Indoor unit

Wall hole 
sleeve (C)

Cut off the 
extra length.

Pipe attach-
ment strap 
(E)

Use the wall hole sleeve 
(C) to prevent indoor/
outdoor connecting wire 
(A) from contacting metal 
parts in the wall and to 
protect the wiring from 
rodents.

Wall hole cover (D)

Attachment screw (F)

Outdoor unit installation

2-13/16 in. (70 

mm) or more/ 

5-1/8 in. (130 mm) 

or more for left and 

left back piping 

(using spacer)

1-4. INSTALLATION DIAGRAM

ACCESSORIES

Check the following parts before installation.
<Indoor unit>

(1) Installation plate

1

(2)

Attachment screws for the installa-
tion plate 
4 × 25 mm

7

(3) Remote controller holder

1

(4)

Screws for the remote controller 
holder
3.5 × 16 mm (Black)

2

(5) Battery (AAA) for (6)

2

(6) Wireless remote controller

1

(7)

Felt tape 
(For left or left-rear piping)

2

(8)  

2

(9) Charge nut

1

(10) L-joint

1

FIELD-SUPPLIED PARTS

(A)

Indoor/outdoor unit connecting wire

*1

1

(B)

Extension pipe

1

(C)

Wall hole sleeve

1

(D)

Wall hole cover

1

(E)

Pipe attachment strap

2 to 5

(F)

Screw for (E) 4 × 20 mm

2 to 5

(G)

Piping tape

1

(H)

Putty

1

(I)

Drain hose 
(or soft PVC hose, 19/32 in. [15 
mm] inner diameter or hard PVC 
pipe VP16)

1

(J)

Refrigerant oil

1

(K)

Power supply cord

*1

1

Units should be installed by licensed contractor 
according to local code requirements.

Note:

*1

  Place indoor/outdoor unit connecting wire 

(A) and power supply cord (K) at least 3 ft. 
(1 m) away from the TV antenna wire.

Unit: inch

Unit: mm

4-11/16 in. 

(120 mm) 

or more

Space for indoor unit working

Please leave the space as shown in the 
picture for maintenance usage. 

After the leak test, apply insulating mate-
rial tightly so that there is no gap.

33-1/16

14-3/16

19-11/16

Air inlet

3-15/16

15-14/32

13

Air outlet

4-3/8 x 13/16 slot

1-18/32

40

840

100

500

Air inlet

392

330

360

Air outlet

4-10 x 21 slot

When the piping is to be attached to a wall 
comprised of tin plate or metal netting, use 
chemically treated wooden piece 25/32 in. 
(20 mm) or thicker between the wall and 
the piping, or wrap insulation vinyl tape 7 to 
8 turns around the piping.
To use existing piping, perform COOL 
operation for 30 minutes and pump down 
before removing the old air conditioner. 
Z" \  "
for new refrigerant.

5/16 in. (7 mm)  or more

4 in.

(100 mm)

or more

4 in.

(100 mm)

or more

14 in.

(350 mm)

or more

20 in. 

(500 mm)*3

or more

Note:

Do not 
obstruct 
the air 
outlet.

Indoor unit

Installation 

plate

Space

9-27/32 in. (250 

mm) or more

4 in. (100 mm)

 or more

8-11/16 in. 
(220 mm) 

or more

clear *2

*2

  20 in. (500 mm) or more when 

front and sides of unit are clear

*3

  When any 2 sides of left, right 

and rear of unit are clear

Seal the wall hole 
gap with putty (H).

Attach the pipe to 
wall with pipe at-
tachment strap (E).

Содержание TRANE NTXWST30A112A Series

Страница 1: ...t into the atmosphere Check that the refrigerant gas does not leak after installation has been completed If refrigerant leaks during installation ventilate the room QN N O N QN N O N N heater space heater stove etc harmful gases will be generated Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times higher than R22 Not using the appropriate tools and materi...

Страница 2: ...30 36A112A N INDOOR UNIT M N M Do not expose to direct sunlight also during the period following unpack ing to before use Y N N radio Operation of the air conditioner may interfere with _ N the affected device Q N N incandescent lights so the infrared remote control can operate the air conditioner normally M Note Install the indoor unit high on the wall where air can distribute over the entire roo...

Страница 3: ...g to local code requirements Note 1 Place indoor outdoor unit connecting wire A and power supply cord K at least 3 ft 1 m away from the TV antenna wire Unit inch Unit mm 4 11 16 in 120 mm or more Space for indoor unit working Please leave the space as shown in the picture for maintenance usage After the leak test apply insulating mate rial tightly so that there is no gap 33 1 16 14 3 16 19 11 16 A...

Страница 4: ... Process the end of indoor outdoor unit connecting wire A Fig 3 Attach it to the terminal block Be careful not to make mis wiring Attach the wire to the terminal block securely so that its core cannot be seen and no external force affects the connecting section of the terminal block 11 Firmly tighten the terminal screws After tightening verify that the wires are tightly fastened 12 Reinstall condu...

Страница 5: ...ndoor unit completely to the left to make placing the piping in the back of the unit easier 7 Cut out two pieces of cardboard from the shipping box use any two pieces of the four pieces roll each piece hook them onto the back rib and use them as spacer to lift the indoor unit Fig 5 8 Connect the refrigerant piping with the extension pipe B 9 Attach the lower part of the indoor unit into the instal...

Страница 6: ...w Do not raise Accumulated drain water Air Waving Water leakage Water leakage Water leakage Tip of drain hose dipped in water Ditch At least 1 31 32 in 50 mm gap Downward slope Drain hose Soft hose I D 19 32 in 15 mm Drain hose Hard vinyl chloride pipe I D 1 3 16 in 30 mm Insert securely Different diameter joint 27 9 16 in 70 cm or more Fig 1 Fig 2 Fig 3 Rear or bottom piping N O from the end 2 In...

Страница 7: ...e closed 2 Connect gauge manifold to ports of stop valves 3 Evacuate the system to 4000 microns from both service valves System manifold gauges must not be used to measure vacuum A micron gauge must be used at all times Break the vacuum with Nitrogen N2 into the discharge service valve to 0 PSIG 4 Evacuate the system to 1500 microns Break the vacuum with Nitrogen N2 into the discharge service valv...

Страница 8: ... outdoor unit 2 Fully close the stop valve on the liquid pipe side of the outdoor unit 3 Close the stop valve on the gas pipe side of the outdoor unit almost completely so that N 4 Start the emergency COOL operation To start the emergency operation in COOL mode disconnect the power supply plug and or turn off the breaker After 15 seconds connect the power supply plug and or turn on the breaker and...

Отзывы: