background image

1

Air-conditioner Control System

Touch Controller  TC-24A

Installation Manual

For distribution to dealers and contractors only

Thoroughly read the following safety precautions prior to installation. Refer to the Initial Setting Manual and the Instruction Book for 

information on operating or making the settings for the controller. Also, refer to the air conditioning unit installation manuals for how to 

connect cables or how to install air conditioning units.

Thoroughly read the following safety precautions prior to installation.

Observe the following precautions to ensure safety.

Nomenclature

After reading this manual, pass it on to the end user to retain for future reference.

Keep this manual for future reference and refer to it as necessary. This manual should be made available to those who repair or relocate 

the controller. Make sure that the manual is passed on to any future TC-24A users.

General precautions

WARNING

Indicates a risk of death or serious injury.

CAUTION

Indicates a risk of serious injury or structural damage.

All electric work must be performed by qualified personnel.

1 Safety Precautions

WARNING

(Prohibited actions)

(Do not touch)

(No water)

(No wet hands)

(Fire hazards)

(Injury hazards)

(Important actions) (Grounding required)

(Electric shock hazards)

Do not install the controller where there is a risk of leaking flammable gas.

If flammable gas accumulates around the controller, it may ignite and cause a 

fire or explosion.

To reduce the risk of shorting, current leakage, electric shock, malfunctions, 

smoke, or fire, do not install the controller in a place exposed to water or in a 

condensing environment.

Controller  must  be  installed  by  qualified  personnel  according  to  the 

instructions detailed in the Installation Manual.

Improper installation may result in electric shock or fire.

Properly  dispose  of  the  packing  materials.  Plastic  bags  pose  suffocation 

hazard to children. 

Take  appropriate  safety  measures  against  earthquakes  to  prevent  the 

controller from causing injury.

To  prevent  injury,  install  the  controller  on  a  flat  surface  strong  enough  to 

support its weight.

To reduce the risk of fire or explosion, do not place flammable materials or 

use flammable sprays around the controller.

To reduce the risk of damage to the controller, do not directly spray insecticide 

or other flammable sprays on the controller. 

To  reduce  the  risk  of  injury,  wear  protective  gear  when  working  on  the 

controller.

To reduce the risk of electric shock or malfunctions, do not touch the touch 

panel, switches, or buttons with a pointy or sharp object.

To reduce the risk of injury and electric shock, avoid contact with sharp edges 

of certain parts.

To avoid injury from broken glass, do not apply excessive force on the glass 

parts.

Do not install the unit in a place where large amounts of oil, steam, organic 

solvents,  or  corrosive  gases,  such  as  sulfuric  gas,  are  present  or  where 

acidic/alkaline solutions or sprays are used frequently. These substances can 

compromise the performance of the unit or cause certain components of the 

unit to corrode, which can result in electric shock, malfunctions, smoke, or fire.

Precautions during installation

WARNING

CAUTION

To reduce the risk of shorting, current leakage, electric shock, malfunctions, 

smoke, or fire, do not wash the controller with water or any other liquid.

Properly  install  all  required  covers  to  keep  moisture  and  dust  out  of  the 

controller. Dust accumulation and water can cause electric shock, smoke, or fire.

To  reduce  the  risk  of  electric  shock,  malfunctions,  smoke  or  fire,  do  not 

operate the switches/buttons or touch other electrical parts with wet hands.

CAUTION

To  reduce  the  risk  of  injury  or  electric  shock,  before  spraying  a  chemical 

around the controller, stop the operation and cover the controller.

To reduce the risk of injury, keep children away while installing, inspecting, or 

repairing the controller.

To reduce the risk of injury or electric shock, stop the operation and switch off 

the power supply before cleaning, maintaining, or inspecting the controller.

Содержание TC-24A

Страница 1: ...ate safety measures against earthquakes to prevent the controller from causing injury To prevent injury install the controller on a flat surface strong enough to support its weight To reduce the risk of fire or explosion do not place flammable materials or use flammable sprays around the controller To reduce the risk of damage to the controller do not directly spray insecticide or other flammable ...

Страница 2: ...the detergent with a wet cloth and wipe off water with a dry cloth Take appropriate measures against electrical noise interference when installing the air conditioners in hospitals or facilities with radio communication capabilities Inverter high frequency medical or wireless communication equipment as well as power generators may cause the air conditioning system to malfunction Air conditioning s...

Страница 3: ...through the M NET transmission line to maintain communica tion during power failure Refer to the CITY MULTI DATABOOK for details The total power consumption of the connected devices should not exceed the capacity of the power supply units The Design Tool by MITSUBISHI ELECTRIC allows its user to design air conditioning systems easily TC 24A is compatible with the Design Tool version 3 71 or later ...

Страница 4: ...the field for registering the address of the system controller in each group Address setting Assign the lowest address to the main indoor unit in the group and assign sequential addresses to the rest of the indoor units in the same group Note The following models require two addresses PEFY AF1200CFM and PEFY AF1200CFM R Assign an address that equals the lowest indoor unit address in the same refri...

Страница 5: ... b Wall surface installation b 1 To route the cable through the wall b 2 To route the cable along the wall surface 4 Preparation 1 Install a breaker on the power supply unit side before installing the controller 2 Select an installation site for the Touch Controller Install the controller at the user s eye level for easy operation Ensure there is enough clearance space as shown in the figure at ri...

Страница 6: ...the detergent with a wet cloth and wipe off water with a dry cloth Take appropriate measures against electrical noise interference when installing the air conditioners in hospitals or facilities with radio communication capabilities Inverter high frequency medical or wireless communication equipment as well as power generators may cause the air conditioning system to malfunction Air conditioning s...

Страница 7: ...remote controller will not be allowed and the ON OFF and Prohibit Permit settings on the Touch Controller cannot be changed Timer operation will not function ON OFF operation from the local remote controller will not be allowed and the ON OFF and Prohibit Permit settings on the Touch Controller cannot be changed Timer operation will not function The ON signal pulse width should be set to a value b...

Страница 8: ...ing unit will not be automatically restored The air conditioning units must be started up manually If the type of signal assigned to the external input contact is ON OFF the units that are stopped will start operation after the input signal changes from OFF to ON Conversely the units that are in operation will stop after the input signal changes from ON to OFF B Pulse signal If the incoming signal...

Страница 9: ...lect a power supply suitable for the relays used 12 VDC or 24 VDC 2 Use a diode at each end of the relay coil Each element will turn on when an error occurs during operation The maximum length of extension cable is 10 m 32 ft Use a cable of 0 3 mm 22AWG or thicker Insulate the area with vinyl tape where the controller cable and the extension cable are connected Relays lamps diode extension cables ...

Отзывы: