En-5

3-2. PIPE CONNECTION

1) Apply a thin coat of refrigeration oil (G) to the flared ends of the pipes and the 

pipe connections of the outdoor unit.

2) Align the center of the pipe with that of the pipe connections of the outdoor unit, 

then hand tighten the flare nut 3 to 4 turns.

3) Tighten the flare nut with a torque wrench as specified in the table.

•  Over-tightening may cause damage to the flare nut, resulting in refrigerant 

leakage.

•  Be sure to wrap insulation around the piping. Direct contact with the bare piping 

may result in burns or frostbite.

3-3. INSULATION AND TAPING

1) Cover piping joints with pipe cover.

2) For outdoor unit side, surely insulate every piping including valves.

3) Using piping tape (E), apply taping starting from the entry of outdoor unit.

•  Stop the end of piping tape (E) with tape (with adhesive agent attached).

•  When piping have to be arranged through above ceiling, closet or where the 

temperature and humidity are high, wind additional commercially sold insulation 

to prevent condensation.

 WARNING

When installing the unit, securely 

connect the refrigerant pipes before 

starting the compressor.

 CAUTION

When there are the ports which are 

not used, make sure their nuts are 

tightened securely.

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Fig. 5

Fig. 6

Tilted Uneven Burred

Good

No good

Burr

Copper pipe

Spare reamer

Pipe cutter

Smooth all 

around

Even length 

all around

Inside is shin-

ing without any 

scratches.

B

Flare nut

Die

Copper pipe

Clutch type

Flaring tool

Wing nut type

Copper 

pipe

Pipe diameter  

[inch (mm)]

[inch (mm)]

A [inch (mm)]

Tightening torque

Clutch type tool for R410A Clutch type tool for R22

Wing nut type tool for R22

ft-Ib

N•m

kgf•cm

1/4 (ø6.35)

21/32 (17)

0 to 0.02

(0 to 0.5)

0.04 to 0.06

(1.0 to 1.5)

0.06 to 0.08

(1.5 to 2.0)

10 to 13

13.7 to 17.7

140 to 180

3/8 (ø9.52)

7/8 (22)

25 to 30

34.3 to 41.2

350 to 420

1/2 (ø12.7)

1-1/32 (26)

0.08 to 1.0

(2.0 to 2.5)

36 to 42

49.0 to 56.4

500 to 575

5/8 (ø15.88)

1-5/32 (29)

54 to 58

73.5 to 78.4

750 to 800

3-1. FLARING WORK

1) Cut the copper pipe correctly with pipe cutter. (Fig. 1, 2)

2) Completely remove all burrs from the cut cross section of 

pipe. (Fig. 3)

•  Aim the copper pipe downward while removing burrs to 

prevent burrs from dropping in the pipe.

3) Remove flare nuts attached to indoor and outdoor units, 

then put them on pipe having completed burr removal. 

(Not possible to put them on after flaring work.) 

4) Flaring work (Fig. 4, 5). Firmly hold copper pipe in the 

dimension shown in the table. Select A inch (mm) from 

the table according to the tool selected.

5) Check 

•  Compare the flared work with Fig. 6.

•  If flare is noted to be defective, cut off the flared section 

and do flaring work again.

4-1. PURGING PROCEDURES AND LEAK TEST

1) Remove service port cap of stop valve on the side of the outdoor unit gas pipe. (The 

stop valves are fully closed and covered in caps in their initial state.)

2) Connect gauge manifold valve and vacuum pump to service port of stop valve on 

the side of the outdoor unit gas pipe.

3) Run the vacuum pump. (Vacuumize for more than 15 minutes.)

4) Check the vacuum with gauge manifold valve, then close gauge manifold valve, 

and stop the vacuum pump.

5) Leave as it is for one or two minutes. Make sure the pointer of gauge manifold valve 

remains in the same position. Confirm that pressure gauge shows -14.7 psi [Gauge] 

(-0.101 MPa).

6) Remove gauge manifold valve quickly from service port of stop valve.

7) Fully open all stop valves on the gas pipe and the liquid pipe. Operating without 

fully opening lowers the performance and this causes trouble.

8) Refer to 1-2., and charge the prescribed amount of refrigerant if needed. Be sure 

to charge slowly with liquid refrigerant. Otherwise, composition of the refrigerant in 

the system may be changed and affect performance of the air conditioner.

9) Tighten cap of service port to obtain the initial status.

10

) Leak test

Gauge manifold 

valve 

(for R410A)

Compound pressure 

gauge (for R410A)

Handle High

Charge hose 

(for R410A)

Pressure gauge

(for R410A)

-14.7 psi 

(-0.101 MPa)

Handle Low

Vacuum pump

(for R410A)

Stop valve cap

(Torque 15 to 

20 ft-lb, 21.5 to 

27.5 N•m, 220 

to 280 kgf•cm)

*Close

*Open

Hexagonal wrench

*4 to 5 turns

Service port cap

(Torque 7 to 9 ft-lb, 

10 to 12 N•m, 

100 

to 120 kgf•

cm)

Stop valve cap

(Torque 18 to 

22 ft-lb, 24.4 to 

30.4 N•m, 250 

to 310 kgf•cm)

Precautions when us-

ing the control valve

When attaching the control valve 

to the service port, valve core may 

deform or loosen if excess pres-

sure is applied. This may cause 

gas leak.

Service port

Charge hose 

(for R410A)

Body

Close

Open

Control 

valve

A

When attaching the control valve to 

the service port, make sure that the 

valve core is in closed position, and 

then tighten part A. Do not tighten 

part A or turn the body when valve 

core is in open position.

3.  FLARING WORK AND PIPE CONNECTION

4.  PURGING PROCEDURES, LEAK TEST, AND TEST RUN

VG79A940H01_01En.indd   5

2018/08/24   14:00:43

Содержание TRANE NTXMMX42A152A Series

Страница 1: ... de l appareil intérieur consultez la notice d installation de cet appareil Toute altération structurelle requise pour l installation doit être conforme aux exi gences du code du bâtiment local Manual de instalación Para el INSTALADOR En este manual sólo se describe la instalación de la unidad exterior Para instalar la unidad interior consulte el manual de instalación de dicha unidad Cualquier mod...

Страница 2: ... outlet make sure that there is no dust blockage or loose parts both in the outlet and on the plug Verify that the power supply plug is completely in the outlet If there is dust blockage or loose parts on the power supply plug or the outlet it could cause electric shock or fire If loose parts are found on the power supply plug replace it Securely attach the electrical cover to the indoor unit and ...

Страница 3: ...nd on the sides of the unit is required 2 Front blowing side open As long as space indicated in the figure is provided it is allowed to install the unit where obstacles are behind and on the sides of the unit No obstacle above the unit FREE SPACE REQUIRED AROUND OUTDOOR UNIT Service space When installing the unit in an area that is enclosed with walls such as a verandah be sure to have enough spac...

Страница 4: ...unit More than 3 15 16 in 100 mm Open as a rule More than 19 11 16 in 500 mm if the front and both sides are open More than 3 15 16 in 100 mm More than 7 7 8 in 200 mm if there are obstacles to both sides Open as a rule More than 19 11 16 in 500 mm if the back both sides and top are open More than 13 25 32 in 350 mm Outdoor unit installation Air inlet Air outlet 2 U shape notched holes Base bolt M...

Страница 5: ...code GROUND WIRE Use solid or stranded conductor Min AWG8 Use copper conductors only Follow local electrical code WARNING Use the indoor outdoor unit connecting wire that meets the Stand ards to connect the indoor and outdoor units and fix the wire to the terminal block securely so that no external force is conveyed to the connecting section of the terminal block An incomplete connection or fixing...

Страница 6: ...e to put them on after flaring work 4 Flaring work Fig 4 5 Firmly hold copper pipe in the dimension shown in the table Select A inch mm from the table according to the tool selected 5 Check Compare the flared work with Fig 6 If flare is noted to be defective cut off the flared section and do flaring work again 4 1 PURGING PROCEDURES AND LEAK TEST 1 Remove service port cap of stop valve on the side...

Страница 7: ... cold season But never use naked fire or steam Union Stop valve Liquid pipe Indoor unit Stop valve with service port Gas pipe Refrigerant gas cylinder operating valve for R410A Gauge manifold valve for R410A Charge hose for R410A Refrigerant gas cylinder for R410A with siphon Electronic scale for refrigerant charging Refrigerant liquid Outdoor unit Union Union Union Procedure Press the piping wiri...

Страница 8: ...n manual about the method for stopping the operation If too much refrigerant has been added to the air conditioner system the pressure may not drop to 0 1 to 0 psi Gauge 0 05 to 0 MPa or the protection function may operate due to the pressure increase in the high pressure refrigerant circuit If this occurs use a refrigerant collecting device to collect all of the refrigerant in the system and then...

Страница 9: ...fiche Veillez à enfoncer à fond la fiche d alimentation dans la prise secteur La présence de poussière de saleté ou d éléments desserrés sur la fiche d alimentation ou la prise secteur peut entraîner un choc électrique ou un incendie Remplacez les éventuels éléments desserrés Fixez correctement le couvercle du boîtier électrique de l unité interne et le panneau de service de l unité externe Si le ...

Страница 10: ...imatiseur alors que la température extérieure est basse veillez à observer les instructions ci dessous N installez jamais l unité externe dans un endroit où le côté présentant l entrée la sortie d air risque d être directement exposé au vent Pour protéger l unité externe du vent installez la de façon à ce que l entrée d air soit face au mur Pour éviter toute exposition au vent il est recommandé d ...

Страница 11: ...mum entre le mur et la tuyauterie ou isoler la tuyauterie en lui appliquant 7 à 8 couches de ruban isolant en vinyle Pour utiliser la tuyauterie existante effectuer un cycle COOL REFROI DISSEMENT de 30 minutes et lancer l aspiration avant de procéder à la dépose de l ancien climatiseur Reformer l écrou évasé en respec tant les dimensions des nouveaux tuyaux de réfrigérant 23 5 8 600 14 9 16 370 Fi...

Страница 12: ...os correspondants Lors du raccordement du cordon et ou du fil au bloc de sortie veiller à fixer chaque vis à la borne correspondante APPAREIL INTÉRIEUR Prévoir une longueur de câble de raccordement supplémentaire en vue des entretiens ultérieurs Remarque Un sectionneur devrait être nécessaire Vérifier le code local Connecter un câble de terre à une borne à l aide d une cosse à anneau Bloc de sorti...

Страница 13: ...de service pour recréer les conditions d origine 10 Test de contrôle des fuites 3 2 RACCORDEMENT DES TUYAUX 1 Appliquez une fine couche d huile réfrigérante G sur les embouts évasés des tuyaux ainsi que sur les raccords de tuyau de l appareil extérieur 2 Alignez la partie médiane du tuyau sur les raccords de tuyau de l appareil extérieur et serrez les écrous évasés à la main de 3 à 4 tours 3 Serre...

Страница 14: ...ouveau sur le commutateur de correc tion de câblage tuyauterie SW871 pour annuler cette fonction Vérifier ensuite les raccordements de câblage et tuyauterie de manière conventionnelle en faisant fonctionner les appareils intérieurs l un après l autre Pour utiliser cette fonction l appareil doit être alimenté Veiller à ne pas toucher des éléments autres que le commutateur notamment le panneau de co...

Страница 15: ...de l appareil intérieur pour la méthode d arrêt du système Si trop de réfrigérant a été ajouté au système de climatisation il se peut que la pression ne parvienne pas à baisser jusqu à 0 1 à 0 psi jauge 0 05 à 0 MPa ou la fonction de protection pourrait se déclencher en raison de la montée de pression dans le circuit de réfrigérant à haute pression Dans ce cas utilisez un dispositif de collecte du...

Страница 16: ...strucciones o piezas sueltas en el enchufe de alimentación o la toma podría provocar incendios o descargas eléctricas Si el enchufe de alimentación presenta piezas sueltas sustitúyalo Fije firmemente la cubierta de la instalación eléctrica a la unidad interior y el panel de servicio a la unidad exterior Si no se fijan con firmeza la cubierta de instalación eléctrica de la unidad interior y el pane...

Страница 17: ...za el acondicionador de aire cuando la temperatura exterior sea baja observe las instrucciones siguientes No instale nunca la unidad exterior en un lugar en el que el lado de entra da salida de aire quede expuesto directamente al viento Para evitar la exposición al viento instale la unidad exterior con el lado de entrada de aire hacia la pared Para evitar la exposición al viento se recomienda inst...

Страница 18: ...tratada químicamente de 25 32 pulg 20 mm o más de grosor entre la pared y los tubos o envuelva los tubos con 7 u 8 vueltas de cinta aislante de vinilo Para utilizar tuberías ya existentes active el modo COOL REFRIGERA CIÓN durante 30 minutos y realice el bombeo de vaciado antes de retirar el acondicionador de aire antiguo Adapte el abocardado a las dimensiones para el nuevo refrigerante 2 1 INSTAL...

Страница 19: ...su terminal correspon diente cuando fije los cables al panel de terminales Con vistas a un futuro mantenimiento prolongue los cables de conexión 2 2 CABLES DE CONEXIÓN PARA LA UNIDAD EXTERIOR ESPECIFICACIONES ELÉCTRICAS UNIDAD EXTERIOR NTXMPH20A122A NTXMPH24A132A NTXMPH30A132A NTXMMX42A152A Alimentación V FASE Hz 208 230 1 60 Tamaño máx fusible retardo A 40 Amperaje mín del circuito A 28 9 29 9 29...

Страница 20: ...ervicio de la válvula de retención situada en el lado de la tubería de gas de la unidad exterior Inicialmente las válvulas de retención están completamente cerradas y cubiertas con sus tapas 2 Conecte la válvula colectora de manómetro y la bomba de vacío al puerto de servicio de la válvula de retención en el lado de la tubería del gas de la unidad exterior 3 Ponga en funcionamiento la bomba de vac...

Страница 21: ...esulte difícil confirmarla use esta función para detectarla y corregirla siguiendo estos procedimientos Asegúrese de lo siguiente La unidad recibe corriente Las válvulas de retención están abiertas 4 4 EXPLICACIÓN PARA EL USUARIO Basándose en el MANUAL DE INSTRUCCIONES explique al usuario cómo utilizar el equipo de aire acondicionado cómo utilizar el controlador remoto cómo retirar los filtros de ...

Страница 22: ...lte el manual de instalación de la unidad interior para más detalles acerca del método de detención de la operación Si se ha añadido demasiado refrigerante al sistema con acondicionador de aire puede que la presión no baje de 0 1 a 0 psi manómetro de 0 05 a 0 MPa o que la función de protección se ponga en funcionamiento debido a la subida de presión en el circuito de refrigeración de presión eleva...

Страница 23: ...A4_white_tombo indd 1 2016 04 25 10 16 47 ...

Страница 24: ...MITSUBISHI ELECTRIC TRANE HVAC US LLC VG79A940H01 VG79A940H01_cover4 indd 2 2018 08 02 19 22 02 HEAD OFFICE 1340 SATELLITE BOULEVARD SUWANEE GA 30024 USA Publication No 691 XX Published Dec 2018 ...

Отзывы: