background image

2

To reduce the risk of damage to the controller, malfunctions, smoke, or fire, do 

not connect the power cable to the signal terminal block.

To reduce the risk of current leakage, overheating, smoke, or fire, use properly 

rated cables with adequate current carrying capacity.

All electric work must be performed by a qualified electrician according to the 

local  regulations,  standards,  and  the  instructions  detailed  in  the  Installation 

Manual.Capacity shortage to the power supply circuit or improper installation 

may result in malfunction, electric shock, smoke, or fire.

Use properly rated breakers and fuses (breaker, local switch <  fuse>, 

no-fuse breaker).The use of a breaker with a breaking capacity greater than the 

specified capacity may cause electric shock, malfunctions, smoke, or fire.

Proper grounding must be provided by a licensed electrician.

Do not connect the grounding wire to a gas pipe, water pipe, lightning rod, or 

telephone wire. Improper grounding may result in electric shock, smoke, fire, or 

malfunction due to electrical noise interference. 

To  reduce  the  risk  of  electric  shock,  install  a  breaker  and  a  residual  current 

circuit breaker on the power supply. To reduce the risk of electric shock, smoke, 

or fire, install a breaker for each controller.

The controller should be repaired or moved only by qualified personnel. Do not 

disassemble or modify the controller.

Improper installation or repair may cause injury, electric shock, or fire.

Properly secure the cables in place and provide adequate slack in the cables 

so  as  not  to  stress  the  terminals.Improperly  connected  cables  may  break, 

overheat, and cause smoke or fire.

To reduce the risk of injury or electric shock, switch off the main power before 

performing electrical work.

Precautions during wiring

WARNING

Precautions for moving or repairing the controller

WARNING

To avoid damage to the controller, use appropriate tools to install, inspect, or repair 

the controller.

To avoid malfunctions, do not bundle power cables and signal cables together, or 

place them in the same metallic conduit.

To avoid discoloration, do not use benzene, thinner, or chemical rag to clean the 

controller.To clean the controller, wipe with a soft cloth soaked in water with mild 

detergent, wipe off the detergent with a wet cloth, and wipe off water with a dry cloth.

Take appropriate measures against electrical noise interference when installing the 

air conditioners in hospitals or facilities with radio communication capabilities.

Inverter, high-frequency medical, or wireless communication equipment as well as 

power  generators  may  cause  the  air  conditioning  system  to  malfunction.  Air 

conditioning  system  may  also  adversely  affect  the  operation  of  these  types  of 

equipment by creating electrical noise.

TC-24A  is  designed  for  exclusive  use  with  the  Building  Management  System  by 

Mitsubishi  Electric.  The  use  of  this  controller  for  with  other  systems  or  for  other 

purposes may cause malfunctions. 

Do not use solderless terminals to connect cables to the terminal block. 

Solderless terminals may come in contact with the circuit board and cause malfunc-

tions or damage the controller cover.

To avoid deformation and malfunction, do not install the remote controller in direct 

sunlight or where the ambient temperature may exceed 40ºC (104ºF) or drop below 

0ºC (32ºF).

To avoid damage to the controller, do not overtighten the screws.

To avoid damage to the controller, provide protection against static electricity.

To avoid damage to the controller, do not make holes on the controller cover. 

Additional precautions

To reduce the risk of shorting, electric shock, fire, or malfunction, do not touch 

the circuit board with tools or with your hands, and do not allow dust to accumu-

late on the circuit board.

CAUTION

CAUTION

To  reduce  the  risk  of  electric  shock,  malfunctions,  or  fire,  seal  the  gap 

between the cables and cable access holes with putty.

To  reduce  the  risk  of  electric  shock,  shorting,  or  malfunctions,  keep  wire 

pieces and sheath shavings out of the terminal block.

To reduce the risk of shorting, current leakage, electric shock, or malfunc-

tions, keep the cables out of contact with controller edges.

2 Parts list

The package contains the following parts.

*1 ISO metric screw thread

1. Touch Controller

2. Mounting bracket

Parts

Touch Controller
Mounting bracket
M4.1 wood screws x 16 *1
(Use to attach the mounting bracket to a wall.)
M4 Roundhead cross slot screws x 30 *1
(Use to attach the mounting bracket to an electric box.)
M4 roundhead screws with spring washers/washers x 20
(Use to attach the mounting bracket to the controller.) *1
Installation Manual (This manual)
Initial Setting Manual
Instruction Book

1.
2.

3.

4.

5.

6.
7.
8.

Qty.

1
1

4

2

2

1
1
1

Содержание TC-24A

Страница 1: ...ate safety measures against earthquakes to prevent the controller from causing injury To prevent injury install the controller on a flat surface strong enough to support its weight To reduce the risk of fire or explosion do not place flammable materials or use flammable sprays around the controller To reduce the risk of damage to the controller do not directly spray insecticide or other flammable ...

Страница 2: ...the detergent with a wet cloth and wipe off water with a dry cloth Take appropriate measures against electrical noise interference when installing the air conditioners in hospitals or facilities with radio communication capabilities Inverter high frequency medical or wireless communication equipment as well as power generators may cause the air conditioning system to malfunction Air conditioning s...

Страница 3: ...through the M NET transmission line to maintain communica tion during power failure Refer to the CITY MULTI DATABOOK for details The total power consumption of the connected devices should not exceed the capacity of the power supply units The Design Tool by MITSUBISHI ELECTRIC allows its user to design air conditioning systems easily TC 24A is compatible with the Design Tool version 3 71 or later ...

Страница 4: ...the field for registering the address of the system controller in each group Address setting Assign the lowest address to the main indoor unit in the group and assign sequential addresses to the rest of the indoor units in the same group Note The following models require two addresses PEFY AF1200CFM and PEFY AF1200CFM R Assign an address that equals the lowest indoor unit address in the same refri...

Страница 5: ... b Wall surface installation b 1 To route the cable through the wall b 2 To route the cable along the wall surface 4 Preparation 1 Install a breaker on the power supply unit side before installing the controller 2 Select an installation site for the Touch Controller Install the controller at the user s eye level for easy operation Ensure there is enough clearance space as shown in the figure at ri...

Страница 6: ...the detergent with a wet cloth and wipe off water with a dry cloth Take appropriate measures against electrical noise interference when installing the air conditioners in hospitals or facilities with radio communication capabilities Inverter high frequency medical or wireless communication equipment as well as power generators may cause the air conditioning system to malfunction Air conditioning s...

Страница 7: ...remote controller will not be allowed and the ON OFF and Prohibit Permit settings on the Touch Controller cannot be changed Timer operation will not function ON OFF operation from the local remote controller will not be allowed and the ON OFF and Prohibit Permit settings on the Touch Controller cannot be changed Timer operation will not function The ON signal pulse width should be set to a value b...

Страница 8: ...ing unit will not be automatically restored The air conditioning units must be started up manually If the type of signal assigned to the external input contact is ON OFF the units that are stopped will start operation after the input signal changes from OFF to ON Conversely the units that are in operation will stop after the input signal changes from ON to OFF B Pulse signal If the incoming signal...

Страница 9: ...lect a power supply suitable for the relays used 12 VDC or 24 VDC 2 Use a diode at each end of the relay coil Each element will turn on when an error occurs during operation The maximum length of extension cable is 10 m 32 ft Use a cable of 0 3 mm 22AWG or thicker Insulate the area with vinyl tape where the controller cable and the extension cable are connected Relays lamps diode extension cables ...

Отзывы: