Installation plate (1)

Center of 
ø 3 in.  
(75 mm) 
hole

8-11/16 in. 

(220 mm) 
or more 

4-11/16 in. 
(120 mm) 
or more 

2-13/16 in. (70 mm) or more
5-1/8 in. (130 mm) or more for left 
and left back piping (using spacer)

Ceiling

Wall

Wall

Attachment screw (2)

* Same for left hole.

Insert 
the 
scale. *

Align the 
scale with 
the line. *

Level 

    -

 !""#$

2-1. ATTACHING THE INSTALLATION PLATE 

 %      & $' +;+=

?$"+

 @&M  & $N"M; O;   "

the holes indicated in the illustration. For added support, additional screws may also be 
installed in other holes.

 QN;O N &&$

Wall

Outdoor side

2-2. DRILLING

1) Determine where the holes will be located on the wall.
2) Drill a ø 3 in. (75 mm) hole. The outdoor side should be 6/32 to 9/32 in. (5 to 7 mm) lower 

than the indoor side.

3) Insert wall hole sleeve (C).

2-3. CONNECTING WIRES FOR INDOOR UNIT

Note:

When the indoor unit is powered from the outdoor unit, depending on local code, a discon-
nect switch needs to be installed to a power supply circuit.

1) Open the front panel.
2) Place the upper part of the indoor unit on the installation plate.
3) Remove electrical cover.
4) Remove VA clamp.
5) Remove corner box.
6) Remove cable guide.
7) Remove conduit plate.
8) Attach conduit pipe (for rear piping) / elbow joint (for right, left, or downward piping) to 

conduit plate with lock nut. The thread of the installed conduit pipe / elbow joint appearing 
inside should be less than 3/8 in. (10 mm). (Fig. 1) Elbow joint should appear less than 
1-3/16 in. (30 mm) outside. (Fig. 2)

9)  Process the end of ground wire (Fig. 3). Connect it to the ground terminal of electrical parts 

box.

10)  Process the end of indoor/outdoor unit connecting wire (A) (Fig.3). Attach it to the terminal 

block. Be careful not to make mis-wiring. Attach the wire to the terminal block securely 
so that its core cannot be seen, and no external force affects the connecting section of 
the terminal block. 

11)  Firmly tighten the terminal screws. After tightening, verify that the wires are tightly fastened.
12)  Reinstall conduit plate.
13)  Reinstall cable guide.
14) According to the piping direction, remove the shaded part of the left side of box (Fig.4) 

or corner box (Fig. 5).

15)  Reinstall VA clamp.
16)  Reinstall electrical cover.
17)  Reinstall panel assembly.

6/32-9/32 in.
(5-7 mm)

ø 3 in.
(75 mm)

Lead 
wire

5/8 in.
(15 mm)

2-3/16 in.
(55 mm)

Less than 3/8 in. 
(10 mm)

Conduit plate

Conduit pipe or 
elbow joint

Lock nut

Elbow joint   

(for right, left, or downward piping)

Less than 1-3/16 in. 
(30 mm)

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Corner box

Remove panel 
for piping on right 
side of unit

Remove panel for 
piping on bottom 
side of unit

Fig. 5

Box

Remove panel for piping 
on bottom left side of unit

Remove panel 
for piping on 
left side of unit

4 in. 

(100 mm)  

Remark:
*  A disconnect switch should be 

required.

  Check the local code.
** Use a ring tongue terminal in 

order to connect a ground wire 
to terminal.

Power supply 
208/230 V AC, 
1phase 2 wires, 
!'

INDOOR UNIT

Terminal block

208/230 V AC 
& O!'

OUTDOOR UNIT

Terminal 

block 1

Ground

Grounding terminal**

Grounding 
terminal**

Disconnect 
switch*

Pull tab to remove cable guide.

 ^ &&&

terminals

 %NMO M"

slack in the connecting wires.

Electrical cover

VA Clamp

Indoor 
terminal 
block

Electrical box

Cable guide

Grounding 
terminal

Conduit pipe

Lock nut

Conduit plate

Elbow joint

Conduit plate

or

2.  INDOOR UNIT INSTALLATION

Содержание TRANE NTXWST30A112A Series

Страница 1: ...t into the atmosphere Check that the refrigerant gas does not leak after installation has been completed If refrigerant leaks during installation ventilate the room QN N O N QN N O N N heater space heater stove etc harmful gases will be generated Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times higher than R22 Not using the appropriate tools and materi...

Страница 2: ...30 36A112A N INDOOR UNIT M N M Do not expose to direct sunlight also during the period following unpack ing to before use Y N N radio Operation of the air conditioner may interfere with _ N the affected device Q N N incandescent lights so the infrared remote control can operate the air conditioner normally M Note Install the indoor unit high on the wall where air can distribute over the entire roo...

Страница 3: ...g to local code requirements Note 1 Place indoor outdoor unit connecting wire A and power supply cord K at least 3 ft 1 m away from the TV antenna wire Unit inch Unit mm 4 11 16 in 120 mm or more Space for indoor unit working Please leave the space as shown in the picture for maintenance usage After the leak test apply insulating mate rial tightly so that there is no gap 33 1 16 14 3 16 19 11 16 A...

Страница 4: ... Process the end of indoor outdoor unit connecting wire A Fig 3 Attach it to the terminal block Be careful not to make mis wiring Attach the wire to the terminal block securely so that its core cannot be seen and no external force affects the connecting section of the terminal block 11 Firmly tighten the terminal screws After tightening verify that the wires are tightly fastened 12 Reinstall condu...

Страница 5: ...ndoor unit completely to the left to make placing the piping in the back of the unit easier 7 Cut out two pieces of cardboard from the shipping box use any two pieces of the four pieces roll each piece hook them onto the back rib and use them as spacer to lift the indoor unit Fig 5 8 Connect the refrigerant piping with the extension pipe B 9 Attach the lower part of the indoor unit into the instal...

Страница 6: ...w Do not raise Accumulated drain water Air Waving Water leakage Water leakage Water leakage Tip of drain hose dipped in water Ditch At least 1 31 32 in 50 mm gap Downward slope Drain hose Soft hose I D 19 32 in 15 mm Drain hose Hard vinyl chloride pipe I D 1 3 16 in 30 mm Insert securely Different diameter joint 27 9 16 in 70 cm or more Fig 1 Fig 2 Fig 3 Rear or bottom piping N O from the end 2 In...

Страница 7: ...e closed 2 Connect gauge manifold to ports of stop valves 3 Evacuate the system to 4000 microns from both service valves System manifold gauges must not be used to measure vacuum A micron gauge must be used at all times Break the vacuum with Nitrogen N2 into the discharge service valve to 0 PSIG 4 Evacuate the system to 1500 microns Break the vacuum with Nitrogen N2 into the discharge service valv...

Страница 8: ... outdoor unit 2 Fully close the stop valve on the liquid pipe side of the outdoor unit 3 Close the stop valve on the gas pipe side of the outdoor unit almost completely so that N 4 Start the emergency COOL operation To start the emergency operation in COOL mode disconnect the power supply plug and or turn off the breaker After 15 seconds connect the power supply plug and or turn on the breaker and...

Отзывы: