

Die

Copper pipe

Clutch type

Flaring tool

Wing nut type

Pipe diameter 

inch (mm)

inch

(mm)

A inch (mm)

Tightening torque

Clutch  

type tool  

for R410A

Clutch  

type tool  

for R22

Wing nut 

type tool  

for R22

ft-lb

N"$

ƒ"

ø 1/4  (6.35)

21/32 

(17)

0 to 0.02

(0 to 0.5)

0.04 to 0.06

(1.0 to 1.5)

0.06 to 0.08

(1.5 to 2.0)

10 to 13

(140 to 180)

13.7 to 17.7

ø 3/8  (9.52)

7/8 (22)

25 to 30

(350 to 420)

34.3 to 41.2

ø 1/2  (12.7)

1-1/32 

(26)

0.08 to 0.10

(2.0 to 2.5)

36 to 42

(500 to 575)

49.0 to 56.4

ø 5/8  (15.88)

1-5/32 

(29)

54 to 58

(750 to 800)

73.5 to 78.4

4-1. PURGING PROCEDURES AND LEAK TEST

1) Remove service port caps from stop valves on both sides of refrigerant lines. (The stop 

valves are fully closed when shipped.) Leave closed.

2) Connect gauge manifold to ports of stop valves.
3)  Evacuate the system to 4000 microns from both service valves. System manifold gauges 

must not be used to measure vacuum. A micron gauge must be used at all times. Break 
the vacuum with Nitrogen(N2) into the discharge service valve to 0 PSIG.

4) Evacuate the system to 1500 microns. Break the vacuum with Nitrogen(N2) into the 

discharge service valve to 0 PSIG.

5) Evacuate the system to 500 microns. 
6) Close gauge manifold valves, stop the pump, and conduct a 30 minute rise test.
7) System should hold 500 microns for a minimum of 1 hour.
8) Fully open all stop valves on both sides of gas pipe and liquid pipe. Operating without 

fully opening lowers the performance and this causes trouble.

9) Refer to 1-3 and charge the prescribed amount of additional refrigerant if needed. Be 

sure to charge slowly with liquid refrigerant. Otherwise composition of the refrigerant in 
the system may be changed and affect performance of the air conditioner.

10) Remove gauge manifolds and replace service port caps and tighten.
11) Leak  test

Uneven Burred

 WARNING

When installing the unit, securely connect the refrigerant pipes before starting the 
compressor.

B

Stop valve for 
GAS

Stop valve cap
(Torque 15 to 
22 ft-lb, 19.6 to 
?ƒ"O?!!
Y!!N”"$

Vacuum pump (or the vacuum 
pump with the function to 
&M; \$

Gauge manifold valve 
(for R410A)

Compound pressure gauge 
(for R410A)

–14.7 psi [Gauge] 
–!!& $

Handle 
Low

Handle High

Adapter for 
preventing the 
; \

Charge hose 
(for R410A)

*Close

*Open

Hexagonal wrench

Precautions when using the control valve

When attaching the control valve 
to the service port, valve core may 
deform or loosen if excess pressure 
is applied. This may cause gas leak.

Service port

Charge hose 

Body

Close

Open

Control valve

A

When attaching the control valve to 
the service port, make sure that the 
valve core is in closed position, and 
then tighten part A. Do not tighten 
part A or turn the body when valve 
core is in open position.

Service port cap
(Torque 10 to 13 ft-Ib, 
Y‹‹‹ƒ"O140 
to 180 kgfcm)

*4 to 5 turns

Stop valve for LIQUID

Pressure gauge
(for R410A)

4.  PURGING PROCEDURES, LEAK TEST, AND TEST RUN

Содержание TRANE NTXWST30A112A Series

Страница 1: ...t into the atmosphere Check that the refrigerant gas does not leak after installation has been completed If refrigerant leaks during installation ventilate the room QN N O N QN N O N N heater space heater stove etc harmful gases will be generated Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times higher than R22 Not using the appropriate tools and materi...

Страница 2: ...30 36A112A N INDOOR UNIT M N M Do not expose to direct sunlight also during the period following unpack ing to before use Y N N radio Operation of the air conditioner may interfere with _ N the affected device Q N N incandescent lights so the infrared remote control can operate the air conditioner normally M Note Install the indoor unit high on the wall where air can distribute over the entire roo...

Страница 3: ...g to local code requirements Note 1 Place indoor outdoor unit connecting wire A and power supply cord K at least 3 ft 1 m away from the TV antenna wire Unit inch Unit mm 4 11 16 in 120 mm or more Space for indoor unit working Please leave the space as shown in the picture for maintenance usage After the leak test apply insulating mate rial tightly so that there is no gap 33 1 16 14 3 16 19 11 16 A...

Страница 4: ... Process the end of indoor outdoor unit connecting wire A Fig 3 Attach it to the terminal block Be careful not to make mis wiring Attach the wire to the terminal block securely so that its core cannot be seen and no external force affects the connecting section of the terminal block 11 Firmly tighten the terminal screws After tightening verify that the wires are tightly fastened 12 Reinstall condu...

Страница 5: ...ndoor unit completely to the left to make placing the piping in the back of the unit easier 7 Cut out two pieces of cardboard from the shipping box use any two pieces of the four pieces roll each piece hook them onto the back rib and use them as spacer to lift the indoor unit Fig 5 8 Connect the refrigerant piping with the extension pipe B 9 Attach the lower part of the indoor unit into the instal...

Страница 6: ...w Do not raise Accumulated drain water Air Waving Water leakage Water leakage Water leakage Tip of drain hose dipped in water Ditch At least 1 31 32 in 50 mm gap Downward slope Drain hose Soft hose I D 19 32 in 15 mm Drain hose Hard vinyl chloride pipe I D 1 3 16 in 30 mm Insert securely Different diameter joint 27 9 16 in 70 cm or more Fig 1 Fig 2 Fig 3 Rear or bottom piping N O from the end 2 In...

Страница 7: ...e closed 2 Connect gauge manifold to ports of stop valves 3 Evacuate the system to 4000 microns from both service valves System manifold gauges must not be used to measure vacuum A micron gauge must be used at all times Break the vacuum with Nitrogen N2 into the discharge service valve to 0 PSIG 4 Evacuate the system to 1500 microns Break the vacuum with Nitrogen N2 into the discharge service valv...

Страница 8: ... outdoor unit 2 Fully close the stop valve on the liquid pipe side of the outdoor unit 3 Close the stop valve on the gas pipe side of the outdoor unit almost completely so that N 4 Start the emergency COOL operation To start the emergency operation in COOL mode disconnect the power supply plug and or turn off the breaker After 15 seconds connect the power supply plug and or turn on the breaker and...

Отзывы: