•The relays and extension cables are field supplied.

•Use a no-voltage contact and minute load relay (minimum application load 5VDC-1mA).

•The length of the connection cable extension should not exceed 10 m (32 ft). (Use a cable of 0.3 mm² (22AWG) or thicker.)

•Insulate the area with vinyl tape where the controller cable and the extension cable are connected.

•Insulate the end of unused lead wires with tape.

2. External signal output 

*To use external output, an external input/output adapter (PAC-YT41HAA; sold separately) is required.

Requires a separate external power source.

(1) External signal output (CN3)

Operation signal will be output when one or more air conditioning units are in operation, and error signal will be output when one or 

more units are in error.

The On-signal will be output even during an error.

(2) External output specifications

(3) Sample circuit recommended

Relay-driven circuit

CN3

1
2

Lead wire

Brown

Red

Signal

ON/OFF

Error/Normal

CN3

3
4

Lead wire

Orange

Yellow

Signal

Ground for all external outputs

Not used

Parts

External input/output 
adapter

Model

PAC-YT41HAA

Usage

Enables the use of external 
input/output function

Note

Required to use the external input/output function
5-wire cable (input) , 4-wire cable (output)

CN3

Diode (*2)

Power source

(*1)

 

Z

Z2

L

L2

Red

Brown 

Orange 

Yellow

Touch Controller

2

1

3

4

Maximum

10 m

(32 ft)

Z2

Z1

L1 : Operation indicator

L2 : Error indicator

Use relays that meet the following specifications for relays indicated as Z1 

and Z2 in the figure.

Operating coil

Rated voltage:12 VDC or 24 VDC

Power consumption: 0.9 W or below

(*1) Select a power supply suitable for the relays used. (12 VDC or 24 VDC)

(*2) Use a diode at each end of the relay coil.

• Each element will turn on when an error occurs during operation.

• The maximum length of extension cable is 10 m (32 ft). (Use a cable of 

0.3 mm² (22AWG) or thicker.)

• Insulate the area with vinyl tape where the controller cable and the 

extension cable are connected.

• Relays, lamps, diode, extension cables are field-supplied.

To connect cables from an external input/output adapter to connectors CN2 and CN3 on the controller, cut out the appropriate 

knockout holes on the controller with nippers.

After  connecting  the  cables  to  the  connectors,  hold  the  cables  in  place  with  a  piece  of  tape  included  with  the  external 

input/output adapter (PAC-YT41HAA).

Use caution not to damage the circuit board with the nippers or other tools when cutting out knockout holes.

Note

7 Using an SD memor

y

 card

8 Optional Parts

9 Note

■ 

A protective film is placed on the display.

Remove the protective film off the display before use.

HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN 

WT05821X01

Field supplied

The Touch Controller has a slot for an SD memory card at the 

bottom that can be used to update software.

Refer to the Initial Setting Manual for the detailed information 

about updates.

*Only the 1GB and 2GB SD memory cards by SanDisk are 

supported.

Back of controller

Cut out the

knockout holes.

CN2

External input connector

CN3

External output connector

Tape

External

input/output adapter

Bottom of controller

(a) Remove the SD memory card slot cover from the controller.

(b) Insert the SD memory card into the slot until it clicks.

(c) To remove the SD memory card, push it in until it clicks. 

SD memory slot (for program updates)

“SD Logo is a trademark of SD-3C , LLC.”

(a)

(b)

(c)

Содержание TC-24A

Страница 1: ...ate safety measures against earthquakes to prevent the controller from causing injury To prevent injury install the controller on a flat surface strong enough to support its weight To reduce the risk of fire or explosion do not place flammable materials or use flammable sprays around the controller To reduce the risk of damage to the controller do not directly spray insecticide or other flammable ...

Страница 2: ...the detergent with a wet cloth and wipe off water with a dry cloth Take appropriate measures against electrical noise interference when installing the air conditioners in hospitals or facilities with radio communication capabilities Inverter high frequency medical or wireless communication equipment as well as power generators may cause the air conditioning system to malfunction Air conditioning s...

Страница 3: ...through the M NET transmission line to maintain communica tion during power failure Refer to the CITY MULTI DATABOOK for details The total power consumption of the connected devices should not exceed the capacity of the power supply units The Design Tool by MITSUBISHI ELECTRIC allows its user to design air conditioning systems easily TC 24A is compatible with the Design Tool version 3 71 or later ...

Страница 4: ...the field for registering the address of the system controller in each group Address setting Assign the lowest address to the main indoor unit in the group and assign sequential addresses to the rest of the indoor units in the same group Note The following models require two addresses PEFY AF1200CFM and PEFY AF1200CFM R Assign an address that equals the lowest indoor unit address in the same refri...

Страница 5: ... b Wall surface installation b 1 To route the cable through the wall b 2 To route the cable along the wall surface 4 Preparation 1 Install a breaker on the power supply unit side before installing the controller 2 Select an installation site for the Touch Controller Install the controller at the user s eye level for easy operation Ensure there is enough clearance space as shown in the figure at ri...

Страница 6: ...the detergent with a wet cloth and wipe off water with a dry cloth Take appropriate measures against electrical noise interference when installing the air conditioners in hospitals or facilities with radio communication capabilities Inverter high frequency medical or wireless communication equipment as well as power generators may cause the air conditioning system to malfunction Air conditioning s...

Страница 7: ...remote controller will not be allowed and the ON OFF and Prohibit Permit settings on the Touch Controller cannot be changed Timer operation will not function ON OFF operation from the local remote controller will not be allowed and the ON OFF and Prohibit Permit settings on the Touch Controller cannot be changed Timer operation will not function The ON signal pulse width should be set to a value b...

Страница 8: ...ing unit will not be automatically restored The air conditioning units must be started up manually If the type of signal assigned to the external input contact is ON OFF the units that are stopped will start operation after the input signal changes from OFF to ON Conversely the units that are in operation will stop after the input signal changes from ON to OFF B Pulse signal If the incoming signal...

Страница 9: ...lect a power supply suitable for the relays used 12 VDC or 24 VDC 2 Use a diode at each end of the relay coil Each element will turn on when an error occurs during operation The maximum length of extension cable is 10 m 32 ft Use a cable of 0 3 mm 22AWG or thicker Insulate the area with vinyl tape where the controller cable and the extension cable are connected Relays lamps diode extension cables ...

Отзывы: