background image

1-3. SPECIFICATIONS

1-3-1.  POWER SUPPLY AND INDOOR/OUTDOOR WIRE 

CONNECTION

 …; N" =M;
 `;;  && ;  
 `;" N  "
 ‡+

Connecting wires and the ground wire

 }`† or stranded conductor `†.
 }; &&!!‰
 }&&+
* Follow local electrical codes.

Power supply cable and ground wire

 } `†10.
 }&&+
* Follow local electrical codes.

Note: 

When the indoor unit is powered from the outdoor unit, depending on 
local code, a disconnect switch needs to be installed to a power supply 
circuit.

Pipe length

Up to 25 ft. (7.5 m)

No additional charge is required.

Exceeding 25 ft. (7.5 m)

Additional charge is required.

(Refer to the table below.)

 ZN  ~"QN&&=?‚N‹‚"$O 

refrigerant (R410A) charge is required.

(The outdoor unit is charged with refrigerant for pipe length up to 25 ft. 
[7.5 m])

Limits

Pipe length

100 ft. (30 m) max.

Height difference

 50 ft. (15 m) max.

No. of bends

10 max.

 @ \ ;
 Z"MM MMN"O&&
 ZN &&  
 z NM;&&&&;

1-3-2. REFRIGERANT PIPES

 @&M O N &&
 ZN &&; ";!!""$"

 CAUTION

z N& ;$
Excessive insulation may cause incorrect installation of the indoor unit, 
and too little insulation may cause condensate to form.

Pipe

Outside 

diameter

""

thickness

Insulation 

thickness

Insulation material

inch (mm)

For liquid

3/8 (9.52)

0.0315 (0.8)

5/16 (8)

Heat resistant foam plas-
!!‚‡& M+

For gas

5/8 (15.88)

0.0394 (1.0)

5/16 (8)

 &

„{Œ

*+067+8$##9

NTYWST36A112A

*+<67+8$##9

NTXWST36A112A

INDOOR UNIT

Power supply 
‰O…‡O'$

208/230, 1, 60

^"& + (A)

1.0

Fan motor (F.L.A.)

(A)

0.76

OUTDOOR UNIT

Power supply 
‰O…‡O'$

208/230, 1, 60

 =%'
(time delay) 

(A)

25

^"& + (A)

21

Fan motor (F.L.A.)

(A)

0.93

Compressor

(R.L.A) (A)

16

(L.R.A) (A)

20

Control voltage

Indoor unit - Remote controller: (Wireless)

Indoor unit - Outdoor unit: DC12-24 V (Polar)

1-2. SELECTING THE INSTALLATION LOCATION

Refrigerant to be added

NTXWST30/36A112A

?' ‚N‚‚"$

NTYWST30/36A112A

!' ‚N?!"$

INDOOR UNIT 

 ` \;
 `  & M"
 „  &;+NM;
 `=&Do not expose 

to direct sunlight also during the period following unpack-
ing to before use.

 ` ; +
   YN"$"  +N" @‰ 

radio. Operation of the air conditioner may interfere with 
 @‰& "&" +;_N
the affected device.

 Q &  N   + &;N"\ 

incandescent lights (so the infrared remote control can 
operate the air conditioner normally).

 `  ;"M &  +

Note:

 

Install the indoor unit high on the wall where air can 
distribute over the entire room.

REMOTE CONTROLLER 

 `M&   +M;
 `  +
 ‡ & ;N?"$ ;M\

Check that signals from the remote controller from 
that position are received by the indoor unit (‘beep’ 
or ‘beep beep’ receiving tone sounds). Then, attach 
remote controller holder to a pillar or wall and install 
wireless remote controller.

Note: 

Q"M+&\ "& O
the signal from the wireless remote controller may not be 
received.

OUTDOOR UNIT

 `M+=&
 ` \
 `;  +;+&

or hot air.

 ` && M  ;&M

increase of operation sound or vibration.

 `N";;  
 QN    ;MO

be sure to secure the unit legs.

 `  !NY"$  +N"  

of TV set or radio. Operation of the air conditioner may 
interfere with radio or TV reception in areas where recep-
  "&" +;_N NN
device.

