•The relays and extension cables are field supplied.
•Use a no-voltage contact and minute load relay (minimum application load 5VDC-1mA).
•The length of the connection cable extension should not exceed 10 m (32 ft). (Use a cable of 0.3 mm² (22AWG) or thicker.)
•Insulate the area with vinyl tape where the controller cable and the extension cable are connected.
•Insulate the end of unused lead wires with tape.
2. External signal output
*To use external output, an external input/output adapter (PAC-YT41HAA; sold separately) is required.
Requires a separate external power source.
(1) External signal output (CN3)
Operation signal will be output when one or more air conditioning units are in operation, and error signal will be output when one or
more units are in error.
The On-signal will be output even during an error.
(2) External output specifications
(3) Sample circuit recommended
Relay-driven circuit
CN3
1
2
Lead wire
Brown
Red
Signal
ON/OFF
Error/Normal
CN3
3
4
Lead wire
Orange
Yellow
Signal
Ground for all external outputs
Not used
Parts
External input/output
adapter
Model
PAC-YT41HAA
Usage
Enables the use of external
input/output function
Note
Required to use the external input/output function
5-wire cable (input) , 4-wire cable (output)
CN3
Diode (*2)
Power source
(*1)
Z
1
Z2
L
1
L2
Red
Brown
Orange
Yellow
Touch Controller
2
1
3
4
Maximum
10 m
(32 ft)
Z2
Z1
L1 : Operation indicator
L2 : Error indicator
Use relays that meet the following specifications for relays indicated as Z1
and Z2 in the figure.
Operating coil
Rated voltage:12 VDC or 24 VDC
Power consumption: 0.9 W or below
(*1) Select a power supply suitable for the relays used. (12 VDC or 24 VDC)
(*2) Use a diode at each end of the relay coil.
• Each element will turn on when an error occurs during operation.
• The maximum length of extension cable is 10 m (32 ft). (Use a cable of
0.3 mm² (22AWG) or thicker.)
• Insulate the area with vinyl tape where the controller cable and the
extension cable are connected.
• Relays, lamps, diode, extension cables are field-supplied.
●
To connect cables from an external input/output adapter to connectors CN2 and CN3 on the controller, cut out the appropriate
knockout holes on the controller with nippers.
After connecting the cables to the connectors, hold the cables in place with a piece of tape included with the external
input/output adapter (PAC-YT41HAA).
●
Use caution not to damage the circuit board with the nippers or other tools when cutting out knockout holes.
Note
7 Using an SD memor
y
card
8 Optional Parts
9 Note
■
A protective film is placed on the display.
Remove the protective film off the display before use.
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
WT05821X01
Field supplied
The Touch Controller has a slot for an SD memory card at the
bottom that can be used to update software.
Refer to the Initial Setting Manual for the detailed information
about updates.
*Only the 1GB and 2GB SD memory cards by SanDisk are
supported.
Back of controller
Cut out the
knockout holes.
CN2
External input connector
CN3
External output connector
Tape
External
input/output adapter
Bottom of controller
(a) Remove the SD memory card slot cover from the controller.
(b) Insert the SD memory card into the slot until it clicks.
(c) To remove the SD memory card, push it in until it clicks.
SD memory slot (for program updates)
“SD Logo is a trademark of SD-3C , LLC.”