 Q ' +
 …             NN ;+ N  

blowing snow. In areas with heavy snow, please install 
  &+O &  ; N\;

Note:

 Q M ;"  &&& 

so as to reduce vibration.

 %   N+O        

location where continuous direct sunlight or excessive 
water can be avoided as much as possible.

Note:

When operating the air conditioner in low outside tem-
perature, be sure to follow the instructions described 
below.
 ƒM  &  

inlet/outlet side may be exposed directly to wind.

 @&M=&O 

with its air inlet side facing the wall and  ; N\;
on the air outlet side.

Avoid the following places for installation where air 
conditioner trouble is liable to occur.
 `\ "" ;  
 ` =M "N"

in the air.

 `&  

oily smoke (such as cooking areas and factories, in 
which the properties of plastic could be changed and 
damaged).

 ‡ +&  
 `    &
 `N_+_&"
 `   " N  M N ‰„^O

including phthalate compounds, formaldehyde, etc., 
which may cause chemical cracking.

Содержание TRANE NTXWST30A112A Series

Страница 1: ...t into the atmosphere Check that the refrigerant gas does not leak after installation has been completed If refrigerant leaks during installation ventilate the room QN N O N QN N O N N heater space heater stove etc harmful gases will be generated Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times higher than R22 Not using the appropriate tools and materi...

Страница 2: ...30 36A112A N INDOOR UNIT M N M Do not expose to direct sunlight also during the period following unpack ing to before use Y N N radio Operation of the air conditioner may interfere with _ N the affected device Q N N incandescent lights so the infrared remote control can operate the air conditioner normally M Note Install the indoor unit high on the wall where air can distribute over the entire roo...

Страница 3: ...g to local code requirements Note 1 Place indoor outdoor unit connecting wire A and power supply cord K at least 3 ft 1 m away from the TV antenna wire Unit inch Unit mm 4 11 16 in 120 mm or more Space for indoor unit working Please leave the space as shown in the picture for maintenance usage After the leak test apply insulating mate rial tightly so that there is no gap 33 1 16 14 3 16 19 11 16 A...

Страница 4: ... Process the end of indoor outdoor unit connecting wire A Fig 3 Attach it to the terminal block Be careful not to make mis wiring Attach the wire to the terminal block securely so that its core cannot be seen and no external force affects the connecting section of the terminal block 11 Firmly tighten the terminal screws After tightening verify that the wires are tightly fastened 12 Reinstall condu...

Страница 5: ...ndoor unit completely to the left to make placing the piping in the back of the unit easier 7 Cut out two pieces of cardboard from the shipping box use any two pieces of the four pieces roll each piece hook them onto the back rib and use them as spacer to lift the indoor unit Fig 5 8 Connect the refrigerant piping with the extension pipe B 9 Attach the lower part of the indoor unit into the instal...

Страница 6: ...w Do not raise Accumulated drain water Air Waving Water leakage Water leakage Water leakage Tip of drain hose dipped in water Ditch At least 1 31 32 in 50 mm gap Downward slope Drain hose Soft hose I D 19 32 in 15 mm Drain hose Hard vinyl chloride pipe I D 1 3 16 in 30 mm Insert securely Different diameter joint 27 9 16 in 70 cm or more Fig 1 Fig 2 Fig 3 Rear or bottom piping N O from the end 2 In...

Страница 7: ...e closed 2 Connect gauge manifold to ports of stop valves 3 Evacuate the system to 4000 microns from both service valves System manifold gauges must not be used to measure vacuum A micron gauge must be used at all times Break the vacuum with Nitrogen N2 into the discharge service valve to 0 PSIG 4 Evacuate the system to 1500 microns Break the vacuum with Nitrogen N2 into the discharge service valv...

Страница 8: ... outdoor unit 2 Fully close the stop valve on the liquid pipe side of the outdoor unit 3 Close the stop valve on the gas pipe side of the outdoor unit almost completely so that N 4 Start the emergency COOL operation To start the emergency operation in COOL mode disconnect the power supply plug and or turn off the breaker After 15 seconds connect the power supply plug and or turn on the breaker and...

Отзывы: